znetsixe f869296832 feat: level-based control now reaches machine groups + manual Qd forwarding
Two additions to pumpingStation:

1. _controlLevelBased now calls _applyMachineGroupLevelControl in
   addition to _applyMachineLevelControl when the basin is filling
   above startLevel. Previously only direct-child machines received
   the level-based percent-control signal; in a hierarchical topology
   (PS → MGC → pumps) the machines sit under MGC and PS.machines is
   empty, so the level control never reached them.

2. New 'Qd' input topic + forwardDemandToChildren() method. When PS
   is in 'manual' mode (matching the pattern from rotatingMachine's
   virtualControl), operator demand from a dashboard slider is forwarded
   to all child machine groups and direct machines. When PS is in any
   other mode (levelbased, flowbased, etc.), the Qd msg is silently
   dropped with a debug log so the automatic control isn't overridden.

No breaking changes — existing flows that don't send 'Qd' are unaffected,
and _controlLevelBased's additional call to machineGroupLevelControl
is a no-op when no machine groups are registered.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>