Runtime (specificClass.js):
- Replace the "shift left both ramp ends" geometry with a true
hold-then-ramp hysteresis driven by output %, not level:
• Up-curve % crosses shiftArmPercent on the way up → ARM.
• Filling→draining transition while armed → capture the up-curve %
at that moment as _shiftHoldValue.
• Draining + level ≥ shiftLevel → output stays at _shiftHoldValue
(horizontal hold, matching the dashed segment in the SVG).
• Draining + level in [start, shift] → output ramps holdValue → 0 %
along the same curve shape (linear or log) as the up curve.
• Draining + level < startLevel → 0 % AND disarm.
• Returning to filling clears holdValue, stays armed; next drain
transition captures a fresh hold so bouncing fills rearm cleanly.
• Disarm only when level ≤ startLevel.
- New _curveShape(x) helper for shared linear/log shaping.
- Removed legacy _levelBasedRampStart / _levelBasedRampTop /
_updateShiftArmed in favour of the inline state machine.
Adapter (nodeClass.js):
- Pipe shiftArmPercent through to control.levelbased.
Editor (pumpingStation.html + src/editor/):
- Add shiftArmPercent input row (% with unit) to the mode side panel
(only shown when shifted ramp is enabled). Default 95 %.
- Add the horizontal arming-% line + label inside the mode SVG —
this is the "% Threshold triggering shifted ramp down" line from
the original drawing that had been missing.
- Redraw the shifted-down curve to match the SVG geometry literally:
100 % flat from maxLevel → shiftLevel, then ramp shiftLevel →
startLevel down to 0 %, OFF below startLevel. Preview shows the
worst-case envelope (hold = 100 %); runtime hold is captured live.
- Validation extended: 0 < shiftArmPercent ≤ 100; ordering rules
preserved (start < shift ≤ max etc.).
- Auto-default shiftArmPercent to 95 when shift is enabled and the
current value is missing or out of range.
Dashboard example (examples/basic-dashboard.flow.json):
- Parser now reads `level.predicted.atequipment.default` etc. The
MeasurementContainer flatten format includes the implicit 'default'
childId; consumers must include it. Comment in the parser points
at the documenting source in generalFunctions.
Tests:
- test/basic: replace old level-armed-shift tests with two new ones
that exercise the hold-then-ramp arming, capture, hold, ramp-down,
disarm, and the bounce case (filling→draining→filling→draining
captures a fresh hold each time).
- test/integration/shifted-ramp-end-to-end.test.js: new file. Drives
Q_IN/Q_OUT through the full runtime tick with a controllable clock,
asserting the same hysteresis path the dashboard exercises.
- test/integration/basic-dashboard-flow.test.js: fixture keys updated
to the .default-suffixed form so they match the real flatten output.
56/56 tests pass.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
pumpingStation
Wet-well basin model and pump orchestration node for EVOLV.
The detailed documentation lives in wiki/:
wiki/functional-description.mddefines the shared basin model, pipe reference semantics, safety points, net-flow selection, and child registration behaviour.wiki/modes/documents control-mode-specific behaviour such as the level-linearstartLeveldemand ramp.wiki/diagrams/basin-model.drawio.svgis the current source of truth for the generic basin model.