levelBased ramp + engagement: - Ramp foot is now max(startLevel, holdLevel) — was max(startLevel, inflowLevel). inflowLevel is basin geometry, not a control setpoint; the implicit hold zone it created was causing pumps to "start at inflowLevel" instead of startLevel. - New optional `holdLevel` config (defaults to startLevel = no hold band). When raised, pumps engage at startLevel and hold at 0 % = MGC flow.min across [startLevel, holdLevel], then ramp 0..100 % to maxLevel. - Engagement decided in run() (not in `_applyMachineGroupLevelControl`): rising-edge hysteresis arming gates a clean turnOff early-return. Once armed, the helper always forwards setDemand(pct, '%') — 0 % legitimately means "engaged at min flow", no more soft-turnOff at the boundary. - Disengagement paths (minLevel hard-stop, stopLevel falling-edge, pre-arming idle) now all clear the shifted-ramp hysteresis state too. - Threshold validator drops the startLevel ≤ inflowLevel rule; adds startLevel ≤ holdLevel < maxLevel (only checked when holdLevel is explicitly set, so default-null doesn't false-flag). MGC unit math: - Replace direct group.handleInput(percent) with group.setDemand(pct, '%') in _applyMachineGroupLevelControl. The percent → m³/s resolution now lives in MGC.setDemand (committed separately in the MGC submodule). FlowAggregator variant picking: - New _pickFlowSum() helper mirrors selectBestNetFlow's variant precedence (measured first, then predicted) and resolves each side independently. Realistic mixed case — real measured upstream sensor + predicted pump outflow — now feeds the predicted-volume integrator. Was reading only `flow.predicted.*` so a real upstream sensor (which writes `flow.measured.*`) never moved the level. Editor: - New `holdLevel` and `deadZoneKeepAlivePercent` defaults + side-panel input rows in the levelbased mode preview. - Add the missing `ps-mode-line-holdLevel` SVG marker (was declared in the side-panel coupling but the SVG element didn't exist, so the dashed line never rendered). - Relax stopLevel marker gate so it renders for any non-negative typed value — start/stop ordering is the ribbon's job, not the marker's (was hiding the line whenever startLevel was momentarily smaller). - Add holdLevel to the marker loop in mode-preview so changes track. - Add stopLevel + holdLevel + maxLevel to all three bindRedraw lists (basin-diagram, mode-preview, bounds.apply) so the SVG, validation ribbon, and HTML5 min/max attrs update on every edit. - Initialise stopLevel + holdLevel + deadZoneKeepAlivePercent inputs in oneditprepare so reopening the editor shows the saved values. - nodeClass passes holdLevel + deadZoneKeepAlivePercent into the domain config. Tests: - New test/basic/_probe_upstream_emit.test.js: confirms the parent surfaces flow.measured.upstream.* on Port 0 after a measurement child write — pins the previously-invisible measured variant flow. - flowAggregator.basic.test.js: two new regression cases — measured inflow when predicted side is empty, and the measured-in / predicted-out mixed case. - control-levelBased.basic.test.js: new cases for the holdLevel hold band, the [stopLevel, startLevel] keep-alive, the engagement gate, and the "0 % at startLevel = setDemand" contract. - specificClass.test.js: zone tests adjusted to the new ramp foot. Shifted-ramp tests pin holdLevel = 3 explicitly so their legacy arithmetic (ramp foot at inflowLevel) stays self-consistent. - shifted-ramp-end-to-end.test.js: same holdLevel pin for the same reason. Packaging: - Add .gitignore + .npmignore so the published tarball drops the wiki/, simulations/, test/, tools/, .claude/ etc. The pack went from 1.5 MB (72 files) to ~57 KB (30 files). Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
27 KiB
27 KiB