znetsixe 5e2ebe4d96 fix(safety): overfill must keep pumps running, not shut them down
Two hard rules for the safety controller, matching sewer PS design:

1. BELOW stopLevel (dry-run): pumps CANNOT start.
   All downstream equipment shut down. safetyControllerActive=true
   blocks _controlLogic so level control can't restart pumps.
   Only manual override or emergency can change this.

2. ABOVE overflow level (overfill): pumps CANNOT stop.
   Only UPSTREAM equipment is shut down (stop more water coming in).
   Machine groups (downstream pumps) are NOT shut down — they must
   keep draining. safetyControllerActive is NOT set, so _controlLogic
   continues commanding pumps at the demand dictated by the level
   curve (which is >100% near overflow = all pumps at maximum).
   Only manual override or emergency stop can shut pumps during
   an overfill event.

Previously the overfill branch called turnOffAllMachines() on machine
groups AND set safetyControllerActive=true, which shut down the pumps
and blocked level control from restarting them — exactly backwards
for a sewer pumping station where the sewage keeps coming.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>