Commit Graph

57 Commits

Author SHA1 Message Date
znetsixe
2dd419dbf4 Editor: nudge dashed lines themselves, revert tank height
Reverts the tank-bigger approach from last commit. Instead of
scaling the tank and keeping strict proportionality, the dashed
threshold lines are now nudged apart directly so each gets a
guaranteed 36-px vertical gap. Inputs and labels align with the
lines (no more leader lines needed).

Trade-off: the diagram is now an ordered schematic, not a strictly
to-scale rendering. Values are still shown next to each line via
the input boxes, and the value ordering is preserved. For an editor
where the goal is entering parameters, readability wins over scale
fidelity.

Sizing reverted:
  viewBox    620 → 430
  tank h     520 → 340
  botY       560 → 380

Behavior:
  GAP        30 → 36 (more visible space between dashed lines)
  placeItem  takes a single y now (line + input + label + unit
             share it); leader-line mechanism kept as hidden
             plumbing in case we switch back to proportional later

Dead-volume band now anchors to the (possibly-nudged) outflow line
instead of the proportional y so it still visually meets the line
cleanly.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-23 12:10:23 +02:00
znetsixe
785d036dc6 Editor: taller tank — more vertical room between threshold lines
Tank height 340 → 520 px (viewBox 480 → 620). Lines that were
cramped in the bottom metre now have ~50 % more room, so:

- The Outlet arrow no longer visually crowds the minLevel line
- Dashed threshold lines (dryRunLevel, minLevel, outflowLevel)
  have visible breathing room between them for typical wastewater
  values where they sit in the bottom 1 m
- Input-stack GAP bumped 26 → 30 px to match the extra vertical
  real estate

Pure layout change — same proportional mapping, same nudging
algorithm, just more canvas. Floor/datum label and ordering-
warning ribbon positions shifted accordingly.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-23 11:41:03 +02:00
znetsixe
65fe68b87f Editor: nudge crowded threshold inputs off their lines with leader lines
When real wastewater values cluster near the basin floor (minLevel,
dryRunLevel, outflowLevel are often within a few cm of each other),
the threshold inputs were stacking on top of each other. Now:

- Threshold LINE stays at its proportional y on the tank (visual
  truth: that's where the level actually is).
- Input BOX / label / unit are positioned in a nudged right-column
  stack with a minimum 26-px gap so they never overlap.
- A dashed grey leader line connects each line to its input when
  they had to be pulled apart, so the association stays visible.
- Items are sorted by ideal y top-down and nudged downward once;
  basinHeight is pinned at the rim and acts as the anchor.

Also: viewBox extended 430 → 480 so the bottom-of-stack items have
room below the tank when the bottom cluster is tight. Warning ribbon
moved to y=460 accordingly.

No schema change; purely UI layout.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-23 10:41:16 +02:00
znetsixe
d641d2248d Editor: interactive basin diagram — inputs placed at each threshold line
Replaces the static parameters-diagram-above-form-rows layout with a
single interactive SVG where every threshold input sits directly on
the tank at its proportional y-position. Typing a value repositions
the corresponding line + input + label live.

What moved into the diagram (via <foreignObject> holding real
<input> elements with their existing node-input-* IDs so Node-RED
save/restore is untouched):

  basinHeight    — top of tank (fixed at rim by definition)
  overflowLevel  — weir crest (red, dashed)
  maxLevel       — 100 % demand line (orange, dashed)
  startLevel     — ramp-start line (green, dashed)
  minLevel       — MGC-shutdown line (purple, dashed)
  inflowLevel    — Inlet arrow + input on left
  outflowLevel   — Outlet arrow + input on right
  dryRunLevel    — read-only, computed from outflow × (1+dryRunPct/100)

Also in the diagram:
- Dead-volume band fills the area below outflowLevel dynamically
- Warning ribbon appears below the tank if ordering invariants break
  (mirrors specificClass._validateThresholdOrdering)
- All positions scale against the user's basinHeight; if empty, a
  default 5 m scale is used just to keep the diagram readable

What stayed as regular form rows:
- Basin Volume (m³) — not a height, can't be placed on a y-axis
- minLevel / startLevel / maxLevel were in the Control Strategy >
  Level-based section; removed from there and moved into the diagram
  (the level-based subsection now contains a one-line pointer)
- Safety % inputs (dryRun, overfill) stay in the Safety section with
  their derived-level readouts, now synced with the diagram

No schema changes, no field additions, no behaviour changes in the
runtime. Pure editor-UX.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-23 10:28:18 +02:00
znetsixe
12904b4902 Editor: inline parameters diagram at top of Basin Geometry
~3 KB inline SVG showing the 5 threshold lines + inlet/outlet pipe
arrows + floor datum, using the same names as the editor fields
(basinHeight, overflowLevel, maxLevel, startLevel, minLevel,
dryRunLevel). No new inputs — purely a visual reminder of what
each field refers to, so operators don't have to alt-tab to the
wiki to figure out which pipe edge to measure.

Wrapped in <details open> so users can collapse it once they
know the layout — no forced scroll through the diagram on every
edit session.

Matches the vocabulary in wiki/diagrams/basin-model.drawio.svg
(inlet = bottom of pipe, outlet = top of pipe, 0 m datum at
basin floor, dryRunLevel derived from %).

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-23 10:19:23 +02:00
znetsixe
1ebbcb62cc Editor: pipe-edge conventions + live derived safety levels
### P1 — match diagram naming (labels only, no schema change)

- "Inlet Elevation"    → "Inlet (bottom of pipe, m)"
- "Outlet Elevation"   → "Outlet (top of pipe, m)"
- "Overflow Level"     → "Overflow (weir crest, m)"
- "Basin Bottom (m Refheight)" → "Basin floor above datum (m)"
- Added a one-line banner at the top of Basin Geometry:
  "All heights measured from the basin floor (0 m)."

These map directly to the clarifications added to basin-model.drawio.svg
so editor and diagram speak the same vocabulary.

### P3 — live derived safety levels next to the % fields

Low/High Volume Threshold fields now show the resulting trip level
live as the operator types:

  Low Volume Threshold (%)  [ 2  ]  → dryRunLevel ≈ 0.21 m
  High Volume Threshold (%) [ 98 ]  → overfillLevel ≈ 4.41 m

Recomputed on every input/change of outflowLevel, inflowLevel,
overflowLevel, minHeightBasedOn, or either %. Pure UI feedback —
no schema change, no save-side change, same formulas as
specificClass._validateThresholdOrdering().

Also includes the user's latest basin-model.drawio.svg update
(inlet=bottom/outlet=top labels + datum annotation).

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-23 09:58:17 +02:00
znetsixe
3e13512a83 Rename eval/ → simulations/ and fix log-write bug
Per discussion: "test" and "eval" overlap in meaning; "simulations"
is more honest about what's actually happening — scripted plant
inputs driving a physics sim, then recorded for analysis.

Rename scope:
- eval/ → simulations/ (tracked as git renames)
- Internal references in run.js and README.md updated
- wiki/modes/mpc.md link updated

Also fixes a log-write bug noticed during the rename:
- run.js didn't mkdir simulations/logs/ before createWriteStream,
  so the stream opened into a potentially non-existent dir and the
  file never materialised. Added fs.mkdirSync(..., recursive:true).
- end() wasn't awaited, so the process could exit before the stream
  flushed. Now awaits the 'finish' event. Confirmed: 1200 records
  actually land in simulations/logs/<scenario>.jsonl.
- Added simulations/logs/.gitignore so future JSONL artefacts stay
  out of the repo but the dir remains tracked.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 17:46:10 +02:00
znetsixe
66fd3feff8 Add eval harness + Tier 2/3 mode template pages
### eval/ (scenario-based evaluation)

Complements the unit tests under test/basic. Scenarios fluctuate inputs
over simulated time, record every tick to JSONL, print a summary
table + event log, and check expectations. Complementary to unit
tests — these answer "how does the system respond to this input
profile" rather than "is this function correct".

- eval/run.js             — driver; monkey-patches Date.now so the
                            volume integrator ticks at 1 s/iter
                            regardless of wall-clock
- eval/scenarios/         — one file per scenario
  - levelbased-steady.js  — constant inflow, demand converges
  - levelbased-storm.js   — inflow surge, demand saturates
  - safety-dry-run-trip.js — manual mode, empty basin, safety trips
- eval/formatters/table.js — ASCII summary of sampled ticks
- eval/logs/              — per-scenario JSONL output (one line per tick)
- eval/README.md          — usage + scenario file shape + how to pipe
                            into InfluxDB/Grafana

All three starter scenarios PASS with their expectations.

### wiki/modes/ (tier template pages)

The levelbased page templated Tier-1 modes (static transfer function).
Added worked examples for the other two tiers so all mode pages share
a common skeleton and new modes have something concrete to imitate:

- flowbased.md   — Tier 2 (PID on measured outflow)
- powerbased.md  — Tier 2 (levelbased curve clipped by grid power budget)
- mpc.md         — Tier 3 (optimisation + forecast; block diagram +
                           scenario time-series instead of a fixed curve)

- modes/README.md — updated with the three-tier classification table
                    and diagram-type-per-tier guidance

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 16:49:41 +02:00
znetsixe
016433abe6 Add threshold guardrails, fix calibratePredictedLevel bug, rewrite tests
### Guardrails (specificClass.js)

New _validateThresholdOrdering() runs in the constructor. Checks every
ordered pair of basin + control + derived-safety levels and logs a
warning for each violation; returns the list as this.thresholdIssues
so tests and the eval harness can inspect. Non-fatal — we prefer a
running-but-warned station to a refusal-to-start (availability-first).

Strict invariants (bottom → top):
  0 < outflowLevel < inflowLevel < overflowLevel ≤ basinHeight
  dryRunLevel ≤ minLevel ≤ startLevel < maxLevel ≤ overfillLevel

Uses a list-of-checks pattern rather than a switch — easier to add new
invariants without reflowing cases, and the list itself is readable
documentation.

### Bug fix (specificClass.js)

calibratePredictedLevel was writing the volume value into the LEVEL
slot. Root cause: MeasurementContainer is stateful — its type()/
variant()/position() calls mutate the container's own cursor, so
caching chain references (const levelChain = ...; const volumeChain
= ...) doesn't isolate them. The second cached chain ended up sharing
the state of the last type() call. Rebuilt chains fresh each time,
matching the calibratePredictedVolume pattern that already worked.

### Tests (test/basic/specificClass.test.js)

Ported from Jest to node:test + node:assert — the project's standard
per .claude/rules/testing.md. Deleted the stale test/specificClass.test.js
(tests referenced methods that no longer exist post-rename).

New coverage, 42 passing subtests:
- Basin geometry derivations + minHeightBasedOn
- Level/volume roundtrip
- Threshold guardrails (5 violation cases)
- Direction derivation
- Mode change accept/reject
- Calibration (volume and level paths — catches the bug above)
- Levelbased control zones (STOP / DEAD ZONE / RAMP / saturate)
- getOutput flattening
- setManualInflow

Run with: node --test test/basic/*.test.js

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 16:38:41 +02:00
znetsixe
a2189457f6 Rename basin/control thresholds to wiki naming; trim stale comments
Aligns the code with the 5-threshold convention used throughout the
wiki (basin model + per-mode transfer-function diagrams):

  heightInlet       → inflowLevel
  heightOutlet      → outflowLevel
  heightOverflow    → overflowLevel
  stopLevel         → minLevel
  maxFlowLevel      → maxLevel
  minFlowLevel      → removed (collapsed into startLevel; they were
                      always supposed to hold the same value)
  minVolIn          → minVolAtInflow
  minVolOut         → minVolAtOutflow
  maxVolOverflow    → maxVolAtOverflow
  startLevel        → unchanged

Config schema (generalFunctions/src/configs/pumpingStation.json) is
updated in a parallel commit in that submodule.

Also:
- Stripped the ~150-line ASCII basin diagram from initBasinProperties
  JSDoc; it now points at wiki/functional-description.md#basin-model.
- Trimmed the top-of-class JSDoc — the config-sections breakdown was
  drifting from the schema anyway; wiki is now the source of truth.
- Tidied inline comments in _controlLevelBased, _scaleLevelToFlowPercent.
- Editor order reshuffled to match the bottom→top basin order:
  minLevel, startLevel, maxLevel.

Breaking change for saved flows: existing pumpingStation nodes in
production flows reference the old field names and will need to be
re-entered in the editor. No compat shim — node is RnD/trial.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 16:13:59 +02:00
znetsixe
4637448c49 Add modes/ section with levelbased page as the template
Introduces the pattern: basin model is the shared canvas (mode-agnostic
physics); each control mode is its own page under wiki/modes/ plus a
demand-vs-level transfer-function diagram under wiki/diagrams/modes/.

- wiki/modes/README.md — index + per-mode page template (inputs,
  threshold policy, demand formula, edge cases, related)
- wiki/modes/levelbased.md — first worked example using the new naming
  convention (dryRunLevel / minLevel / startLevel / maxLevel /
  overflowLevel). Forward-looking — the code still uses the old names
  until the pending rename refactor.
- wiki/diagrams/modes/levelbased.drawio.svg — transfer-function plot
  (zones: STOP / DEAD ZONE / RAMP / SATURATE, safety trips outside the
  plot). Round-trippable via embedded drawio XML.
- functional-description.md — replaced the inline levelbased/manual
  subsection with a table pointing at the modes/ pages. Removed the
  old control-zones ASCII diagram reference (superseded by the
  per-mode transfer function).
- wiki/README.md — added Control modes entry + diagrams/modes/ pointer.

The remaining placeholder modes (flowbased, pressureBased,
percentageBased, powerBased, hybrid, manual) can each fill in the
template independently.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 15:45:01 +02:00
znetsixe
61e0688f73 Make starter SVG diagrams round-trippable in draw.io
Each <name>.drawio.svg now has the corresponding <name>.drawio XML
embedded as content="..." on the root <svg> element. Opening the
SVG in draw.io (File → Open, or drag-drop) loads the full editable
model — no need to keep the .drawio file around for editing.

Updated diagrams/README.md to reflect that both file formats are
now round-trippable from the start.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 13:00:16 +02:00
znetsixe
0ff55f5e9c Add wiki/ folder with functional description + draw.io diagrams
Moves documentation into the code repo so code, docs, and diagrams
version-lock and review together. Previous location was
pumpingStation.wiki.git; that will shrink to a pointer.

Contents:
- wiki/README.md — doc index
- wiki/functional-description.md — operator-facing reference derived
  from src/specificClass.js: basin model, net-flow selection,
  level-based control zones, safety interlocks, registration topology
- wiki/diagrams/ — editable draw.io sources paired with SVG exports
  (basin-model, control-zones, safety-rules) + README with the
  open/edit/export/commit workflow

The .drawio files are rough starters; iterate in draw.io and re-export.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-22 12:19:26 +02:00
znetsixe
5e2ebe4d96 fix(safety): overfill must keep pumps running, not shut them down
Two hard rules for the safety controller, matching sewer PS design:

1. BELOW stopLevel (dry-run): pumps CANNOT start.
   All downstream equipment shut down. safetyControllerActive=true
   blocks _controlLogic so level control can't restart pumps.
   Only manual override or emergency can change this.

2. ABOVE overflow level (overfill): pumps CANNOT stop.
   Only UPSTREAM equipment is shut down (stop more water coming in).
   Machine groups (downstream pumps) are NOT shut down — they must
   keep draining. safetyControllerActive is NOT set, so _controlLogic
   continues commanding pumps at the demand dictated by the level
   curve (which is >100% near overflow = all pumps at maximum).
   Only manual override or emergency stop can shut pumps during
   an overfill event.

Previously the overfill branch called turnOffAllMachines() on machine
groups AND set safetyControllerActive=true, which shut down the pumps
and blocked level control from restarting them — exactly backwards
for a sewer pumping station where the sewage keeps coming.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-14 14:10:23 +02:00
znetsixe
e8dd657b4f fix: continuous proportional control — eliminate dead zone between start/stop levels
Previously PS only sent demand to MGC when level > startLevel AND
direction === 'filling'. Between startLevel and stopLevel (the 'dead
zone'), pumps kept running at their last commanded setpoint with no
updates. Basin drained uncontrolled until hitting stopLevel.

Fix: send percControl on every tick when level > stopLevel. The
_scaleLevelToFlowPercent math naturally gives:
  - Positive % above startLevel (pumps ramp up)
  - 0% at exactly startLevel (pumps at minimum)
  - Negative % below startLevel → clamped to 0 → MGC scales to 0
    → pumps ramp down gracefully

This creates smooth visible ramp-up and ramp-down as the basin fills
and drains, instead of a sudden jump at startLevel and stuck ctrl in
the dead zone.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-14 13:42:43 +02:00
znetsixe
c62d8bc275 fix: deduplicate predicted-flow child registration + single event subscription
Three bugs in registerChild caused multi-counted outflow in _updatePredictedVolume:

1. machinegroup registered twice (line 66 + line 70 both called
   _registerPredictedFlowChild). Fixed: only register in the
   machinegroup branch.

2. Individual machines registered alongside their machinegroup parent.
   Each pump's predicted flow is already included in MGC's aggregated
   total — subscribing to both triple-counts. Fixed: only register
   individual machines when no machinegroup is present (direct-wired
   pumps without MGC).

3. _registerPredictedFlowChild subscribed to BOTH flow.predicted.downstream
   AND flow.predicted.atequipment events. These carry the same total flow
   on two event names — the handler wrote the value twice per tick.
   Fixed: subscribe to ONE event per child (downstream for outflow,
   upstream for inflow).

These are generalizable patterns:
- When a group aggregator exists, subscribe to IT, not its children.
- One event per measurement type per child — pick the most specific.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-14 13:10:16 +02:00
znetsixe
f869296832 feat: level-based control now reaches machine groups + manual Qd forwarding
Two additions to pumpingStation:

1. _controlLevelBased now calls _applyMachineGroupLevelControl in
   addition to _applyMachineLevelControl when the basin is filling
   above startLevel. Previously only direct-child machines received
   the level-based percent-control signal; in a hierarchical topology
   (PS → MGC → pumps) the machines sit under MGC and PS.machines is
   empty, so the level control never reached them.

2. New 'Qd' input topic + forwardDemandToChildren() method. When PS
   is in 'manual' mode (matching the pattern from rotatingMachine's
   virtualControl), operator demand from a dashboard slider is forwarded
   to all child machine groups and direct machines. When PS is in any
   other mode (levelbased, flowbased, etc.), the Qd msg is silently
   dropped with a debug log so the automatic control isn't overridden.

No breaking changes — existing flows that don't send 'Qd' are unaffected,
and _controlLevelBased's additional call to machineGroupLevelControl
is a no-op when no machine groups are registered.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-14 08:27:11 +02:00
znetsixe
9f430cebb5 docs: add CLAUDE.md with S88 classification and superproject rule reference
References the flow-layout rule set in the EVOLV superproject
(.claude/rules/node-red-flow-layout.md) so Claude Code sessions working
in this repo know the S88 level, colour, and placement lane for this node.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-04-14 07:47:23 +02:00
znetsixe
7d05d37678 Merge commit '762770a' into HEAD
# Conflicts:
#	pumpingStation.html
#	src/nodeClass.js
#	src/specificClass.js
2026-03-31 18:20:09 +02:00
Rene De Ren
762770a063 Expose output format selectors in editor 2026-03-12 16:39:25 +01:00
Rene De Ren
3ff76228eb fix: guard demo IIFE with require.main check
Prevents demo code from executing when module is required by Node-RED,
which caused crashes due to missing measurement data.

Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>
2026-03-11 16:38:08 +01:00
Rene De Ren
f01b0bcb19 fix: rename _calcTimeRemaining to _calcRemainingTime + add tests
Fix method name mismatch in tick() that called non-existent _calcTimeRemaining
instead of _calcRemainingTime. Add 27 unit tests for specificClass.

Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>
2026-03-11 16:31:47 +01:00
Rene De Ren
4e098eefaa refactor: adopt POSITIONS constants and fix ESLint warnings
Replace hardcoded position strings with POSITIONS.* constants.
Prefix unused variables with _ to resolve no-unused-vars warnings.
Fix no-prototype-builtins where applicable.

Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>
2026-03-11 15:35:28 +01:00
Rene De Ren
90f87bb538 Migrate _loadConfig to use ConfigManager.buildConfig()
Replaces manual base config construction with shared buildConfig() method.
Node now only specifies domain-specific config sections.

Part of #1: Extract base config schema

Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>
2026-03-11 14:59:35 +01:00
Rene De Ren
8fe9c7ec05 Fix ESLint errors and bugs
Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>
2026-03-11 13:39:57 +01:00
znetsixe
7efd3b0a07 bug fixes 2025-11-30 20:13:21 +01:00
znetsixe
c81ee1b470 fixed change mode and control logic method 2025-11-30 17:46:07 +01:00
znetsixe
955c17a466 bug fixes 2025-11-30 09:24:18 +01:00
Rene De ren
052ded7b6e fixes 2025-11-28 16:29:05 +01:00
znetsixe
321ea33bf7 rebuilding pumping station NOT WORKING 2025-11-28 09:59:16 +01:00
znetsixe
288bd244dd updating to corrospend with reality 2025-11-27 17:46:24 +01:00
znetsixe
d91609b3a4 updates to safety features 2025-11-25 14:57:39 +01:00
znetsixe
5a575a29fe updated pumpingstation 2025-11-20 12:15:46 +01:00
znetsixe
0a6c7ee2e1 Further bug fixes and optimized level control for groups and machines alike 2025-11-13 19:37:41 +01:00
znetsixe
4cc529b1c2 Fixes next idle machine for level control 2025-11-12 17:37:09 +01:00
znetsixe
fbfcec4b47 Added simpel case for level control 2025-11-10 16:20:23 +01:00
znetsixe
43eb97407f added safeguarding when vol gets too low for machines, 2025-11-07 15:07:56 +01:00
znetsixe
9e4b149b64 fixed multiple children being able to pull and push to pumpingstation 2025-11-06 16:46:54 +01:00
znetsixe
1848486f1c bug fixes output formatting 2025-11-06 11:19:20 +01:00
znetsixe
d44cbc978b updates visual 2025-11-03 09:17:22 +01:00
znetsixe
f243761f00 Updated node status 2025-11-03 07:42:51 +01:00
znetsixe
2a31c7ec69 working pumpingstation with machines 2025-10-28 17:04:26 +01:00
znetsixe
69f68adffe testing codex 2025-10-27 19:55:48 +01:00
znetsixe
5a1eff37d7 Need to remove wobble on level only 2025-10-27 17:45:48 +01:00
znetsixe
e8f9207a92 some major design choises updated 2025-10-27 16:39:06 +01:00
znetsixe
6e9ae9fc7e Need to stich everything together then V1.0 is done. 2025-10-23 18:04:18 +02:00
znetsixe
371f3c65e7 updated retrieval mechanism 2025-10-23 09:51:54 +02:00
znetsixe
b8b7871e38 update before closing 2025-10-21 13:44:31 +02:00
znetsixe
f29aa4f5af latest version 2025-10-21 12:45:19 +02:00
znetsixe
65807881d5 working pumpingstation level and net flow calc 2025-10-16 14:44:45 +02:00