Levelbased control now distinguishes startLevel (rising-edge engage,
ramp foot) from stopLevel (falling-edge disengage). _stopHystRunning
flag flips TRUE crossing startLevel up, FALSE crossing stopLevel down.
While engaged AND level inside [stopLevel, startLevel] (basin draining
through the dead band), emit a configurable keep-alive percControl
(default 1 %) so MGC keeps a single pump running for a full drain
stroke instead of oscillating at startLevel.
Hard turn-off the moment level <= stopLevel — independent of ramp
scaling. Manual-mode demand=0 now also issues explicit turnOff to
keep parity with the new MGC handleInput semantics where demand<=0
means "off".
Editor preview shades the new hysteresis band; admin endpoint
exposes runtime engaged state.