@@ -63,10 +63,21 @@ class PumpingStation {
|
|||||||
this.stations[child.config.general.id] = child;
|
this.stations[child.config.general.id] = child;
|
||||||
} else if (softwareType === 'machinegroup') {
|
} else if (softwareType === 'machinegroup') {
|
||||||
this.machineGroups[child.config.general.id] = child;
|
this.machineGroups[child.config.general.id] = child;
|
||||||
this._registerPredictedFlowChild(child);
|
|
||||||
}
|
}
|
||||||
|
|
||||||
if (softwareType === 'machine' || softwareType === 'pumpingstation' || softwareType === 'machinegroup') {
|
// Register predicted-flow subscription. Only register the HIGHEST-
|
||||||
|
// level aggregator: if a machinegroup is present, subscribe to IT
|
||||||
|
// (its flow.predicted already aggregates all child machines). Do NOT
|
||||||
|
// also subscribe to individual machines — that would double-count
|
||||||
|
// because each pump's flow is included in the group total.
|
||||||
|
//
|
||||||
|
// Individual machines (softwareType='machine') are only subscribed
|
||||||
|
// when there is NO machinegroup parent — i.e., pumps wired directly
|
||||||
|
// to the pumping station without an MGC in between.
|
||||||
|
if (softwareType === 'machinegroup' || softwareType === 'pumpingstation') {
|
||||||
|
this._registerPredictedFlowChild(child);
|
||||||
|
} else if (softwareType === 'machine' && Object.keys(this.machineGroups).length === 0) {
|
||||||
|
// Direct-child machine, no group above it — register its flow.
|
||||||
this._registerPredictedFlowChild(child);
|
this._registerPredictedFlowChild(child);
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
@@ -97,18 +108,21 @@ class PumpingStation {
|
|||||||
const childId = child.config.general.id ?? childName;
|
const childId = child.config.general.id ?? childName;
|
||||||
|
|
||||||
let posKey;
|
let posKey;
|
||||||
let eventNames;
|
let eventName;
|
||||||
switch (position) {
|
switch (position) {
|
||||||
case 'downstream':
|
case 'downstream':
|
||||||
case 'out':
|
case 'out':
|
||||||
case 'atequipment':
|
case 'atequipment':
|
||||||
posKey = 'out';
|
posKey = 'out';
|
||||||
eventNames = ['flow.predicted.downstream', 'flow.predicted.atequipment'];
|
// Subscribe to ONE event only. 'downstream' is the most specific
|
||||||
|
// — avoids double-counting from 'atequipment' which carries the
|
||||||
|
// same total flow on a different event name.
|
||||||
|
eventName = 'flow.predicted.downstream';
|
||||||
break;
|
break;
|
||||||
case 'upstream':
|
case 'upstream':
|
||||||
case 'in':
|
case 'in':
|
||||||
posKey = 'in';
|
posKey = 'in';
|
||||||
eventNames = ['flow.predicted.upstream', 'flow.predicted.atequipment'];
|
eventName = 'flow.predicted.upstream';
|
||||||
break;
|
break;
|
||||||
default:
|
default:
|
||||||
this.logger.warn(`Unsupported predicted flow position "${position}" from ${childName}`);
|
this.logger.warn(`Unsupported predicted flow position "${position}" from ${childName}`);
|
||||||
@@ -132,7 +146,7 @@ class PumpingStation {
|
|||||||
.value(eventData.value, ts, unit);
|
.value(eventData.value, ts, unit);
|
||||||
};
|
};
|
||||||
|
|
||||||
eventNames.forEach((ev) => child.measurements.emitter.on(ev, handler));
|
child.measurements.emitter.on(eventName, handler);
|
||||||
}
|
}
|
||||||
|
|
||||||
/* --------------------------- Calibration --------------------------- */
|
/* --------------------------- Calibration --------------------------- */
|
||||||
@@ -250,15 +264,26 @@ class PumpingStation {
|
|||||||
return;
|
return;
|
||||||
}
|
}
|
||||||
|
|
||||||
if (level > startLevel && direction === 'filling') {
|
// Continuous proportional control: command pumps whenever level is
|
||||||
const percControl = this._scaleLevelToFlowPercent(level);
|
// above stopLevel. The percControl ramp gives:
|
||||||
this.logger.debug(`Controllevel based => Level ${level} control applying to pump : ${percControl}`);
|
// - 0% at minFlowLevel (= startLevel) → pumps barely running
|
||||||
|
// - linearly up to 100% at maxFlowLevel → all pumps full
|
||||||
|
// - Below startLevel but above stopLevel: percControl < 0 → clamp
|
||||||
|
// to 0 → MGC turns off pumps (graceful ramp-down instead of a
|
||||||
|
// dead zone where pumps keep running at their last setpoint).
|
||||||
|
if (level > stopLevel) {
|
||||||
|
const rawPercControl = this._scaleLevelToFlowPercent(level);
|
||||||
|
const percControl = Math.max(0, rawPercControl);
|
||||||
|
this.logger.debug(`Controllevel based => Level ${level} percControl ${percControl}`);
|
||||||
|
if (percControl > 0) {
|
||||||
await this._applyMachineLevelControl(percControl);
|
await this._applyMachineLevelControl(percControl);
|
||||||
// Also forward to machine groups (e.g. MGC) — the level-based
|
|
||||||
// control originally only addressed direct-child machines, but in
|
|
||||||
// a hierarchical topology (PS → MGC → pumps) the machines sit
|
|
||||||
// under MGC and PS.machines is empty.
|
|
||||||
await this._applyMachineGroupLevelControl(percControl);
|
await this._applyMachineGroupLevelControl(percControl);
|
||||||
|
} else {
|
||||||
|
// Between stopLevel and startLevel with percControl ≤ 0:
|
||||||
|
// tell MGC to scale back to 0 rather than leaving pumps
|
||||||
|
// running at the last commanded setpoint.
|
||||||
|
await this._applyMachineGroupLevelControl(0);
|
||||||
|
}
|
||||||
}
|
}
|
||||||
|
|
||||||
if (level < stopLevel && direction === 'draining') {
|
if (level < stopLevel && direction === 'draining') {
|
||||||
@@ -533,6 +558,24 @@ class PumpingStation {
|
|||||||
|
|
||||||
/* --------------------------- Safety --------------------------- */
|
/* --------------------------- Safety --------------------------- */
|
||||||
|
|
||||||
|
/**
|
||||||
|
* Safety controller — two hard rules:
|
||||||
|
*
|
||||||
|
* 1. BELOW stopLevel (dry-run): pumps CANNOT start.
|
||||||
|
* Shuts down all downstream machines + machine groups.
|
||||||
|
* Only a manual override or emergency can restart them.
|
||||||
|
* safetyControllerActive = true → blocks _controlLogic.
|
||||||
|
*
|
||||||
|
* 2. ABOVE overflow level (overfill): pumps CANNOT stop.
|
||||||
|
* Shuts down UPSTREAM equipment only (stop more water coming in).
|
||||||
|
* Does NOT shut down downstream pumps or machine groups — they
|
||||||
|
* must keep draining. Does NOT set safetyControllerActive — the
|
||||||
|
* level-based control keeps running so pumps stay at the demand
|
||||||
|
* dictated by the current level (which will be >100% near overflow,
|
||||||
|
* meaning all pumps at maximum via the normal demand curve).
|
||||||
|
* Only a manual override or emergency stop can shut pumps during
|
||||||
|
* an overfill event.
|
||||||
|
*/
|
||||||
_safetyController(remainingTime, direction) {
|
_safetyController(remainingTime, direction) {
|
||||||
this.safetyControllerActive = false;
|
this.safetyControllerActive = false;
|
||||||
|
|
||||||
@@ -559,10 +602,12 @@ class PumpingStation {
|
|||||||
const triggerHighVol = this.basin.maxVolOverflow * ((Number(overfillThresholdPercent) || 0) / 100);
|
const triggerHighVol = this.basin.maxVolOverflow * ((Number(overfillThresholdPercent) || 0) / 100);
|
||||||
const triggerLowVol = this.basin.minVol * (1 + ((Number(dryRunThresholdPercent) || 0) / 100));
|
const triggerLowVol = this.basin.minVol * (1 + ((Number(dryRunThresholdPercent) || 0) / 100));
|
||||||
|
|
||||||
|
// Rule 1: DRY-RUN — below stopLevel, pumps cannot run.
|
||||||
if (direction === 'draining') {
|
if (direction === 'draining') {
|
||||||
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
||||||
const dryRunTriggered = dryRunEnabled && vol < triggerLowVol;
|
const dryRunTriggered = dryRunEnabled && vol < triggerLowVol;
|
||||||
if (timeTriggered || dryRunTriggered) {
|
if (timeTriggered || dryRunTriggered) {
|
||||||
|
// Shut down all downstream equipment — pumps must stop.
|
||||||
Object.values(this.machines).forEach((machine) => {
|
Object.values(this.machines).forEach((machine) => {
|
||||||
const pos = machine?.config?.functionality?.positionVsParent;
|
const pos = machine?.config?.functionality?.positionVsParent;
|
||||||
if ((pos === 'downstream' || pos === 'atequipment') && machine._isOperationalState()) {
|
if ((pos === 'downstream' || pos === 'atequipment') && machine._isOperationalState()) {
|
||||||
@@ -572,28 +617,38 @@ class PumpingStation {
|
|||||||
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
||||||
Object.values(this.machineGroups).forEach((group) => group.turnOffAllMachines());
|
Object.values(this.machineGroups).forEach((group) => group.turnOffAllMachines());
|
||||||
this.logger.warn(
|
this.logger.warn(
|
||||||
`Safe guard triggered: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down downstream equipment`
|
`Dry-run safety: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down downstream equipment`
|
||||||
);
|
);
|
||||||
|
// Block _controlLogic so level-based control can't restart pumps.
|
||||||
this.safetyControllerActive = true;
|
this.safetyControllerActive = true;
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|
||||||
|
// Rule 2: OVERFILL — above overflow level, pumps cannot stop.
|
||||||
|
// Only shut down UPSTREAM equipment. Downstream pumps + machine
|
||||||
|
// groups keep running at whatever the level control demands
|
||||||
|
// (which will be >100% near overflow = all pumps at max).
|
||||||
|
// Do NOT set safetyControllerActive — _controlLogic must keep
|
||||||
|
// running to maintain pump demand.
|
||||||
if (direction === 'filling') {
|
if (direction === 'filling') {
|
||||||
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
||||||
const overfillTriggered = overfillEnabled && vol > triggerHighVol;
|
const overfillTriggered = overfillEnabled && vol > triggerHighVol;
|
||||||
if (timeTriggered || overfillTriggered) {
|
if (timeTriggered || overfillTriggered) {
|
||||||
|
// Shut down UPSTREAM only — stop more water coming in.
|
||||||
Object.values(this.machines).forEach((machine) => {
|
Object.values(this.machines).forEach((machine) => {
|
||||||
const pos = machine?.config?.functionality?.positionVsParent;
|
const pos = machine?.config?.functionality?.positionVsParent;
|
||||||
if (pos === 'upstream' && machine._isOperationalState()) {
|
if (pos === 'upstream' && machine._isOperationalState()) {
|
||||||
machine.handleInput('parent', 'execSequence', 'shutdown');
|
machine.handleInput('parent', 'execSequence', 'shutdown');
|
||||||
}
|
}
|
||||||
});
|
});
|
||||||
Object.values(this.machineGroups).forEach((group) => group.turnOffAllMachines());
|
|
||||||
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
||||||
|
// NOTE: machine groups (downstream pumps) are NOT shut down.
|
||||||
|
// They must keep draining to prevent overflow from worsening.
|
||||||
this.logger.warn(
|
this.logger.warn(
|
||||||
`Safe guard triggered: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down upstream equipment`
|
`Overfill safety: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down upstream equipment only — pumps keep running`
|
||||||
);
|
);
|
||||||
this.safetyControllerActive = true;
|
// NOTE: safetyControllerActive is NOT set — level control
|
||||||
|
// keeps commanding pumps at maximum demand.
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|||||||