@@ -25,8 +25,9 @@ Aliases log a one-time deprecation warning the first time they fire.
|
|||||||
- **Port 1 (InfluxDB telemetry):** same shape as Port 0, formatted with the
|
- **Port 1 (InfluxDB telemetry):** same shape as Port 0, formatted with the
|
||||||
`'influxdb'` formatter.
|
`'influxdb'` formatter.
|
||||||
- **Port 2 (registration):** at startup the node sends one
|
- **Port 2 (registration):** at startup the node sends one
|
||||||
`{ topic: 'registerChild', payload: <node.id>, positionVsParent, distance }`
|
`{ topic: 'child.register', payload: <node.id>, positionVsParent, distance }`
|
||||||
to the upstream parent.
|
to the upstream parent (`child.register` is canonical; `registerChild` is the
|
||||||
|
deprecated *input* alias, not what this node emits).
|
||||||
|
|
||||||
## Events emitted by `source.measurements.emitter`
|
## Events emitted by `source.measurements.emitter`
|
||||||
|
|
||||||
|
|||||||
@@ -1,479 +1,360 @@
|
|||||||
[
|
[
|
||||||
{
|
{
|
||||||
"id": "77f00aef1c966167",
|
"id": "ps_basic_tab",
|
||||||
"type": "tab",
|
"type": "tab",
|
||||||
"label": "PumpingStation - Basic",
|
"label": "PumpingStation - Basic",
|
||||||
"disabled": false,
|
"disabled": false,
|
||||||
"info": "Tier 1: single pumpingStation node driven by inject nodes only. Demonstrates the canonical Phase-2 topic API: set.mode, set.inflow, set.demand."
|
"info": "Tier 1: single pumpingStation node driven by inject nodes only. Demonstrates the canonical Phase-2 topic API: set.mode, set.inflow, set.demand."
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_title",
|
||||||
|
"type": "comment",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "PumpingStation - Basic\n━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━\nA 50 m³ basin (3.5 m tall, inflow at 3.0 m, outflow at 0.2 m,\noverflow at 3.2 m). controlMode = levelbased, manual demand allowed\nonly when set.mode = manual.\n\nHOW TO USE:\n 1. Deploy the flow.\n 2. Click \"set.mode = manual\" so set.demand is honoured.\n 3. Click \"set.inflow = 60 m3/h\" to push wastewater into the basin.\n 4. Watch the basin fill on Port 0 (level, volume, percControl rise).\n 5. Click \"calibrate volume 25 m3\" to jump straight to half-full.\n\nAliases (changemode, q_in, Qd, …) still work but log a deprecation\nwarning - fresh flows use the canonical names.",
|
||||||
|
"info": "",
|
||||||
|
"x": 600,
|
||||||
|
"y": 40,
|
||||||
|
"wires": []
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_inj_mode",
|
||||||
|
"type": "inject",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "set.mode = manual",
|
||||||
|
"props": [
|
||||||
|
{
|
||||||
|
"p": "topic",
|
||||||
|
"vt": "str"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "payload",
|
||||||
|
"v": "manual",
|
||||||
|
"vt": "str"
|
||||||
|
}
|
||||||
|
],
|
||||||
|
"topic": "set.mode",
|
||||||
|
"repeat": "",
|
||||||
|
"crontab": "",
|
||||||
|
"once": false,
|
||||||
|
"onceDelay": "",
|
||||||
|
"x": 200,
|
||||||
|
"y": 160,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_node"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_inj_mode_lvl",
|
||||||
|
"type": "inject",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "set.mode = levelbased",
|
||||||
|
"props": [
|
||||||
|
{
|
||||||
|
"p": "topic",
|
||||||
|
"vt": "str"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "payload",
|
||||||
|
"v": "levelbased",
|
||||||
|
"vt": "str"
|
||||||
|
}
|
||||||
|
],
|
||||||
|
"topic": "set.mode",
|
||||||
|
"repeat": "",
|
||||||
|
"crontab": "",
|
||||||
|
"once": false,
|
||||||
|
"onceDelay": "",
|
||||||
|
"x": 220,
|
||||||
|
"y": 200,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_node"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_inj_inflow",
|
||||||
|
"type": "inject",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "set.inflow = 60 m3/h",
|
||||||
|
"props": [
|
||||||
|
{
|
||||||
|
"p": "topic",
|
||||||
|
"vt": "str"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "payload",
|
||||||
|
"v": "60",
|
||||||
|
"vt": "num"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "unit",
|
||||||
|
"v": "m3/h",
|
||||||
|
"vt": "str"
|
||||||
|
}
|
||||||
|
],
|
||||||
|
"topic": "set.inflow",
|
||||||
|
"repeat": "",
|
||||||
|
"crontab": "",
|
||||||
|
"once": false,
|
||||||
|
"onceDelay": "",
|
||||||
|
"x": 200,
|
||||||
|
"y": 260,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_node"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_inj_demand",
|
||||||
|
"type": "inject",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "set.demand = 40 m3/h",
|
||||||
|
"props": [
|
||||||
|
{
|
||||||
|
"p": "topic",
|
||||||
|
"vt": "str"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "payload",
|
||||||
|
"v": "40",
|
||||||
|
"vt": "num"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "unit",
|
||||||
|
"v": "m3/h",
|
||||||
|
"vt": "str"
|
||||||
|
}
|
||||||
|
],
|
||||||
|
"topic": "set.demand",
|
||||||
|
"repeat": "",
|
||||||
|
"crontab": "",
|
||||||
|
"once": false,
|
||||||
|
"onceDelay": "",
|
||||||
|
"x": 200,
|
||||||
|
"y": 300,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_node"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_inj_calvol",
|
||||||
|
"type": "inject",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "calibrate volume 25 m3",
|
||||||
|
"props": [
|
||||||
|
{
|
||||||
|
"p": "topic",
|
||||||
|
"vt": "str"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "payload",
|
||||||
|
"v": "25",
|
||||||
|
"vt": "num"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "unit",
|
||||||
|
"v": "m3",
|
||||||
|
"vt": "str"
|
||||||
|
}
|
||||||
|
],
|
||||||
|
"topic": "cmd.calibrate.volume",
|
||||||
|
"repeat": "",
|
||||||
|
"crontab": "",
|
||||||
|
"once": false,
|
||||||
|
"onceDelay": "",
|
||||||
|
"x": 220,
|
||||||
|
"y": 360,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_node"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_inj_callvl",
|
||||||
|
"type": "inject",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "calibrate level 1.5 m",
|
||||||
|
"props": [
|
||||||
|
{
|
||||||
|
"p": "topic",
|
||||||
|
"vt": "str"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "payload",
|
||||||
|
"v": "1.5",
|
||||||
|
"vt": "num"
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"p": "unit",
|
||||||
|
"v": "m",
|
||||||
|
"vt": "str"
|
||||||
|
}
|
||||||
|
],
|
||||||
|
"topic": "cmd.calibrate.level",
|
||||||
|
"repeat": "",
|
||||||
|
"crontab": "",
|
||||||
|
"once": false,
|
||||||
|
"onceDelay": "",
|
||||||
|
"x": 220,
|
||||||
|
"y": 400,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_node"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_node",
|
||||||
|
"type": "pumpingStation",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "Pumping Station",
|
||||||
|
"simulator": false,
|
||||||
|
"basinVolume": 50,
|
||||||
|
"basinHeight": 3.5,
|
||||||
|
"inflowLevel": 3,
|
||||||
|
"outflowLevel": 0.2,
|
||||||
|
"overflowLevel": 3.2,
|
||||||
|
"defaultFluid": "wastewater",
|
||||||
|
"inletPipeDiameter": 0.3,
|
||||||
|
"outletPipeDiameter": 0.3,
|
||||||
|
"pipelineLength": 80,
|
||||||
|
"maxDischargeHead": 24,
|
||||||
|
"staticHead": 12,
|
||||||
|
"maxInflowRate": 200,
|
||||||
|
"temperatureReferenceDegC": 15,
|
||||||
|
"timeleftToFullOrEmptyThresholdSeconds": 0,
|
||||||
|
"enableDryRunProtection": true,
|
||||||
|
"enableOverfillProtection": true,
|
||||||
|
"dryRunThresholdPercent": 2,
|
||||||
|
"overfillThresholdPercent": 98,
|
||||||
|
"minHeightBasedOn": "outlet",
|
||||||
|
"processOutputFormat": "process",
|
||||||
|
"dbaseOutputFormat": "influxdb",
|
||||||
|
"refHeight": "NAP",
|
||||||
|
"basinBottomRef": 1,
|
||||||
|
"uuid": "example-ps-001",
|
||||||
|
"supplier": "WBD-RD",
|
||||||
|
"category": "station",
|
||||||
|
"assetType": "pumpingstation",
|
||||||
|
"model": "demo-50m3",
|
||||||
|
"unit": "m3/h",
|
||||||
|
"enableLog": true,
|
||||||
|
"logLevel": "info",
|
||||||
|
"positionVsParent": "atEquipment",
|
||||||
|
"positionIcon": "",
|
||||||
|
"hasDistance": false,
|
||||||
|
"distance": "",
|
||||||
|
"distanceUnit": "m",
|
||||||
|
"distanceDescription": "",
|
||||||
|
"controlMode": "levelbased",
|
||||||
|
"startLevel": 1.2,
|
||||||
|
"minLevel": 0.4,
|
||||||
|
"maxLevel": 2.8,
|
||||||
|
"flowSetpoint": null,
|
||||||
|
"flowDeadband": null,
|
||||||
|
"x": 1320,
|
||||||
|
"y": 300,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_format"
|
||||||
|
],
|
||||||
|
[
|
||||||
|
"ps_basic_dbg_influx"
|
||||||
|
],
|
||||||
|
[
|
||||||
|
"ps_basic_dbg_parent"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_format",
|
||||||
|
"type": "function",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "Merge deltas + format",
|
||||||
|
"func": "const p = (msg && msg.payload && typeof msg.payload === 'object') ? msg.payload : {};\nconst cache = context.get('c') || {};\nObject.assign(cache, p);\ncontext.set('c', cache);\nfunction pick(prefix) {\n for (const k of Object.keys(cache)) if (k === prefix || k.indexOf(prefix + '.') === 0) {\n const v = Number(cache[k]); if (Number.isFinite(v)) return v;\n } return null;\n}\nconst vol = pick('volume.predicted.atequipment');\nconst lvl = pick('level.predicted.atequipment');\nconst flIn = pick('flow.predicted.in');\nmsg.payload = {\n state: cache.state || 'unknown',\n controlMode: cache.controlMode || cache.mode || 'n/a',\n direction: cache.direction || 'n/a',\n percControl: cache.percControl != null ? Number(cache.percControl).toFixed(1) + ' %' : 'n/a',\n volume: vol != null ? vol.toFixed(2) + ' m3' : 'n/a',\n volumePercent: cache.volumePercent != null ? Number(cache.volumePercent).toFixed(1) + ' %' : 'n/a',\n level: lvl != null ? lvl.toFixed(3) + ' m' : 'n/a',\n inflow: flIn != null ? (flIn * 3600).toFixed(1) + ' m3/h' : 'n/a',\n timeToFull: cache.timeToFull != null ? Number(cache.timeToFull).toFixed(0) + ' s' : 'n/a',\n timeToEmpty: cache.timeToEmpty != null ? Number(cache.timeToEmpty).toFixed(0) + ' s' : 'n/a'\n};\nreturn msg;",
|
||||||
|
"outputs": 1,
|
||||||
|
"noerr": 0,
|
||||||
|
"initialize": "",
|
||||||
|
"finalize": "",
|
||||||
|
"libs": [],
|
||||||
|
"x": 1560,
|
||||||
|
"y": 280,
|
||||||
|
"wires": [
|
||||||
|
[
|
||||||
|
"ps_basic_dbg_process"
|
||||||
|
]
|
||||||
|
]
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_dbg_process",
|
||||||
|
"type": "debug",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "Port 0: Process",
|
||||||
|
"active": true,
|
||||||
|
"tosidebar": true,
|
||||||
|
"console": false,
|
||||||
|
"tostatus": false,
|
||||||
|
"complete": "payload",
|
||||||
|
"targetType": "msg",
|
||||||
|
"x": 1800,
|
||||||
|
"y": 240,
|
||||||
|
"wires": []
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_dbg_influx",
|
||||||
|
"type": "debug",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "Port 1: InfluxDB",
|
||||||
|
"active": false,
|
||||||
|
"tosidebar": true,
|
||||||
|
"console": false,
|
||||||
|
"tostatus": false,
|
||||||
|
"complete": "true",
|
||||||
|
"targetType": "full",
|
||||||
|
"x": 1800,
|
||||||
|
"y": 320,
|
||||||
|
"wires": []
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "ps_basic_dbg_parent",
|
||||||
|
"type": "debug",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "Port 2: Parent reg",
|
||||||
|
"active": true,
|
||||||
|
"tosidebar": true,
|
||||||
|
"console": false,
|
||||||
|
"tostatus": false,
|
||||||
|
"complete": "true",
|
||||||
|
"targetType": "full",
|
||||||
|
"x": 1800,
|
||||||
|
"y": 380,
|
||||||
|
"wires": []
|
||||||
|
},
|
||||||
|
{
|
||||||
|
"id": "grp_ps_basic",
|
||||||
|
"type": "group",
|
||||||
|
"z": "ps_basic_tab",
|
||||||
|
"name": "Pumping Station (PC)",
|
||||||
|
"style": {
|
||||||
|
"label": true,
|
||||||
|
"stroke": "#000000",
|
||||||
|
"fill": "#0c99d9",
|
||||||
|
"fill-opacity": "0.10"
|
||||||
},
|
},
|
||||||
{
|
"nodes": [
|
||||||
"id": "aa3381b896eb2cfb",
|
"ps_basic_node",
|
||||||
"type": "group",
|
"ps_basic_format"
|
||||||
"z": "77f00aef1c966167",
|
],
|
||||||
"name": "Pumping Station (Process Cell)",
|
"x": 1290,
|
||||||
"style": {
|
"y": 230,
|
||||||
"label": true,
|
"w": 500,
|
||||||
"stroke": "#000000",
|
"h": 140
|
||||||
"fill": "#0c99d9",
|
}
|
||||||
"fill-opacity": "0.10"
|
|
||||||
},
|
|
||||||
"nodes": [
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
],
|
|
||||||
"x": 534,
|
|
||||||
"y": 351.5,
|
|
||||||
"w": 232,
|
|
||||||
"h": 97
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "4996420d47442fad",
|
|
||||||
"type": "group",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"name": "1. Control mode",
|
|
||||||
"style": {
|
|
||||||
"stroke": "#666666",
|
|
||||||
"fill": "#ffdf7f",
|
|
||||||
"fill-opacity": "0.15",
|
|
||||||
"label": true,
|
|
||||||
"color": "#333333"
|
|
||||||
},
|
|
||||||
"nodes": [
|
|
||||||
"1155bbbde7c65363",
|
|
||||||
"e9bea0f95b557f5d"
|
|
||||||
],
|
|
||||||
"x": 94,
|
|
||||||
"y": 119,
|
|
||||||
"w": 272,
|
|
||||||
"h": 122
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "a9f9b38b0e00c1d7",
|
|
||||||
"type": "group",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"name": "2. Flow signals (inflow / outflow)",
|
|
||||||
"style": {
|
|
||||||
"stroke": "#666666",
|
|
||||||
"fill": "#ffdf7f",
|
|
||||||
"fill-opacity": "0.15",
|
|
||||||
"label": true,
|
|
||||||
"color": "#333333"
|
|
||||||
},
|
|
||||||
"nodes": [
|
|
||||||
"7b2b5eb919b1ab15",
|
|
||||||
"3350187815774b95"
|
|
||||||
],
|
|
||||||
"x": 94,
|
|
||||||
"y": 279,
|
|
||||||
"w": 262,
|
|
||||||
"h": 122
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "42bf82c87d05f498",
|
|
||||||
"type": "group",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"name": "3. Operator demand (manual mode only)",
|
|
||||||
"style": {
|
|
||||||
"stroke": "#666666",
|
|
||||||
"fill": "#ffdf7f",
|
|
||||||
"fill-opacity": "0.15",
|
|
||||||
"label": true,
|
|
||||||
"color": "#333333"
|
|
||||||
},
|
|
||||||
"nodes": [
|
|
||||||
"48c2262c345c46b9"
|
|
||||||
],
|
|
||||||
"x": 94,
|
|
||||||
"y": 479,
|
|
||||||
"w": 261,
|
|
||||||
"h": 82
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "234bdce20170061a",
|
|
||||||
"type": "group",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"name": "4. Calibration",
|
|
||||||
"style": {
|
|
||||||
"stroke": "#666666",
|
|
||||||
"fill": "#ffdf7f",
|
|
||||||
"fill-opacity": "0.15",
|
|
||||||
"label": true,
|
|
||||||
"color": "#333333"
|
|
||||||
},
|
|
||||||
"nodes": [
|
|
||||||
"463eefdd54df89a5",
|
|
||||||
"2e0642275899fc79"
|
|
||||||
],
|
|
||||||
"x": 94,
|
|
||||||
"y": 599,
|
|
||||||
"w": 272,
|
|
||||||
"h": 122
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "f4ba4542514ed853",
|
|
||||||
"type": "group",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"name": "Expected outputs",
|
|
||||||
"style": {
|
|
||||||
"stroke": "#666666",
|
|
||||||
"fill": "#d1d1d1",
|
|
||||||
"fill-opacity": "0.2",
|
|
||||||
"label": true,
|
|
||||||
"color": "#333333"
|
|
||||||
},
|
|
||||||
"nodes": [
|
|
||||||
"b2450e5ee2eebfaa",
|
|
||||||
"386af1ad8aa8ed12",
|
|
||||||
"c27c2655f199b530"
|
|
||||||
],
|
|
||||||
"x": 874,
|
|
||||||
"y": 299,
|
|
||||||
"w": 252,
|
|
||||||
"h": 202
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "b30af582f935bcb7",
|
|
||||||
"type": "comment",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"name": "PumpingStation — Basic (Tier 1)",
|
|
||||||
"info": "Single pumpingStation node driven by inject buttons. Shows the canonical msg.topic command surface.\n\nDefault controlMode = levelbased. Switch to manual to honour set.demand.\n\nHOW TO USE\n1. Deploy the flow.\n2. (optional) Click \"set.mode = manual\" if you want set.demand to forward; otherwise leave it on levelbased and the ramp drives demand from level.\n3. Click \"set.inflow = 60 m³/h\" to push wastewater into the basin.\n4. Watch the basin fill on Port 0 (level, volume rise) and Port 1 (InfluxDB-shaped payload).\n5. In manual mode: click \"set.demand = 40\" — the value surfaces as `manualDemand` on Port 0/1 and in the node status badge.\n6. Click \"calibrate volume 25 m³\" or \"calibrate level 1.5 m\" to snap the predicted-volume integrator.\n\nPORTS\n- Port 0: process output (changed fields only)\n- Port 1: InfluxDB-shaped {measurement, fields, tags, timestamp}\n- Port 2: parent registration (child handshake)",
|
|
||||||
"x": 650,
|
|
||||||
"y": 300,
|
|
||||||
"wires": []
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "1155bbbde7c65363",
|
|
||||||
"type": "inject",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "4996420d47442fad",
|
|
||||||
"name": "set.mode = manual",
|
|
||||||
"props": [
|
|
||||||
{
|
|
||||||
"p": "topic",
|
|
||||||
"vt": "str"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"p": "payload",
|
|
||||||
"v": "manual",
|
|
||||||
"vt": "str"
|
|
||||||
}
|
|
||||||
],
|
|
||||||
"repeat": "",
|
|
||||||
"crontab": "",
|
|
||||||
"once": false,
|
|
||||||
"onceDelay": "",
|
|
||||||
"topic": "set.mode",
|
|
||||||
"x": 230,
|
|
||||||
"y": 160,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "e9bea0f95b557f5d",
|
|
||||||
"type": "inject",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "4996420d47442fad",
|
|
||||||
"name": "set.mode = levelbased",
|
|
||||||
"props": [
|
|
||||||
{
|
|
||||||
"p": "topic",
|
|
||||||
"vt": "str"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"p": "payload",
|
|
||||||
"v": "levelbased",
|
|
||||||
"vt": "str"
|
|
||||||
}
|
|
||||||
],
|
|
||||||
"repeat": "",
|
|
||||||
"crontab": "",
|
|
||||||
"once": false,
|
|
||||||
"onceDelay": "",
|
|
||||||
"topic": "set.mode",
|
|
||||||
"x": 240,
|
|
||||||
"y": 200,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "7b2b5eb919b1ab15",
|
|
||||||
"type": "inject",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "a9f9b38b0e00c1d7",
|
|
||||||
"name": "set.inflow = 60 m3/h",
|
|
||||||
"props": [
|
|
||||||
{
|
|
||||||
"p": "topic",
|
|
||||||
"vt": "str"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"p": "payload",
|
|
||||||
"v": "60",
|
|
||||||
"vt": "num"
|
|
||||||
}
|
|
||||||
],
|
|
||||||
"repeat": "",
|
|
||||||
"crontab": "",
|
|
||||||
"once": false,
|
|
||||||
"onceDelay": "",
|
|
||||||
"topic": "set.inflow",
|
|
||||||
"x": 240,
|
|
||||||
"y": 360,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "48c2262c345c46b9",
|
|
||||||
"type": "inject",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "42bf82c87d05f498",
|
|
||||||
"name": "set.demand = 40 %",
|
|
||||||
"props": [
|
|
||||||
{
|
|
||||||
"p": "topic",
|
|
||||||
"vt": "str"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"p": "payload",
|
|
||||||
"v": "40",
|
|
||||||
"vt": "num"
|
|
||||||
}
|
|
||||||
],
|
|
||||||
"repeat": "",
|
|
||||||
"crontab": "",
|
|
||||||
"once": false,
|
|
||||||
"onceDelay": "",
|
|
||||||
"topic": "set.demand",
|
|
||||||
"x": 230,
|
|
||||||
"y": 520,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "463eefdd54df89a5",
|
|
||||||
"type": "inject",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "234bdce20170061a",
|
|
||||||
"name": "calibrate volume 25 m3",
|
|
||||||
"props": [
|
|
||||||
{
|
|
||||||
"p": "topic",
|
|
||||||
"vt": "str"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"p": "payload",
|
|
||||||
"v": "25",
|
|
||||||
"vt": "num"
|
|
||||||
}
|
|
||||||
],
|
|
||||||
"repeat": "",
|
|
||||||
"crontab": "",
|
|
||||||
"once": false,
|
|
||||||
"onceDelay": "",
|
|
||||||
"topic": "cmd.calibrate.volume",
|
|
||||||
"x": 240,
|
|
||||||
"y": 640,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "2e0642275899fc79",
|
|
||||||
"type": "inject",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "234bdce20170061a",
|
|
||||||
"name": "calibrate level 1.5 m",
|
|
||||||
"props": [
|
|
||||||
{
|
|
||||||
"p": "topic",
|
|
||||||
"vt": "str"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"p": "payload",
|
|
||||||
"v": "1.5",
|
|
||||||
"vt": "num"
|
|
||||||
}
|
|
||||||
],
|
|
||||||
"repeat": "",
|
|
||||||
"crontab": "",
|
|
||||||
"once": false,
|
|
||||||
"onceDelay": "",
|
|
||||||
"topic": "cmd.calibrate.level",
|
|
||||||
"x": 240,
|
|
||||||
"y": 680,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "b2450e5ee2eebfaa",
|
|
||||||
"type": "debug",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "f4ba4542514ed853",
|
|
||||||
"name": "Port 0: Process",
|
|
||||||
"active": true,
|
|
||||||
"tosidebar": true,
|
|
||||||
"console": false,
|
|
||||||
"tostatus": false,
|
|
||||||
"complete": "payload",
|
|
||||||
"targetType": "msg",
|
|
||||||
"x": 980,
|
|
||||||
"y": 340,
|
|
||||||
"wires": []
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "386af1ad8aa8ed12",
|
|
||||||
"type": "debug",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "f4ba4542514ed853",
|
|
||||||
"name": "Port 1: InfluxDB",
|
|
||||||
"active": true,
|
|
||||||
"tosidebar": true,
|
|
||||||
"console": false,
|
|
||||||
"tostatus": false,
|
|
||||||
"complete": "true",
|
|
||||||
"targetType": "full",
|
|
||||||
"x": 980,
|
|
||||||
"y": 400,
|
|
||||||
"wires": []
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "c27c2655f199b530",
|
|
||||||
"type": "debug",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "f4ba4542514ed853",
|
|
||||||
"name": "Port 2: Parent reg",
|
|
||||||
"active": true,
|
|
||||||
"tosidebar": true,
|
|
||||||
"console": false,
|
|
||||||
"tostatus": false,
|
|
||||||
"complete": "true",
|
|
||||||
"targetType": "full",
|
|
||||||
"x": 990,
|
|
||||||
"y": 460,
|
|
||||||
"wires": []
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "8e78b6607deb33a7",
|
|
||||||
"type": "pumpingStation",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "aa3381b896eb2cfb",
|
|
||||||
"name": "",
|
|
||||||
"simulator": false,
|
|
||||||
"basinVolume": 50,
|
|
||||||
"basinHeight": 4,
|
|
||||||
"inflowLevel": 1.5,
|
|
||||||
"outflowLevel": 0.2,
|
|
||||||
"overflowLevel": 3.8,
|
|
||||||
"defaultFluid": "wastewater",
|
|
||||||
"inletPipeDiameter": 0.3,
|
|
||||||
"outletPipeDiameter": 0.3,
|
|
||||||
"pipelineLength": 80,
|
|
||||||
"maxDischargeHead": 24,
|
|
||||||
"staticHead": 12,
|
|
||||||
"maxInflowRate": 200,
|
|
||||||
"temperatureReferenceDegC": 15,
|
|
||||||
"timeleftToFullOrEmptyThresholdSeconds": 0,
|
|
||||||
"enableDryRunProtection": true,
|
|
||||||
"enableHighVolumeSafety": true,
|
|
||||||
"enableOverfillProtection": true,
|
|
||||||
"dryRunThresholdPercent": 2,
|
|
||||||
"highVolumeSafetyThresholdPercent": 98,
|
|
||||||
"overfillThresholdPercent": 98,
|
|
||||||
"minHeightBasedOn": "outlet",
|
|
||||||
"processOutputFormat": "process",
|
|
||||||
"dbaseOutputFormat": "influxdb",
|
|
||||||
"refHeight": "NAP",
|
|
||||||
"basinBottomRef": 1,
|
|
||||||
"uuid": "",
|
|
||||||
"supplier": "",
|
|
||||||
"category": "",
|
|
||||||
"assetType": "",
|
|
||||||
"model": "",
|
|
||||||
"unit": "",
|
|
||||||
"enableLog": false,
|
|
||||||
"logLevel": "error",
|
|
||||||
"positionVsParent": "atEquipment",
|
|
||||||
"positionIcon": "⊥",
|
|
||||||
"hasDistance": false,
|
|
||||||
"distance": "",
|
|
||||||
"controlMode": "levelbased",
|
|
||||||
"levelCurveType": "linear",
|
|
||||||
"logCurveFactor": 9,
|
|
||||||
"enableShiftedRamp": false,
|
|
||||||
"shiftLevel": 0,
|
|
||||||
"shiftArmPercent": 95,
|
|
||||||
"startLevel": 1,
|
|
||||||
"stopLevel": 0.5,
|
|
||||||
"minLevel": 0.20400000000000001,
|
|
||||||
"maxLevel": 3.8,
|
|
||||||
"flowSetpoint": null,
|
|
||||||
"flowDeadband": null,
|
|
||||||
"x": 650,
|
|
||||||
"y": 400,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"b2450e5ee2eebfaa"
|
|
||||||
],
|
|
||||||
[
|
|
||||||
"386af1ad8aa8ed12"
|
|
||||||
],
|
|
||||||
[
|
|
||||||
"c27c2655f199b530"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "3350187815774b95",
|
|
||||||
"type": "inject",
|
|
||||||
"z": "77f00aef1c966167",
|
|
||||||
"g": "a9f9b38b0e00c1d7",
|
|
||||||
"name": "set.outflow= 80 m3/h",
|
|
||||||
"props": [
|
|
||||||
{
|
|
||||||
"p": "topic",
|
|
||||||
"vt": "str"
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"p": "payload"
|
|
||||||
}
|
|
||||||
],
|
|
||||||
"repeat": "",
|
|
||||||
"crontab": "",
|
|
||||||
"once": false,
|
|
||||||
"onceDelay": "",
|
|
||||||
"topic": "set.outflow",
|
|
||||||
"payload": "80",
|
|
||||||
"payloadType": "num",
|
|
||||||
"x": 230,
|
|
||||||
"y": 320,
|
|
||||||
"wires": [
|
|
||||||
[
|
|
||||||
"8e78b6607deb33a7"
|
|
||||||
]
|
|
||||||
]
|
|
||||||
},
|
|
||||||
{
|
|
||||||
"id": "ef77c1819422a098",
|
|
||||||
"type": "global-config",
|
|
||||||
"env": [],
|
|
||||||
"modules": {
|
|
||||||
"EVOLV": "1.0.29"
|
|
||||||
}
|
|
||||||
}
|
|
||||||
]
|
]
|
||||||
@@ -79,8 +79,12 @@ These flows follow the EVOLV layout rule set in
|
|||||||
- **Group boxes** wrap each parent + its direct children, coloured by the
|
- **Group boxes** wrap each parent + its direct children, coloured by the
|
||||||
parent's S88 level.
|
parent's S88 level.
|
||||||
|
|
||||||
## Regenerating
|
## Maintaining
|
||||||
|
|
||||||
The current example JSON files are hand-maintained. If you re-introduce a
|
These example flows are **hand-authored one-offs** — edit the JSON directly.
|
||||||
generator, regenerate `01-Basic.json` and `02-Dashboard.json` from it
|
There is intentionally no generator: examples are illustrative, not produced in
|
||||||
rather than editing the JSON directly.
|
bulk. Validate any change with `flow-lint`:
|
||||||
|
|
||||||
|
```bash
|
||||||
|
node ../../../tools/flow-lint/bin/flow-lint.js 01-Basic.json 02-Dashboard.json
|
||||||
|
```
|
||||||
|
|||||||
@@ -48,42 +48,29 @@ exports.calibrateLevel = (source, msg, ctx) => {
|
|||||||
source.calibratePredictedLevel(v);
|
source.calibratePredictedLevel(v);
|
||||||
};
|
};
|
||||||
|
|
||||||
exports.setInflow = (source, msg) => {
|
// The registry has already normalised any accepted shape (number, numeric
|
||||||
// Payload is either a number (legacy q_in shape) or
|
// string, or { value, unit } object) to a number in the descriptor unit
|
||||||
// { value, unit, timestamp } (richer object form).
|
// (m3/h) and tagged msg.unit. Handlers just read the normalised scalar.
|
||||||
const p = msg.payload;
|
exports.setInflow = (source, msg, ctx) => {
|
||||||
let value;
|
const log = _logger(source, ctx);
|
||||||
let unit;
|
const value = Number(msg.payload);
|
||||||
let timestamp;
|
if (!Number.isFinite(value)) {
|
||||||
if (p !== null && typeof p === 'object') {
|
log?.warn?.(`set.inflow: non-numeric payload '${JSON.stringify(msg.payload)}'`);
|
||||||
value = Number(p.value);
|
return;
|
||||||
unit = p.unit;
|
|
||||||
timestamp = p.timestamp || Date.now();
|
|
||||||
} else {
|
|
||||||
value = Number(p);
|
|
||||||
unit = msg?.unit;
|
|
||||||
timestamp = msg?.timestamp || Date.now();
|
|
||||||
}
|
}
|
||||||
source.setManualInflow(value, timestamp, unit);
|
source.setManualInflow(value, msg.timestamp, msg.unit);
|
||||||
};
|
};
|
||||||
|
|
||||||
exports.setOutflow = (source, msg) => {
|
exports.setOutflow = (source, msg, ctx) => {
|
||||||
// Manual q_out — basin-docs dashboard injects a drain rate without
|
// Manual q_out — basin-docs dashboard injects a drain rate without wiring a
|
||||||
// wiring a real pump. Same payload shape as q_in.
|
// real pump. Same normalised shape as set.inflow.
|
||||||
const p = msg.payload;
|
const log = _logger(source, ctx);
|
||||||
let value;
|
const value = Number(msg.payload);
|
||||||
let unit;
|
if (!Number.isFinite(value)) {
|
||||||
let timestamp;
|
log?.warn?.(`set.outflow: non-numeric payload '${JSON.stringify(msg.payload)}'`);
|
||||||
if (p !== null && typeof p === 'object') {
|
return;
|
||||||
value = Number(p.value);
|
|
||||||
unit = p.unit;
|
|
||||||
timestamp = p.timestamp || Date.now();
|
|
||||||
} else {
|
|
||||||
value = Number(p);
|
|
||||||
unit = msg?.unit;
|
|
||||||
timestamp = msg?.timestamp || Date.now();
|
|
||||||
}
|
}
|
||||||
source.setManualOutflow(value, timestamp, unit);
|
source.setManualOutflow(value, msg.timestamp, msg.unit);
|
||||||
};
|
};
|
||||||
|
|
||||||
exports.setDemand = (source, msg, ctx) => {
|
exports.setDemand = (source, msg, ctx) => {
|
||||||
|
|||||||
@@ -26,9 +26,10 @@ module.exports = [
|
|||||||
{
|
{
|
||||||
topic: 'cmd.calibrate.volume',
|
topic: 'cmd.calibrate.volume',
|
||||||
aliases: ['calibratePredictedVolume'],
|
aliases: ['calibratePredictedVolume'],
|
||||||
// any: payload may be a number or numeric string.
|
// any: payload may be a number, numeric string, or { value, unit } object —
|
||||||
|
// the registry normalises all of them to a number in `unit` before the handler.
|
||||||
payloadSchema: { type: 'any' },
|
payloadSchema: { type: 'any' },
|
||||||
units: { measure: 'volume', default: 'm3' },
|
unit: 'm3',
|
||||||
description: 'Calibrate the predicted-volume integrator to a known basin volume.',
|
description: 'Calibrate the predicted-volume integrator to a known basin volume.',
|
||||||
handler: handlers.calibrateVolume,
|
handler: handlers.calibrateVolume,
|
||||||
},
|
},
|
||||||
@@ -36,16 +37,15 @@ module.exports = [
|
|||||||
topic: 'cmd.calibrate.level',
|
topic: 'cmd.calibrate.level',
|
||||||
aliases: ['calibratePredictedLevel'],
|
aliases: ['calibratePredictedLevel'],
|
||||||
payloadSchema: { type: 'any' },
|
payloadSchema: { type: 'any' },
|
||||||
units: { measure: 'length', default: 'm' },
|
unit: 'm',
|
||||||
description: 'Calibrate the predicted-volume integrator to a known basin level.',
|
description: 'Calibrate the predicted-volume integrator to a known basin level.',
|
||||||
handler: handlers.calibrateLevel,
|
handler: handlers.calibrateLevel,
|
||||||
},
|
},
|
||||||
{
|
{
|
||||||
topic: 'set.inflow',
|
topic: 'set.inflow',
|
||||||
aliases: ['q_in'],
|
aliases: ['q_in'],
|
||||||
// any: number, numeric string, or { value, unit, timestamp } object.
|
|
||||||
payloadSchema: { type: 'any' },
|
payloadSchema: { type: 'any' },
|
||||||
units: { measure: 'volumeFlowRate', default: 'm3/h' },
|
unit: 'm3/h',
|
||||||
description: 'Push a measured inflow value into the basin balance.',
|
description: 'Push a measured inflow value into the basin balance.',
|
||||||
handler: handlers.setInflow,
|
handler: handlers.setInflow,
|
||||||
},
|
},
|
||||||
@@ -53,7 +53,7 @@ module.exports = [
|
|||||||
topic: 'set.outflow',
|
topic: 'set.outflow',
|
||||||
aliases: ['q_out'],
|
aliases: ['q_out'],
|
||||||
payloadSchema: { type: 'any' },
|
payloadSchema: { type: 'any' },
|
||||||
units: { measure: 'volumeFlowRate', default: 'm3/h' },
|
unit: 'm3/h',
|
||||||
description: 'Push a measured outflow value into the basin balance.',
|
description: 'Push a measured outflow value into the basin balance.',
|
||||||
handler: handlers.setOutflow,
|
handler: handlers.setOutflow,
|
||||||
},
|
},
|
||||||
@@ -61,7 +61,7 @@ module.exports = [
|
|||||||
topic: 'set.demand',
|
topic: 'set.demand',
|
||||||
aliases: ['Qd'],
|
aliases: ['Qd'],
|
||||||
payloadSchema: { type: 'any' },
|
payloadSchema: { type: 'any' },
|
||||||
units: { measure: 'volumeFlowRate', default: 'm3/h' },
|
unit: 'm3/h',
|
||||||
description: 'Operator outflow demand setpoint for the station.',
|
description: 'Operator outflow demand setpoint for the station.',
|
||||||
handler: handlers.setDemand,
|
handler: handlers.setDemand,
|
||||||
},
|
},
|
||||||
|
|||||||
@@ -32,7 +32,7 @@ class PumpingStation extends BaseDomain {
|
|||||||
static unitPolicy = UnitPolicy.declare({
|
static unitPolicy = UnitPolicy.declare({
|
||||||
canonical: { flow: 'm3/s', pressure: 'Pa', power: 'W', temperature: 'K' },
|
canonical: { flow: 'm3/s', pressure: 'Pa', power: 'W', temperature: 'K' },
|
||||||
output: {
|
output: {
|
||||||
flow: 'm3/h', netFlowRate: 'm3/h', level: 'm', volume: 'm3',
|
flow: 'm3/s', netFlowRate: 'm3/s', level: 'm', volume: 'm3',
|
||||||
overflowVolume: 'm3', underflowVolume: 'm3',
|
overflowVolume: 'm3', underflowVolume: 'm3',
|
||||||
},
|
},
|
||||||
requireUnitForTypes: [],
|
requireUnitForTypes: [],
|
||||||
|
|||||||
101
test/_output-manifest.md
Normal file
101
test/_output-manifest.md
Normal file
@@ -0,0 +1,101 @@
|
|||||||
|
# pumpingStation output manifest
|
||||||
|
|
||||||
|
> Single source of truth for **what this node emits and where it is tested**, per
|
||||||
|
> [`.claude/rules/output-coverage.md`](https://gitea.wbd-rd.nl/RnD/EVOLV/src/branch/development/.claude/rules/output-coverage.md).
|
||||||
|
> Generated against code-ref `a83a85e`. Regenerate the wiki contract with
|
||||||
|
> `npm run wiki:all` and re-check this table whenever `getOutput()`,
|
||||||
|
> `src/commands/index.js`, or an `examples/*.json` fan-out changes.
|
||||||
|
|
||||||
|
**Null convention for this node:** a Port-0 key whose source is not yet
|
||||||
|
available is emitted as **explicit `null`** (e.g. `timeleft`, `flowSource`,
|
||||||
|
`manualDemand` outside manual mode), never silently absent. Delta-compression on
|
||||||
|
Port 0 then drops keys whose value is unchanged since the previous tick.
|
||||||
|
|
||||||
|
## Port 0 (process data) — `specificClass.getOutput()` → `outputUtils.formatMsg(..., 'process')`
|
||||||
|
|
||||||
|
`msg.topic = config.general.name`. Keys below are the full pre-delta-compression set.
|
||||||
|
|
||||||
|
| Key | Source | Type | States tested | Test file |
|
||||||
|
|---|---|---|---|---|
|
||||||
|
| `mode` | `getOutput` ← `this.mode` | string (`levelbased`/`manual`/`flowbased`/`none`) | populated (`manual`) | test/basic/specificClass.test.js |
|
||||||
|
| `manualDemand` | `getOutput` ← `_manualDemand` | number m³/h, `null` outside manual | populated, null | test/basic/specificClass.test.js |
|
||||||
|
| `direction` | `getOutput` ← `state.direction` | string (`filling`/`draining`/`steady`) | present | test/basic/specificClass.test.js |
|
||||||
|
| `flowSource` | `getOutput` ← `state.flowSource` | string, `null` when no source | null (pre-child) | test/basic/specificClass.test.js |
|
||||||
|
| `timeleft` | `getOutput` ← `state.seconds` | number s, `null` when steady | present, null | test/basic/specificClass.test.js |
|
||||||
|
| `percControl` | `getOutput` ← `controlState.percControl` | number % 0..100 | 0, 25, 50, 75, 85, 100 | test/basic/specificClass.test.js |
|
||||||
|
| `dryRunLevel` | `_computeSafetyPoints` | number m | populated | test/basic/specificClass.test.js |
|
||||||
|
| `dryRunSafetyVol` | `_computeSafetyPoints` | number m³ | populated | test/basic/specificClass.test.js |
|
||||||
|
| `highVolumeSafetyLevel` | `_computeSafetyPoints` | number m | populated | test/basic/specificClass.test.js |
|
||||||
|
| `highVolumeSafetyVol` | `_computeSafetyPoints` | number m³ | populated | test/basic/specificClass.test.js |
|
||||||
|
| `predictedOverflowVolume` | `measurements` overflowVolume | number m³ | populated, 0 | test/basic/specificClass.test.js |
|
||||||
|
| `predictedOverflowRate` | `measurements` flow.overflow | number m³/s | populated, 0 | test/basic/specificClass.test.js |
|
||||||
|
| `predictedUnderflowVolume` | `measurements` underflowVolume | number m³ | 0 | test/basic/specificClass.test.js |
|
||||||
|
| `volume.predicted.atequipment.<childId>` | `measurements.getFlattenedOutput` | number m³ | populated | test/basic/specificClass.test.js |
|
||||||
|
| basin geometry: `heightBasin`, `surfaceArea`, `maxVol`, `minVol`, `maxVolAtOverflow`, `minVolAtInflow`, `minVolAtOutflow`, `volEmptyBasin`, `inflowLevel`, `outflowLevel`, `overflowLevel`, `inletPipeDiameter`, `outletPipeDiameter`, `minHeightBasedOn` | `basin.snapshot()` | number (m/m²/m³) / string | populated | test/basic/specificClass.test.js, test/basic/BasinGeometry.basic.test.js |
|
||||||
|
|
||||||
|
## Port 1 (InfluxDB telemetry) — `formatMsg(..., 'influxdb')`
|
||||||
|
|
||||||
|
Same key set as Port 0 (formatted via the `influxdb` formatter rather than
|
||||||
|
`process`). Field names == Port-0 keys; `config.general.name` is the measurement
|
||||||
|
tag. No Port-1-only fields. Covered transitively by the Port-0 tests above; a
|
||||||
|
dedicated Port-1 line-protocol assertion is a **gap** (see below).
|
||||||
|
|
||||||
|
## Port 2 (registration / control plumbing) — `BaseNodeAdapter._scheduleRegistration`
|
||||||
|
|
||||||
|
| Topic | Source | Payload shape | States tested | Test file |
|
||||||
|
|---|---|---|---|---|
|
||||||
|
| `child.register` | `BaseNodeAdapter.js:122` | `{ topic:'child.register', payload:<node.id>, positionVsParent, distance }` | — | _(gap — see below)_ |
|
||||||
|
|
||||||
|
> Note: the canonical outgoing topic is **`child.register`** (matching the input
|
||||||
|
> registry). Earlier docs said `registerChild`; that is the deprecated input
|
||||||
|
> alias, not what this node emits.
|
||||||
|
|
||||||
|
## Child-facing events — `measurements.emitter`
|
||||||
|
|
||||||
|
Fired as `<type>.<variant>.<position>` when a series receives a value. Parents
|
||||||
|
subscribe by event name (data-driven, not a fixed catalogue):
|
||||||
|
|
||||||
|
| Event | When | Test file |
|
||||||
|
|---|---|---|
|
||||||
|
| `volume.predicted.atequipment` | each integrator tick | test/basic/flowAggregator.basic.test.js |
|
||||||
|
| `level.predicted.atequipment` | recomputed from volume | test/basic/specificClass.test.js |
|
||||||
|
| `flow.predicted.in` (child `manual-qin`) | `set.inflow` handler | test/basic/measurementRouter.basic.test.js |
|
||||||
|
| `overflowVolume`/`underflowVolume`/`flow.predicted.overflow` | integrator hits a physical bound | test/basic/flowAggregator.basic.test.js |
|
||||||
|
|
||||||
|
## Example-flow function-node fan-out
|
||||||
|
|
||||||
|
### examples/02-Dashboard.json :: `fn_status_split` (outputs: 15)
|
||||||
|
|
||||||
|
| # | Target widget | Payload | Populated | Degraded/null |
|
||||||
|
|---|---|---|---|---|
|
||||||
|
| 0 | ui-text "Mode" | string | ✔ structure | gap |
|
||||||
|
| 1 | ui-text "Direction" | string | ✔ | gap |
|
||||||
|
| 2 | ui-text "Level" | number m | ✔ | gap |
|
||||||
|
| 3 | ui-text "Volume" | number m³ | ✔ | gap |
|
||||||
|
| 4 | ui-text "Volume %" | number % | ✔ | gap |
|
||||||
|
| 5 | ui-text "percControl" | number % | ✔ | gap |
|
||||||
|
| 6 | ui-text "Manual demand" | number m³/h or — | gap | gap |
|
||||||
|
| 7 | ui-chart "Level (m)" | `{topic,payload:number}` or no-msg | ✔ | gap |
|
||||||
|
| 8 | ui-chart "Volume (m³)" | ″ | ✔ | gap |
|
||||||
|
| 9 | ui-chart "Volume %" | ″ | ✔ | gap |
|
||||||
|
| 10 | ui-chart "Flow (m³/h)" — Inflow | ″ | ✔ | gap |
|
||||||
|
| 11 | ui-chart "Flow (m³/h)" — Outflow | ″ | ✔ | gap |
|
||||||
|
| 12 | ui-chart "Flow (m³/h)" — Net | ″ | ✔ | gap |
|
||||||
|
| 13 | ui-template "Raw output table" | whole object (array) | ✔ | gap |
|
||||||
|
| 14 | ui-chart "percControl" | `{topic:'percControl',payload:number}` | ✔ | gap |
|
||||||
|
|
||||||
|
Populated/structure coverage: test/integration/basic-dashboard-flow.test.js
|
||||||
|
(asserts output count = 15 and routes outputs 0–14). **Degraded/empty-input**
|
||||||
|
coverage (no `payload:null` reaching any `ui-chart`) is still a gap — see below.
|
||||||
|
|
||||||
|
## Known coverage gaps (tracked, prospective per the rule)
|
||||||
|
|
||||||
|
The output-coverage rule applies prospectively. Outstanding items for this node:
|
||||||
|
|
||||||
|
- [ ] Dedicated `test/basic/output-port0.test.js` exercising **every** key above
|
||||||
|
in both populated and degraded (pre-tick / null) states.
|
||||||
|
- [ ] Port-1 line-protocol assertion (field names + tag).
|
||||||
|
- [ ] Port-2 `child.register` payload-shape test.
|
||||||
|
- [ ] `fn_status_split` degraded/empty-input fan-out test (no `payload:null` to
|
||||||
|
any `ui-chart`) — the failure mode the rule was written for. The structure
|
||||||
|
test in `basic-dashboard-flow.test.js` covers the populated path only.
|
||||||
@@ -35,7 +35,7 @@ test('basic dashboard flow contains the pumpingStation node and trend widgets',
|
|||||||
assert.equal(ps.inletPipeDiameter, 0.3);
|
assert.equal(ps.inletPipeDiameter, 0.3);
|
||||||
assert.equal(ps.outletPipeDiameter, 0.3);
|
assert.equal(ps.outletPipeDiameter, 0.3);
|
||||||
assert.ok(parser, 'fn_status_split should exist');
|
assert.ok(parser, 'fn_status_split should exist');
|
||||||
assert.equal(parser.outputs, 14);
|
assert.equal(parser.outputs, 15);
|
||||||
assert.equal(levelChart.type, 'ui-chart');
|
assert.equal(levelChart.type, 'ui-chart');
|
||||||
assert.equal(volumeChart.type, 'ui-chart');
|
assert.equal(volumeChart.type, 'ui-chart');
|
||||||
assert.equal(flowChart.type, 'ui-chart');
|
assert.equal(flowChart.type, 'ui-chart');
|
||||||
@@ -72,7 +72,7 @@ test('basic dashboard parser routes process fields to charts and state text', ()
|
|||||||
}, context, node);
|
}, context, node);
|
||||||
|
|
||||||
assert.ok(Array.isArray(out));
|
assert.ok(Array.isArray(out));
|
||||||
assert.equal(out.length, 14);
|
assert.equal(out.length, 15);
|
||||||
assert.equal(out[0].payload, 'levelbased');
|
assert.equal(out[0].payload, 'levelbased');
|
||||||
assert.equal(out[1].payload, 'filling');
|
assert.equal(out[1].payload, 'filling');
|
||||||
assert.equal(out[2].payload, '3.25 m');
|
assert.equal(out[2].payload, '3.25 m');
|
||||||
@@ -86,6 +86,7 @@ test('basic dashboard parser routes process fields to charts and state text', ()
|
|||||||
assert.deepEqual(out[11], { topic: 'Outflow', payload: 7.2 });
|
assert.deepEqual(out[11], { topic: 'Outflow', payload: 7.2 });
|
||||||
assert.deepEqual(out[12], { topic: 'Net', payload: 10.8 });
|
assert.deepEqual(out[12], { topic: 'Net', payload: 10.8 });
|
||||||
assert.ok(Array.isArray(out[13].payload));
|
assert.ok(Array.isArray(out[13].payload));
|
||||||
|
assert.deepEqual(out[14], { topic: 'percControl', payload: 25 });
|
||||||
});
|
});
|
||||||
|
|
||||||
test('basic dashboard parser keeps previous values when process output sends only changed fields', () => {
|
test('basic dashboard parser keeps previous values when process output sends only changed fields', () => {
|
||||||
|
|||||||
@@ -1,949 +0,0 @@
|
|||||||
#!/usr/bin/env node
|
|
||||||
'use strict';
|
|
||||||
|
|
||||||
/**
|
|
||||||
* build-examples.js — regenerate the three example flows for pumpingStation.
|
|
||||||
*
|
|
||||||
* Source of truth for the Tier 1/2/3 example flows under examples/.
|
|
||||||
* Follows EVOLV/.claude/rules/node-red-flow-layout.md:
|
|
||||||
* - Lane positions L0..L7 = [120, 360, 600, 840, 1080, 1320, 1560, 1800]
|
|
||||||
* - S88 colours per Node-RED group (Process Cell = #0c99d9, Unit = #50a8d9,
|
|
||||||
* Equipment Module = #86bbdd, Control Module = #a9daee, neutral = #dddddd)
|
|
||||||
* - Cross-tab wiring via named link out/link in channels (cmd:* / evt:* / setup:*)
|
|
||||||
* - ui-chart objects carry every mandatory key (interpolation, yAxisProperty,
|
|
||||||
* xAxisPropertyType, action, removeOlder*, colors, etc.) — omitting any
|
|
||||||
* causes FlowFuse to render the chart blank with no error.
|
|
||||||
*
|
|
||||||
* Only canonical pumpingStation topic names are used (per CONTRACT.md):
|
|
||||||
* set.mode, set.inflow, set.demand, cmd.calibrate.volume, cmd.calibrate.level.
|
|
||||||
*
|
|
||||||
* Run from repo root or any cwd:
|
|
||||||
* node nodes/pumpingStation/tools/build-examples.js
|
|
||||||
*/
|
|
||||||
|
|
||||||
const fs = require('fs');
|
|
||||||
const path = require('path');
|
|
||||||
|
|
||||||
const OUT_DIR = path.join(__dirname, '..', 'examples');
|
|
||||||
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
/* Layout constants */
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
|
|
||||||
const LANE_X = [120, 360, 600, 840, 1080, 1320, 1560, 1800];
|
|
||||||
const S88 = {
|
|
||||||
AR: '#0f52a5',
|
|
||||||
PC: '#0c99d9',
|
|
||||||
UN: '#50a8d9',
|
|
||||||
EM: '#86bbdd',
|
|
||||||
CM: '#a9daee',
|
|
||||||
neutral: '#dddddd',
|
|
||||||
};
|
|
||||||
|
|
||||||
const CHART_COLORS = [
|
|
||||||
'#0095FF', '#FF0000', '#FF7F0E', '#2CA02C', '#A347E1',
|
|
||||||
'#D62728', '#FF9896', '#9467BD', '#C5B0D5',
|
|
||||||
];
|
|
||||||
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
/* Helpers */
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
|
|
||||||
function tab(id, label, info) {
|
|
||||||
return { id, type: 'tab', label, disabled: false, info: info || '' };
|
|
||||||
}
|
|
||||||
|
|
||||||
function comment(id, z, name, x, y) {
|
|
||||||
return { id, type: 'comment', z, name, info: '', x, y, wires: [] };
|
|
||||||
}
|
|
||||||
|
|
||||||
function linkOut(id, z, name, x, y, links) {
|
|
||||||
return { id, type: 'link out', z, name, mode: 'link', links: links || [], x, y, wires: [] };
|
|
||||||
}
|
|
||||||
|
|
||||||
function linkIn(id, z, name, x, y, links, downstream) {
|
|
||||||
return { id, type: 'link in', z, name, links: links || [], x, y, wires: [downstream || []] };
|
|
||||||
}
|
|
||||||
|
|
||||||
function inject(id, z, name, topic, payload, payloadType, x, y, wires, opts) {
|
|
||||||
const o = opts || {};
|
|
||||||
return {
|
|
||||||
id, type: 'inject', z, name,
|
|
||||||
props: [
|
|
||||||
{ p: 'topic', vt: 'str' },
|
|
||||||
{ p: 'payload', v: String(payload), vt: payloadType },
|
|
||||||
],
|
|
||||||
topic,
|
|
||||||
repeat: o.repeat || '',
|
|
||||||
crontab: '',
|
|
||||||
once: !!o.once,
|
|
||||||
onceDelay: o.onceDelay || '',
|
|
||||||
x, y,
|
|
||||||
wires: [wires || []],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function fn(id, z, name, code, x, y, wires, outputs) {
|
|
||||||
return {
|
|
||||||
id, type: 'function', z, name,
|
|
||||||
func: code,
|
|
||||||
outputs: outputs || 1,
|
|
||||||
noerr: 0,
|
|
||||||
initialize: '',
|
|
||||||
finalize: '',
|
|
||||||
libs: [],
|
|
||||||
x, y,
|
|
||||||
wires: wires || [[]],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function debugNode(id, z, name, x, y, complete, targetType, active) {
|
|
||||||
return {
|
|
||||||
id, type: 'debug', z, name,
|
|
||||||
active: active !== false,
|
|
||||||
tosidebar: true,
|
|
||||||
console: false,
|
|
||||||
tostatus: false,
|
|
||||||
complete: complete || 'payload',
|
|
||||||
targetType: targetType || 'msg',
|
|
||||||
x, y, wires: [],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function group(id, z, name, color, nodes, bbox) {
|
|
||||||
return {
|
|
||||||
id, type: 'group', z, name,
|
|
||||||
style: { label: true, stroke: '#000000', fill: color, 'fill-opacity': '0.10' },
|
|
||||||
nodes,
|
|
||||||
x: bbox.x, y: bbox.y, w: bbox.w, h: bbox.h,
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function bboxOf(nodeList, ids, pad) {
|
|
||||||
const p = pad == null ? 20 : pad;
|
|
||||||
const ns = nodeList.filter((n) => ids.includes(n.id));
|
|
||||||
const xs = ns.map((n) => n.x || 0);
|
|
||||||
const ys = ns.map((n) => n.y || 0);
|
|
||||||
const minX = Math.min(...xs) - p;
|
|
||||||
const minY = Math.min(...ys) - p - 20;
|
|
||||||
const w = Math.max(...xs) - Math.min(...xs) + 200 + 2 * p;
|
|
||||||
const h = Math.max(...ys) - Math.min(...ys) + 60 + 2 * p;
|
|
||||||
return { x: minX, y: minY, w, h };
|
|
||||||
}
|
|
||||||
|
|
||||||
/* Build a fully-specified pumpingStation node. Every config field is set
|
|
||||||
* explicitly per rule §9 (no schema-default reliance for operational
|
|
||||||
* parameters). 50 m³ basin, 3.5 m height, inflow at 3 m, outflow at 0.2 m,
|
|
||||||
* overflow at 3.2 m. Level thresholds chosen so levelbased control activates
|
|
||||||
* mid-tank and saturates near overflow.
|
|
||||||
*/
|
|
||||||
function pumpingStationNode(id, z, name, x, y, wires) {
|
|
||||||
return {
|
|
||||||
id, type: 'pumpingStation', z, name,
|
|
||||||
simulator: false,
|
|
||||||
basinVolume: 50,
|
|
||||||
basinHeight: 3.5,
|
|
||||||
inflowLevel: 3.0,
|
|
||||||
outflowLevel: 0.2,
|
|
||||||
overflowLevel: 3.2,
|
|
||||||
defaultFluid: 'wastewater',
|
|
||||||
inletPipeDiameter: 0.3,
|
|
||||||
outletPipeDiameter: 0.3,
|
|
||||||
pipelineLength: 80,
|
|
||||||
maxDischargeHead: 24,
|
|
||||||
staticHead: 12,
|
|
||||||
maxInflowRate: 200,
|
|
||||||
temperatureReferenceDegC: 15,
|
|
||||||
timeleftToFullOrEmptyThresholdSeconds: 0,
|
|
||||||
enableDryRunProtection: true,
|
|
||||||
enableOverfillProtection: true,
|
|
||||||
dryRunThresholdPercent: 2,
|
|
||||||
overfillThresholdPercent: 98,
|
|
||||||
minHeightBasedOn: 'outlet',
|
|
||||||
processOutputFormat: 'process',
|
|
||||||
dbaseOutputFormat: 'influxdb',
|
|
||||||
refHeight: 'NAP',
|
|
||||||
basinBottomRef: 1,
|
|
||||||
uuid: 'example-ps-001',
|
|
||||||
supplier: 'WBD-RD',
|
|
||||||
category: 'station',
|
|
||||||
assetType: 'pumpingstation',
|
|
||||||
model: 'demo-50m3',
|
|
||||||
unit: 'm3/h',
|
|
||||||
enableLog: true,
|
|
||||||
logLevel: 'info',
|
|
||||||
positionVsParent: 'atEquipment',
|
|
||||||
positionIcon: '',
|
|
||||||
hasDistance: false,
|
|
||||||
distance: '',
|
|
||||||
distanceUnit: 'm',
|
|
||||||
distanceDescription: '',
|
|
||||||
controlMode: 'levelbased',
|
|
||||||
startLevel: 1.2,
|
|
||||||
minLevel: 0.4,
|
|
||||||
maxLevel: 2.8,
|
|
||||||
flowSetpoint: null,
|
|
||||||
flowDeadband: null,
|
|
||||||
x, y,
|
|
||||||
wires: wires || [[], [], []],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function measurementLevelNode(id, z, name, x, y, wires) {
|
|
||||||
return {
|
|
||||||
id, type: 'measurement', z, name,
|
|
||||||
mode: 'analog',
|
|
||||||
channels: '[]',
|
|
||||||
scaling: false,
|
|
||||||
i_min: 0, i_max: 0, i_offset: 0,
|
|
||||||
o_min: 0, o_max: 1,
|
|
||||||
simulator: true,
|
|
||||||
smooth_method: 'mean',
|
|
||||||
count: 5,
|
|
||||||
processOutputFormat: 'process',
|
|
||||||
dbaseOutputFormat: 'influxdb',
|
|
||||||
uuid: 'example-level-001',
|
|
||||||
supplier: 'vega',
|
|
||||||
category: 'sensor',
|
|
||||||
assetType: 'level',
|
|
||||||
model: 'VEGAPULS-31',
|
|
||||||
unit: 'm',
|
|
||||||
assetTagNumber: 'LT-001',
|
|
||||||
enableLog: false,
|
|
||||||
logLevel: 'error',
|
|
||||||
positionVsParent: 'atEquipment',
|
|
||||||
positionIcon: '',
|
|
||||||
hasDistance: false,
|
|
||||||
distance: 0,
|
|
||||||
distanceUnit: 'm',
|
|
||||||
distanceDescription: '',
|
|
||||||
x, y,
|
|
||||||
wires: wires || [[], [], []],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function machineGroupControlNode(id, z, name, x, y, wires) {
|
|
||||||
return {
|
|
||||||
id, type: 'machineGroupControl', z, name,
|
|
||||||
enableLog: true,
|
|
||||||
logLevel: 'info',
|
|
||||||
positionVsParent: 'atEquipment',
|
|
||||||
positionIcon: '',
|
|
||||||
hasDistance: false,
|
|
||||||
distance: '',
|
|
||||||
distanceUnit: 'm',
|
|
||||||
x, y,
|
|
||||||
wires: wires || [[], [], []],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function rotatingMachineNode(id, z, name, uuid, x, y, wires) {
|
|
||||||
return {
|
|
||||||
id, type: 'rotatingMachine', z, name,
|
|
||||||
speed: '1',
|
|
||||||
startup: '2', warmup: '1', shutdown: '2', cooldown: '1',
|
|
||||||
movementMode: 'staticspeed',
|
|
||||||
machineCurve: '',
|
|
||||||
uuid,
|
|
||||||
supplier: 'hidrostal',
|
|
||||||
category: 'pump',
|
|
||||||
assetType: 'pump-centrifugal',
|
|
||||||
model: 'hidrostal-H05K-S03R',
|
|
||||||
unit: 'm3/h',
|
|
||||||
curvePressureUnit: 'mbar',
|
|
||||||
curveFlowUnit: 'm3/h',
|
|
||||||
curvePowerUnit: 'kW',
|
|
||||||
curveControlUnit: '%',
|
|
||||||
enableLog: false,
|
|
||||||
logLevel: 'error',
|
|
||||||
positionVsParent: 'atEquipment',
|
|
||||||
positionIcon: '',
|
|
||||||
hasDistance: false,
|
|
||||||
distance: '',
|
|
||||||
distanceUnit: 'm',
|
|
||||||
distanceDescription: '',
|
|
||||||
x, y,
|
|
||||||
wires: wires || [[], [], []],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
/* FlowFuse ui-chart with every required key (per layout rule §4). */
|
|
||||||
function uiChart(id, z, group, name, label, order, yAxisLabel, x, y, color) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-chart', z, group, name, label,
|
|
||||||
order, width: 12, height: 6,
|
|
||||||
chartType: 'line',
|
|
||||||
category: 'topic',
|
|
||||||
categoryType: 'msg',
|
|
||||||
xAxisLabel: 'time',
|
|
||||||
xAxisType: 'time',
|
|
||||||
xAxisProperty: '',
|
|
||||||
xAxisPropertyType: 'timestamp',
|
|
||||||
xAxisFormat: '',
|
|
||||||
xAxisFormatType: 'auto',
|
|
||||||
yAxisLabel,
|
|
||||||
yAxisProperty: 'payload',
|
|
||||||
yAxisPropertyType: 'msg',
|
|
||||||
xmin: '', xmax: '', ymin: '', ymax: '',
|
|
||||||
bins: 10,
|
|
||||||
action: 'append',
|
|
||||||
stackSeries: false,
|
|
||||||
pointShape: 'circle',
|
|
||||||
pointRadius: 4,
|
|
||||||
interpolation: 'linear',
|
|
||||||
showLegend: true,
|
|
||||||
className: '',
|
|
||||||
removeOlder: '15',
|
|
||||||
removeOlderUnit: '60',
|
|
||||||
removeOlderPoints: '200',
|
|
||||||
colors: color ? [color, ...CHART_COLORS.slice(1)] : CHART_COLORS,
|
|
||||||
textColor: ['#666666'],
|
|
||||||
textColorDefault: true,
|
|
||||||
gridColor: ['#e5e5e5'],
|
|
||||||
gridColorDefault: true,
|
|
||||||
x, y, wires: [],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function uiText(id, z, group, name, label, order, x, y, format) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-text', z, group, name, label,
|
|
||||||
order, width: 4, height: 1,
|
|
||||||
format: format || '{{msg.payload}}',
|
|
||||||
layout: 'row-spread',
|
|
||||||
x, y, wires: [],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function uiSlider(id, z, group, name, label, order, x, y, topic, min, max, step) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-slider', z, group, name, label,
|
|
||||||
order, width: 6, height: 1,
|
|
||||||
passthru: true,
|
|
||||||
outs: 'end',
|
|
||||||
topic,
|
|
||||||
topicType: 'str',
|
|
||||||
min, max, step,
|
|
||||||
icon: '',
|
|
||||||
thumbLabel: 'always',
|
|
||||||
showValue: true,
|
|
||||||
className: '',
|
|
||||||
x, y, wires: [[]],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function uiDropdown(id, z, group, name, label, order, x, y, topic, options, wires) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-dropdown', z, group, name, label,
|
|
||||||
order, width: 6, height: 1,
|
|
||||||
passthru: true,
|
|
||||||
multiple: false,
|
|
||||||
options: options.map((o) => ({ label: o, value: o, type: 'str' })),
|
|
||||||
payload: '',
|
|
||||||
topic,
|
|
||||||
topicType: 'str',
|
|
||||||
x, y,
|
|
||||||
wires: [wires || []],
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function uiBase(id) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-base',
|
|
||||||
name: 'EVOLV Demo',
|
|
||||||
path: '/dashboard',
|
|
||||||
appIcon: '',
|
|
||||||
includeClientData: true,
|
|
||||||
acceptsClientConfig: ['ui-notification', 'ui-control'],
|
|
||||||
showPathInSidebar: false,
|
|
||||||
headerContent: 'page',
|
|
||||||
navigationStyle: 'default',
|
|
||||||
titleBarStyle: 'default',
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function uiTheme(id) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-theme',
|
|
||||||
name: 'EVOLV Theme',
|
|
||||||
colors: {
|
|
||||||
surface: '#ffffff', primary: '#0c99d9', bgPage: '#eeeeee',
|
|
||||||
groupBg: '#ffffff', groupOutline: '#cccccc',
|
|
||||||
},
|
|
||||||
sizes: {
|
|
||||||
density: 'default', pagePadding: '14px', groupGap: '14px',
|
|
||||||
groupBorderRadius: '6px', widgetGap: '12px',
|
|
||||||
},
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function uiPage(id, base, theme, name, path, order) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-page', name, ui: base, path,
|
|
||||||
icon: 'water',
|
|
||||||
layout: 'grid', theme,
|
|
||||||
breakpoints: [{ name: 'Default', px: '0', cols: '12' }],
|
|
||||||
order, className: '',
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
function uiGroup(id, page, name, width, height, order) {
|
|
||||||
return {
|
|
||||||
id, type: 'ui-group', name, page, width, height, order,
|
|
||||||
showTitle: true, className: '',
|
|
||||||
};
|
|
||||||
}
|
|
||||||
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
/* Tier 1 — 01-Basic.json */
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
|
|
||||||
function buildBasic() {
|
|
||||||
const Z = 'ps_basic_tab';
|
|
||||||
const nodes = [];
|
|
||||||
|
|
||||||
nodes.push(tab(Z, 'PumpingStation - Basic',
|
|
||||||
'Tier 1: single pumpingStation node driven by inject nodes only. ' +
|
|
||||||
'Demonstrates the canonical Phase-2 topic API: set.mode, set.inflow, set.demand.'));
|
|
||||||
|
|
||||||
nodes.push(comment('ps_basic_title', Z,
|
|
||||||
'PumpingStation - Basic\n' +
|
|
||||||
'━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━\n' +
|
|
||||||
'A 50 m³ basin (3.5 m tall, inflow at 3.0 m, outflow at 0.2 m,\n' +
|
|
||||||
'overflow at 3.2 m). controlMode = levelbased, manual demand allowed\n' +
|
|
||||||
'only when set.mode = manual.\n\n' +
|
|
||||||
'HOW TO USE:\n' +
|
|
||||||
' 1. Deploy the flow.\n' +
|
|
||||||
' 2. Click "set.mode = manual" so set.demand is honoured.\n' +
|
|
||||||
' 3. Click "set.inflow = 60 m3/h" to push wastewater into the basin.\n' +
|
|
||||||
' 4. Watch the basin fill on Port 0 (level, volume, percControl rise).\n' +
|
|
||||||
' 5. Click "calibrate volume 25 m3" to jump straight to half-full.\n\n' +
|
|
||||||
'Aliases (changemode, q_in, Qd, …) still work but log a deprecation\n' +
|
|
||||||
'warning - fresh flows use the canonical names.', 600, 40));
|
|
||||||
|
|
||||||
// Lane 0: link-in placeholders (none for Tier 1 - all inputs are local).
|
|
||||||
// Lane 2..3: inject nodes (we keep them in lane 1 for proximity).
|
|
||||||
const injectMode = inject('ps_basic_inj_mode', Z, 'set.mode = manual', 'set.mode', 'manual', 'str', 200, 160, ['ps_basic_node']);
|
|
||||||
const injectModeLvl = inject('ps_basic_inj_mode_lvl',Z, 'set.mode = levelbased','set.mode', 'levelbased', 'str', 220, 200, ['ps_basic_node']);
|
|
||||||
const injectInflow = inject('ps_basic_inj_inflow', Z, 'set.inflow = 60 m3/h', 'set.inflow', '60', 'num', 200, 260, ['ps_basic_node']);
|
|
||||||
const injectDemand = inject('ps_basic_inj_demand', Z, 'set.demand = 40 %', 'set.demand', '40', 'num', 200, 300, ['ps_basic_node']);
|
|
||||||
const injectCalVol = inject('ps_basic_inj_calvol', Z, 'calibrate volume 25 m3','cmd.calibrate.volume','25','num', 220, 360, ['ps_basic_node']);
|
|
||||||
const injectCalLvl = inject('ps_basic_inj_callvl', Z, 'calibrate level 1.5 m','cmd.calibrate.level','1.5','num', 220, 400, ['ps_basic_node']);
|
|
||||||
nodes.push(injectMode, injectModeLvl, injectInflow, injectDemand, injectCalVol, injectCalLvl);
|
|
||||||
|
|
||||||
// Lane 5 (PC): the pumpingStation itself.
|
|
||||||
const ps = pumpingStationNode('ps_basic_node', Z, 'Pumping Station', LANE_X[5], 300,
|
|
||||||
[['ps_basic_format'], ['ps_basic_dbg_influx'], ['ps_basic_dbg_parent']]);
|
|
||||||
nodes.push(ps);
|
|
||||||
|
|
||||||
// Lane 6: format/merge function for Port 0.
|
|
||||||
const formatFn = fn('ps_basic_format', Z, 'Merge deltas + format',
|
|
||||||
"const p = (msg && msg.payload && typeof msg.payload === 'object') ? msg.payload : {};\n" +
|
|
||||||
"const cache = context.get('c') || {};\n" +
|
|
||||||
"Object.assign(cache, p);\n" +
|
|
||||||
"context.set('c', cache);\n" +
|
|
||||||
"function pick(prefix) {\n" +
|
|
||||||
" for (const k of Object.keys(cache)) if (k === prefix || k.indexOf(prefix + '.') === 0) {\n" +
|
|
||||||
" const v = Number(cache[k]); if (Number.isFinite(v)) return v;\n" +
|
|
||||||
" } return null;\n" +
|
|
||||||
"}\n" +
|
|
||||||
"const vol = pick('volume.predicted.atequipment');\n" +
|
|
||||||
"const lvl = pick('level.predicted.atequipment');\n" +
|
|
||||||
"const flIn = pick('flow.predicted.in');\n" +
|
|
||||||
"msg.payload = {\n" +
|
|
||||||
" state: cache.state || 'unknown',\n" +
|
|
||||||
" controlMode: cache.controlMode || cache.mode || 'n/a',\n" +
|
|
||||||
" direction: cache.direction || 'n/a',\n" +
|
|
||||||
" percControl: cache.percControl != null ? Number(cache.percControl).toFixed(1) + ' %' : 'n/a',\n" +
|
|
||||||
" volume: vol != null ? vol.toFixed(2) + ' m3' : 'n/a',\n" +
|
|
||||||
" volumePercent: cache.volumePercent != null ? Number(cache.volumePercent).toFixed(1) + ' %' : 'n/a',\n" +
|
|
||||||
" level: lvl != null ? lvl.toFixed(3) + ' m' : 'n/a',\n" +
|
|
||||||
" inflow: flIn != null ? (flIn * 3600).toFixed(1) + ' m3/h' : 'n/a',\n" +
|
|
||||||
" timeToFull: cache.timeToFull != null ? Number(cache.timeToFull).toFixed(0) + ' s' : 'n/a',\n" +
|
|
||||||
" timeToEmpty: cache.timeToEmpty != null ? Number(cache.timeToEmpty).toFixed(0) + ' s' : 'n/a'\n" +
|
|
||||||
"};\nreturn msg;",
|
|
||||||
LANE_X[6], 280, [['ps_basic_dbg_process']]);
|
|
||||||
nodes.push(formatFn);
|
|
||||||
|
|
||||||
// Lane 7: debug taps.
|
|
||||||
nodes.push(debugNode('ps_basic_dbg_process', Z, 'Port 0: Process', LANE_X[7], 240, 'payload', 'msg', true));
|
|
||||||
nodes.push(debugNode('ps_basic_dbg_influx', Z, 'Port 1: InfluxDB', LANE_X[7], 320, 'true', 'full', false));
|
|
||||||
nodes.push(debugNode('ps_basic_dbg_parent', Z, 'Port 2: Parent reg', LANE_X[7], 380, 'true', 'full', true));
|
|
||||||
|
|
||||||
// Wrap the station + its formatter in a Process Cell group box.
|
|
||||||
const psGroupIds = ['ps_basic_node', 'ps_basic_format'];
|
|
||||||
nodes.push(group('grp_ps_basic', Z, 'Pumping Station (PC)', S88.PC, psGroupIds,
|
|
||||||
bboxOf(nodes, psGroupIds, 30)));
|
|
||||||
|
|
||||||
return nodes;
|
|
||||||
}
|
|
||||||
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
/* Tier 2 — 02-Integration.json */
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
|
|
||||||
function buildIntegration() {
|
|
||||||
const TAB_PROC = 'ps_int_proc';
|
|
||||||
const TAB_SETUP = 'ps_int_setup';
|
|
||||||
const nodes = [];
|
|
||||||
|
|
||||||
nodes.push(tab(TAB_PROC, 'Process Plant',
|
|
||||||
'Tier 2: pumpingStation + measurement child + machineGroupControl parent with two rotatingMachine pumps. ' +
|
|
||||||
'Demonstrates Phase-2 parent/child handshakes and the canonical set.mode/set.inflow/set.demand topics.'));
|
|
||||||
nodes.push(tab(TAB_SETUP, 'Setup',
|
|
||||||
'Deploy-time once-true injects that initialise control modes on the EVOLV nodes.'));
|
|
||||||
|
|
||||||
/* ---------- Process Plant tab ---------------------------------- */
|
|
||||||
|
|
||||||
nodes.push(comment('ps_int_title', TAB_PROC,
|
|
||||||
'PumpingStation - Integration\n' +
|
|
||||||
'━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━\n' +
|
|
||||||
'L0 link-ins | L2 level sensor (CM) | L3 pumps (EM) | L4 MGC (UN) | L5 station (PC).\n' +
|
|
||||||
'Pumps register with MGC via Port 2; MGC and the level sensor register with the station via Port 2.\n' +
|
|
||||||
'Cross-tab channels: setup:* drive once-true initialisation from the Setup tab.', 600, 40));
|
|
||||||
|
|
||||||
/* Link-ins on L0 receive from the Setup tab. */
|
|
||||||
const linInMode = linkIn('lin_setup_mode', TAB_PROC, 'setup:to-ps-mode', LANE_X[0], 500, [], ['ps_int_station']);
|
|
||||||
const linInInflow = linkIn('lin_setup_inflow', TAB_PROC, 'setup:to-ps-inflow', LANE_X[0], 560, [], ['ps_int_station']);
|
|
||||||
const linInMgcMode = linkIn('lin_setup_mgcmode', TAB_PROC, 'setup:to-mgc-mode', LANE_X[0], 360, [], ['ps_int_mgc']);
|
|
||||||
nodes.push(linInMode, linInInflow, linInMgcMode);
|
|
||||||
|
|
||||||
/* L2: level measurement (Control Module). */
|
|
||||||
const levelMeas = measurementLevelNode('meas_level', TAB_PROC, 'Basin level sensor',
|
|
||||||
LANE_X[2], 700, [['ps_int_dbg_level'], [], ['ps_int_station']]);
|
|
||||||
nodes.push(levelMeas);
|
|
||||||
// Simulator measurement injector for the level sensor (push a varying level so PS sees something).
|
|
||||||
const levelInj = inject('ps_int_inj_level', TAB_PROC, 'sim level 1.6 m', 'measurement', '1.6', 'num', LANE_X[0], 700, ['meas_level']);
|
|
||||||
nodes.push(levelInj);
|
|
||||||
|
|
||||||
/* L3: two rotatingMachine pumps (Equipment Module). */
|
|
||||||
const pumpA = rotatingMachineNode('pump_a', TAB_PROC, 'Pump A', 'example-pump-a',
|
|
||||||
LANE_X[3], 320, [['ps_int_dbg_pa'], [], ['ps_int_mgc']]);
|
|
||||||
const pumpB = rotatingMachineNode('pump_b', TAB_PROC, 'Pump B', 'example-pump-b',
|
|
||||||
LANE_X[3], 400, [['ps_int_dbg_pb'], [], ['ps_int_mgc']]);
|
|
||||||
nodes.push(pumpA, pumpB);
|
|
||||||
|
|
||||||
/* L4: MGC (Unit). */
|
|
||||||
const mgc = machineGroupControlNode('ps_int_mgc', TAB_PROC, 'Pump Group',
|
|
||||||
LANE_X[4], 360, [['ps_int_dbg_mgc'], [], ['ps_int_station']]);
|
|
||||||
nodes.push(mgc);
|
|
||||||
|
|
||||||
/* L5: pumpingStation (Process Cell). */
|
|
||||||
const station = pumpingStationNode('ps_int_station', TAB_PROC, 'Pumping Station',
|
|
||||||
LANE_X[5], 520, [['ps_int_format'], ['ps_int_dbg_influx'], []]);
|
|
||||||
nodes.push(station);
|
|
||||||
|
|
||||||
/* L6: formatter for the station's Port 0. */
|
|
||||||
const formatFn = fn('ps_int_format', TAB_PROC, 'Merge deltas + format',
|
|
||||||
"const p = (msg && msg.payload && typeof msg.payload === 'object') ? msg.payload : {};\n" +
|
|
||||||
"const cache = context.get('c') || {}; Object.assign(cache, p); context.set('c', cache);\n" +
|
|
||||||
"function pick(prefix){ for (const k of Object.keys(cache)) if (k===prefix||k.indexOf(prefix+'.')===0){ const v=Number(cache[k]); if(Number.isFinite(v)) return v;} return null; }\n" +
|
|
||||||
"const vol=pick('volume.predicted.atequipment'), lvl=pick('level.predicted.atequipment'), flIn=pick('flow.predicted.in'), flOut=pick('flow.predicted.out');\n" +
|
|
||||||
"msg.payload = {\n" +
|
|
||||||
" state: cache.state || 'unknown',\n" +
|
|
||||||
" controlMode: cache.controlMode || cache.mode || 'n/a',\n" +
|
|
||||||
" direction: cache.direction || 'n/a',\n" +
|
|
||||||
" percControl: cache.percControl != null ? Number(cache.percControl).toFixed(1)+' %' : 'n/a',\n" +
|
|
||||||
" volume: vol != null ? vol.toFixed(2)+' m3' : 'n/a',\n" +
|
|
||||||
" volumePercent: cache.volumePercent != null ? Number(cache.volumePercent).toFixed(1)+' %' : 'n/a',\n" +
|
|
||||||
" level: lvl != null ? lvl.toFixed(3)+' m' : 'n/a',\n" +
|
|
||||||
" inflow: flIn != null ? (flIn*3600).toFixed(1)+' m3/h' : 'n/a',\n" +
|
|
||||||
" outflow: flOut != null ? (flOut*3600).toFixed(1)+' m3/h' : 'n/a',\n" +
|
|
||||||
" childCount: cache.childCount != null ? cache.childCount : 'n/a'\n" +
|
|
||||||
"};\nreturn msg;",
|
|
||||||
LANE_X[6], 520, [['ps_int_dbg_process']]);
|
|
||||||
nodes.push(formatFn);
|
|
||||||
|
|
||||||
/* L7: debug taps for the various ports. */
|
|
||||||
nodes.push(debugNode('ps_int_dbg_process', TAB_PROC, 'PS Port 0: Process', LANE_X[7], 480, 'payload', 'msg', true));
|
|
||||||
nodes.push(debugNode('ps_int_dbg_influx', TAB_PROC, 'PS Port 1: InfluxDB', LANE_X[7], 540, 'true', 'full', false));
|
|
||||||
nodes.push(debugNode('ps_int_dbg_mgc', TAB_PROC, 'MGC Port 0', LANE_X[7], 360, 'payload', 'msg', true));
|
|
||||||
nodes.push(debugNode('ps_int_dbg_pa', TAB_PROC, 'Pump A Port 0', LANE_X[7], 320, 'payload', 'msg', false));
|
|
||||||
nodes.push(debugNode('ps_int_dbg_pb', TAB_PROC, 'Pump B Port 0', LANE_X[7], 400, 'payload', 'msg', false));
|
|
||||||
nodes.push(debugNode('ps_int_dbg_level', TAB_PROC, 'Level Port 0', LANE_X[7], 700, 'payload', 'msg', false));
|
|
||||||
|
|
||||||
/* Group boxes. */
|
|
||||||
const pumpAIds = ['pump_a', 'ps_int_dbg_pa'];
|
|
||||||
const pumpBIds = ['pump_b', 'ps_int_dbg_pb'];
|
|
||||||
const mgcIds = ['ps_int_mgc', 'ps_int_dbg_mgc', 'lin_setup_mgcmode'];
|
|
||||||
const stationIds = ['ps_int_station', 'ps_int_format', 'ps_int_dbg_process', 'ps_int_dbg_influx', 'lin_setup_mode', 'lin_setup_inflow'];
|
|
||||||
const levelIds = ['meas_level', 'ps_int_inj_level', 'ps_int_dbg_level'];
|
|
||||||
nodes.push(group('grp_pumpa', TAB_PROC, 'Pump A (EM)', S88.EM, pumpAIds, bboxOf(nodes, pumpAIds, 25)));
|
|
||||||
nodes.push(group('grp_pumpb', TAB_PROC, 'Pump B (EM)', S88.EM, pumpBIds, bboxOf(nodes, pumpBIds, 25)));
|
|
||||||
nodes.push(group('grp_mgc', TAB_PROC, 'Pump Group MGC (UN)', S88.UN, mgcIds, bboxOf(nodes, mgcIds, 25)));
|
|
||||||
nodes.push(group('grp_station', TAB_PROC, 'Pumping Station (PC)', S88.PC, stationIds, bboxOf(nodes, stationIds, 25)));
|
|
||||||
nodes.push(group('grp_level', TAB_PROC, 'Level Sensor (CM)', S88.CM, levelIds, bboxOf(nodes, levelIds, 25)));
|
|
||||||
|
|
||||||
/* ---------- Setup tab ----------------------------------------- */
|
|
||||||
|
|
||||||
nodes.push(comment('setup_title', TAB_SETUP,
|
|
||||||
'Deploy-time setup\n' +
|
|
||||||
'━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━\n' +
|
|
||||||
'Fires once after each deploy: pushes the canonical set.mode / set.inflow /\n' +
|
|
||||||
'set.demand topics across cross-tab channels into the Process Plant tab.',
|
|
||||||
LANE_X[2], 40));
|
|
||||||
|
|
||||||
const setMode = inject('setup_inj_mode', TAB_SETUP, 'set.mode = levelbased', 'set.mode', 'levelbased', 'str', LANE_X[0], 160, ['lout_setup_mode'], { once: true, onceDelay: '0.5' });
|
|
||||||
const setMgc = inject('setup_inj_mgcmode', TAB_SETUP, 'MGC set.mode = auto', 'set.mode', 'auto', 'str', LANE_X[0], 220, ['lout_setup_mgcmode'],{ once: true, onceDelay: '0.5' });
|
|
||||||
const setInflow = inject('setup_inj_inflow', TAB_SETUP, 'seed inflow 60 m3/h', 'set.inflow', '60', 'num', LANE_X[0], 280, ['lout_setup_inflow'], { once: true, onceDelay: '1.0' });
|
|
||||||
nodes.push(setMode, setMgc, setInflow);
|
|
||||||
|
|
||||||
const loutMode = linkOut('lout_setup_mode', TAB_SETUP, 'setup:to-ps-mode', LANE_X[7], 160, ['lin_setup_mode']);
|
|
||||||
const loutMgcMode = linkOut('lout_setup_mgcmode', TAB_SETUP, 'setup:to-mgc-mode', LANE_X[7], 220, ['lin_setup_mgcmode']);
|
|
||||||
const loutInflow = linkOut('lout_setup_inflow', TAB_SETUP, 'setup:to-ps-inflow', LANE_X[7], 280, ['lin_setup_inflow']);
|
|
||||||
nodes.push(loutMode, loutMgcMode, loutInflow);
|
|
||||||
|
|
||||||
// Setup tab group.
|
|
||||||
const setupIds = ['setup_inj_mode', 'setup_inj_mgcmode', 'setup_inj_inflow',
|
|
||||||
'lout_setup_mode', 'lout_setup_mgcmode', 'lout_setup_inflow'];
|
|
||||||
nodes.push(group('grp_setup', TAB_SETUP, 'Deploy-time setup', S88.neutral, setupIds, bboxOf(nodes, setupIds, 25)));
|
|
||||||
|
|
||||||
return nodes;
|
|
||||||
}
|
|
||||||
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
/* Tier 3 — 03-Dashboard.json */
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
|
|
||||||
function buildDashboard() {
|
|
||||||
const TAB_PROC = 'ps_dash_proc';
|
|
||||||
const TAB_UI = 'ps_dash_ui';
|
|
||||||
const TAB_SETUP = 'ps_dash_setup';
|
|
||||||
const nodes = [];
|
|
||||||
|
|
||||||
nodes.push(tab(TAB_PROC, 'Process Plant',
|
|
||||||
'Tier 3: full station with measurement + MGC + 2 pumps, formatted for live dashboard.'));
|
|
||||||
nodes.push(tab(TAB_UI, 'Dashboard UI',
|
|
||||||
'FlowFuse dashboard 2.0: 3 charts (flow / level / volumePercent), text widgets and 2 sliders.'));
|
|
||||||
nodes.push(tab(TAB_SETUP, 'Setup',
|
|
||||||
'Once-true injects: initial mode + initial inflow seed.'));
|
|
||||||
|
|
||||||
/* ---------- FlowFuse dashboard scaffolding -------------------- */
|
|
||||||
|
|
||||||
nodes.push(uiBase('ps_dash_base'));
|
|
||||||
nodes.push(uiTheme('ps_dash_theme'));
|
|
||||||
nodes.push(uiPage('ps_dash_page', 'ps_dash_base', 'ps_dash_theme', 'PumpingStation Demo', '/pumping-station', 1));
|
|
||||||
nodes.push(uiGroup('ps_dash_grp_ctrl', 'ps_dash_page', 'Controls', 6, 1, 1));
|
|
||||||
nodes.push(uiGroup('ps_dash_grp_status', 'ps_dash_page', 'Operator Status', 6, 1, 2));
|
|
||||||
nodes.push(uiGroup('ps_dash_grp_trend', 'ps_dash_page', 'Live Trends', 12, 1, 3));
|
|
||||||
|
|
||||||
/* ---------- Process Plant tab --------------------------------- */
|
|
||||||
|
|
||||||
nodes.push(comment('ps_dash_proc_title', TAB_PROC,
|
|
||||||
'Process Plant\n━━━━━━━━━━━━━━━━━\nFull station with parent (MGC) and 2 pump children.\n' +
|
|
||||||
'Events go to Dashboard UI through evt:ps; commands come back through cmd:ps-mode and cmd:ps-demand.',
|
|
||||||
600, 40));
|
|
||||||
|
|
||||||
/* L0 link-ins: setup + dashboard commands. */
|
|
||||||
const linModeProc = linkIn('lin_proc_mode', TAB_PROC, 'cmd:ps-mode', LANE_X[0], 480, [], ['ps_dash_station']);
|
|
||||||
const linDemandProc = linkIn('lin_proc_demand', TAB_PROC, 'cmd:ps-demand', LANE_X[0], 540, [], ['ps_dash_station']);
|
|
||||||
const linSetupMode = linkIn('lin_proc_setupmode', TAB_PROC, 'setup:to-ps-mode', LANE_X[0], 420, [], ['ps_dash_station']);
|
|
||||||
const linSetupInflow= linkIn('lin_proc_setupinflow', TAB_PROC, 'setup:to-ps-inflow',LANE_X[0], 600, [], ['ps_dash_station']);
|
|
||||||
nodes.push(linModeProc, linDemandProc, linSetupMode, linSetupInflow);
|
|
||||||
|
|
||||||
/* L2 level sensor with simulator. */
|
|
||||||
const levelMeas = measurementLevelNode('ps_dash_meas_level', TAB_PROC, 'Basin level sensor',
|
|
||||||
LANE_X[2], 700, [[], [], ['ps_dash_station']]);
|
|
||||||
nodes.push(levelMeas);
|
|
||||||
nodes.push(inject('ps_dash_inj_level', TAB_PROC, 'sim level 1.6 m', 'measurement', '1.6', 'num',
|
|
||||||
LANE_X[0], 700, ['ps_dash_meas_level']));
|
|
||||||
|
|
||||||
/* L3 pumps. */
|
|
||||||
const pumpA = rotatingMachineNode('ps_dash_pump_a', TAB_PROC, 'Pump A', 'example-pump-a',
|
|
||||||
LANE_X[3], 320, [[], [], ['ps_dash_mgc']]);
|
|
||||||
const pumpB = rotatingMachineNode('ps_dash_pump_b', TAB_PROC, 'Pump B', 'example-pump-b',
|
|
||||||
LANE_X[3], 400, [[], [], ['ps_dash_mgc']]);
|
|
||||||
nodes.push(pumpA, pumpB);
|
|
||||||
|
|
||||||
/* L4 MGC. */
|
|
||||||
const mgc = machineGroupControlNode('ps_dash_mgc', TAB_PROC, 'Pump Group',
|
|
||||||
LANE_X[4], 360, [[], [], ['ps_dash_station']]);
|
|
||||||
nodes.push(mgc);
|
|
||||||
|
|
||||||
/* L5 pumpingStation. */
|
|
||||||
const station = pumpingStationNode('ps_dash_station', TAB_PROC, 'Pumping Station',
|
|
||||||
LANE_X[5], 520, [['ps_dash_trend_split'], [], []]);
|
|
||||||
nodes.push(station);
|
|
||||||
|
|
||||||
/* L6 trend-split fn: one output per chart + one output for the status text widgets.
|
|
||||||
* Outputs:
|
|
||||||
* 0 -> chart_flow ({topic: 'Inflow', payload: m3/h}, {topic: 'Outflow', payload: m3/h})
|
|
||||||
* 1 -> chart_level ({topic: 'Level', payload: m})
|
|
||||||
* 2 -> chart_volpct ({topic: 'Volume%', payload: %})
|
|
||||||
* 3 -> text_status (compact state string)
|
|
||||||
* 4 -> text_perc (percControl)
|
|
||||||
* 5 -> text_direction (direction)
|
|
||||||
* 6 -> text_timetoempty(timeToEmpty)
|
|
||||||
*/
|
|
||||||
const trendCode =
|
|
||||||
"const p = (msg && msg.payload && typeof msg.payload === 'object') ? msg.payload : {};\n" +
|
|
||||||
"const cache = context.get('c') || {}; Object.assign(cache, p); context.set('c', cache);\n" +
|
|
||||||
"function pick(prefix){ for (const k of Object.keys(cache)) if (k===prefix||k.indexOf(prefix+'.')===0){ const v=Number(cache[k]); if(Number.isFinite(v)) return v;} return null; }\n" +
|
|
||||||
"const flowIn = pick('flow.predicted.in');\n" +
|
|
||||||
"const flowOut = pick('flow.predicted.out');\n" +
|
|
||||||
"const level = pick('level.predicted.atequipment');\n" +
|
|
||||||
"const volPct = Number(cache.volumePercent);\n" +
|
|
||||||
"const ts = Date.now();\n" +
|
|
||||||
"const flowMsgs = [];\n" +
|
|
||||||
"if (flowIn != null) flowMsgs.push({ topic: 'Inflow', payload: flowIn * 3600, timestamp: ts });\n" +
|
|
||||||
"if (flowOut != null) flowMsgs.push({ topic: 'Outflow', payload: flowOut * 3600, timestamp: ts });\n" +
|
|
||||||
"const flowOut1 = flowMsgs.length ? flowMsgs : null;\n" +
|
|
||||||
"const levelOut = level != null ? { topic: 'Level', payload: level, timestamp: ts } : null;\n" +
|
|
||||||
"const volOut = Number.isFinite(volPct) ? { topic: 'Volume%', payload: volPct, timestamp: ts } : null;\n" +
|
|
||||||
"const stateStr = `state=${cache.state||'?'} | mode=${cache.controlMode||cache.mode||'?'}`;\n" +
|
|
||||||
"const percStr = cache.percControl != null ? Number(cache.percControl).toFixed(1) + ' %' : 'n/a';\n" +
|
|
||||||
"const dirStr = cache.direction || 'n/a';\n" +
|
|
||||||
"const tEmpty = cache.timeToEmpty != null ? Number(cache.timeToEmpty).toFixed(0) + ' s' : 'n/a';\n" +
|
|
||||||
"return [\n" +
|
|
||||||
" flowOut1,\n" +
|
|
||||||
" levelOut,\n" +
|
|
||||||
" volOut,\n" +
|
|
||||||
" { payload: stateStr },\n" +
|
|
||||||
" { payload: percStr },\n" +
|
|
||||||
" { payload: dirStr },\n" +
|
|
||||||
" { payload: tEmpty }\n" +
|
|
||||||
"];";
|
|
||||||
const trendSplit = fn('ps_dash_trend_split', TAB_PROC, 'Trend split + status', trendCode,
|
|
||||||
LANE_X[6], 520,
|
|
||||||
[
|
|
||||||
['lout_evt_flow'],
|
|
||||||
['lout_evt_level'],
|
|
||||||
['lout_evt_volpct'],
|
|
||||||
['lout_evt_state'],
|
|
||||||
['lout_evt_perc'],
|
|
||||||
['lout_evt_dir'],
|
|
||||||
['lout_evt_tempty'],
|
|
||||||
], 7);
|
|
||||||
nodes.push(trendSplit);
|
|
||||||
|
|
||||||
/* L7 link-outs into the Dashboard UI tab. */
|
|
||||||
const loutFlow = linkOut('lout_evt_flow', TAB_PROC, 'evt:flow', LANE_X[7], 420, ['lin_ui_flow']);
|
|
||||||
const loutLevel = linkOut('lout_evt_level', TAB_PROC, 'evt:level', LANE_X[7], 460, ['lin_ui_level']);
|
|
||||||
const loutVolPct = linkOut('lout_evt_volpct', TAB_PROC, 'evt:volpct', LANE_X[7], 500, ['lin_ui_volpct']);
|
|
||||||
const loutState = linkOut('lout_evt_state', TAB_PROC, 'evt:state', LANE_X[7], 540, ['lin_ui_state']);
|
|
||||||
const loutPerc = linkOut('lout_evt_perc', TAB_PROC, 'evt:perc', LANE_X[7], 580, ['lin_ui_perc']);
|
|
||||||
const loutDir = linkOut('lout_evt_dir', TAB_PROC, 'evt:dir', LANE_X[7], 620, ['lin_ui_dir']);
|
|
||||||
const loutTempty = linkOut('lout_evt_tempty', TAB_PROC, 'evt:tempty', LANE_X[7], 660, ['lin_ui_tempty']);
|
|
||||||
nodes.push(loutFlow, loutLevel, loutVolPct, loutState, loutPerc, loutDir, loutTempty);
|
|
||||||
|
|
||||||
/* Process tab groups. */
|
|
||||||
const procStationIds = ['ps_dash_station', 'ps_dash_trend_split',
|
|
||||||
'lin_proc_mode', 'lin_proc_demand', 'lin_proc_setupmode', 'lin_proc_setupinflow',
|
|
||||||
'lout_evt_flow', 'lout_evt_level', 'lout_evt_volpct', 'lout_evt_state', 'lout_evt_perc', 'lout_evt_dir', 'lout_evt_tempty'];
|
|
||||||
const procPumpAIds = ['ps_dash_pump_a'];
|
|
||||||
const procPumpBIds = ['ps_dash_pump_b'];
|
|
||||||
const procMgcIds = ['ps_dash_mgc'];
|
|
||||||
const procLevelIds = ['ps_dash_meas_level', 'ps_dash_inj_level'];
|
|
||||||
nodes.push(group('ps_dash_grp_station', TAB_PROC, 'Pumping Station (PC)', S88.PC, procStationIds, bboxOf(nodes, procStationIds, 25)));
|
|
||||||
nodes.push(group('ps_dash_grp_pa', TAB_PROC, 'Pump A (EM)', S88.EM, procPumpAIds, bboxOf(nodes, procPumpAIds, 25)));
|
|
||||||
nodes.push(group('ps_dash_grp_pb', TAB_PROC, 'Pump B (EM)', S88.EM, procPumpBIds, bboxOf(nodes, procPumpBIds, 25)));
|
|
||||||
nodes.push(group('ps_dash_grp_mgc', TAB_PROC, 'Pump Group MGC (UN)', S88.UN, procMgcIds, bboxOf(nodes, procMgcIds, 25)));
|
|
||||||
nodes.push(group('ps_dash_grp_level', TAB_PROC, 'Level Sensor (CM)', S88.CM, procLevelIds, bboxOf(nodes, procLevelIds, 25)));
|
|
||||||
|
|
||||||
/* ---------- Dashboard UI tab ---------------------------------- */
|
|
||||||
|
|
||||||
nodes.push(comment('ps_dash_ui_title', TAB_UI,
|
|
||||||
'Dashboard UI\n━━━━━━━━━━━━━━━\nLink-ins on L0 receive evt:* from Process Plant.\n' +
|
|
||||||
'Sliders on L2 emit cmd:* back to Process Plant.\n' +
|
|
||||||
'Charts use the trend-split pattern: one chart per metric, series labelled by msg.topic.',
|
|
||||||
600, 40));
|
|
||||||
|
|
||||||
/* L0 link-ins from the process side. */
|
|
||||||
nodes.push(linkIn('lin_ui_flow', TAB_UI, 'evt:flow', LANE_X[0], 220, [], ['ui_chart_flow']));
|
|
||||||
nodes.push(linkIn('lin_ui_level', TAB_UI, 'evt:level', LANE_X[0], 320, [], ['ui_chart_level']));
|
|
||||||
nodes.push(linkIn('lin_ui_volpct', TAB_UI, 'evt:volpct', LANE_X[0], 420, [], ['ui_chart_volpct']));
|
|
||||||
nodes.push(linkIn('lin_ui_state', TAB_UI, 'evt:state', LANE_X[0], 520, [], ['ui_text_state']));
|
|
||||||
nodes.push(linkIn('lin_ui_perc', TAB_UI, 'evt:perc', LANE_X[0], 560, [], ['ui_text_perc']));
|
|
||||||
nodes.push(linkIn('lin_ui_dir', TAB_UI, 'evt:dir', LANE_X[0], 600, [], ['ui_text_dir']));
|
|
||||||
nodes.push(linkIn('lin_ui_tempty', TAB_UI, 'evt:tempty', LANE_X[0], 640, [], ['ui_text_tempty']));
|
|
||||||
|
|
||||||
/* L4 charts and text widgets. */
|
|
||||||
nodes.push(uiChart('ui_chart_flow', TAB_UI, 'ps_dash_grp_trend', 'Flow trend', 'Flow (m³/h)', 1, 'm³/h', LANE_X[4], 220));
|
|
||||||
nodes.push(uiChart('ui_chart_level', TAB_UI, 'ps_dash_grp_trend', 'Level trend', 'Level (m)', 2, 'm', LANE_X[4], 320));
|
|
||||||
nodes.push(uiChart('ui_chart_volpct', TAB_UI, 'ps_dash_grp_trend', 'Volume %', 'Volume (%)', 3, '%', LANE_X[4], 420));
|
|
||||||
nodes.push(uiText( 'ui_text_state', TAB_UI, 'ps_dash_grp_status','State', 'Station state',1, LANE_X[4], 520));
|
|
||||||
nodes.push(uiText( 'ui_text_perc', TAB_UI, 'ps_dash_grp_status','percControl', 'Control %', 2, LANE_X[4], 560));
|
|
||||||
nodes.push(uiText( 'ui_text_dir', TAB_UI, 'ps_dash_grp_status','direction', 'Direction', 3, LANE_X[4], 600));
|
|
||||||
nodes.push(uiText( 'ui_text_tempty', TAB_UI, 'ps_dash_grp_status','timeToEmpty', 'Time to empty',4, LANE_X[4], 640));
|
|
||||||
|
|
||||||
/* L2 controls: dropdown for mode + slider for demand. */
|
|
||||||
const modeDropdown = uiDropdown('ui_dd_mode', TAB_UI, 'ps_dash_grp_ctrl',
|
|
||||||
'Mode', 'Control mode', 1, LANE_X[2], 160, 'set.mode',
|
|
||||||
['manual', 'levelbased', 'flowbased', 'none'], ['ui_wrap_mode']);
|
|
||||||
const demandSlider = uiSlider('ui_sl_demand', TAB_UI, 'ps_dash_grp_ctrl',
|
|
||||||
'Demand', 'Manual demand (m³/h)', 2, LANE_X[2], 220, 'set.demand', 0, 200, 5);
|
|
||||||
nodes.push(modeDropdown, demandSlider);
|
|
||||||
// Slider wires need explicit wiring (uiSlider helper leaves wires empty so we set them post-creation).
|
|
||||||
demandSlider.wires = [['ui_wrap_demand']];
|
|
||||||
|
|
||||||
/* L4 wrappers: enforce the canonical topic on the outgoing msg. */
|
|
||||||
const wrapMode = fn('ui_wrap_mode', TAB_UI, 'topic=set.mode',
|
|
||||||
"msg.topic = 'set.mode';\nmsg.payload = String(msg.payload || 'manual');\nreturn msg;",
|
|
||||||
LANE_X[4], 160, [['lout_cmd_mode']]);
|
|
||||||
const wrapDemand = fn('ui_wrap_demand', TAB_UI, 'topic=set.demand',
|
|
||||||
"msg.topic = 'set.demand';\nmsg.payload = Number(msg.payload);\nreturn Number.isFinite(msg.payload) ? msg : null;",
|
|
||||||
LANE_X[4], 220, [['lout_cmd_demand']]);
|
|
||||||
nodes.push(wrapMode, wrapDemand);
|
|
||||||
|
|
||||||
/* L7 link-outs to the process plant. */
|
|
||||||
nodes.push(linkOut('lout_cmd_mode', TAB_UI, 'cmd:ps-mode', LANE_X[7], 160, ['lin_proc_mode']));
|
|
||||||
nodes.push(linkOut('lout_cmd_demand', TAB_UI, 'cmd:ps-demand', LANE_X[7], 220, ['lin_proc_demand']));
|
|
||||||
|
|
||||||
/* UI tab groups (mirror the dashboard groups). */
|
|
||||||
const uiCtrlIds = ['ui_dd_mode', 'ui_sl_demand', 'ui_wrap_mode', 'ui_wrap_demand',
|
|
||||||
'lout_cmd_mode', 'lout_cmd_demand'];
|
|
||||||
const uiStatusIds = ['ui_text_state', 'ui_text_perc', 'ui_text_dir', 'ui_text_tempty',
|
|
||||||
'lin_ui_state', 'lin_ui_perc', 'lin_ui_dir', 'lin_ui_tempty'];
|
|
||||||
const uiTrendIds = ['ui_chart_flow', 'ui_chart_level', 'ui_chart_volpct',
|
|
||||||
'lin_ui_flow', 'lin_ui_level', 'lin_ui_volpct'];
|
|
||||||
nodes.push(group('grp_ui_ctrl', TAB_UI, 'Controls (PC)', S88.PC, uiCtrlIds, bboxOf(nodes, uiCtrlIds, 25)));
|
|
||||||
nodes.push(group('grp_ui_status', TAB_UI, 'Operator status (PC)', S88.PC, uiStatusIds, bboxOf(nodes, uiStatusIds, 25)));
|
|
||||||
nodes.push(group('grp_ui_trend', TAB_UI, 'Live trends (PC)', S88.PC, uiTrendIds, bboxOf(nodes, uiTrendIds, 25)));
|
|
||||||
|
|
||||||
/* ---------- Setup tab ----------------------------------------- */
|
|
||||||
|
|
||||||
nodes.push(comment('ps_dash_setup_title', TAB_SETUP, 'Deploy-time setup\n━━━━━━━━━━━━━━━━━━━\n' +
|
|
||||||
'Initialises set.mode = levelbased and seeds an inflow at deploy time.',
|
|
||||||
LANE_X[2], 40));
|
|
||||||
|
|
||||||
nodes.push(inject('ps_dash_setup_mode', TAB_SETUP, 'set.mode = levelbased', 'set.mode', 'levelbased', 'str',
|
|
||||||
LANE_X[0], 160, ['ps_dash_lout_setup_mode'], { once: true, onceDelay: '0.5' }));
|
|
||||||
nodes.push(inject('ps_dash_setup_inflow', TAB_SETUP, 'seed inflow 60 m3/h', 'set.inflow', '60', 'num',
|
|
||||||
LANE_X[0], 220, ['ps_dash_lout_setup_inflow'], { once: true, onceDelay: '1.0' }));
|
|
||||||
|
|
||||||
nodes.push(linkOut('ps_dash_lout_setup_mode', TAB_SETUP, 'setup:to-ps-mode', LANE_X[7], 160, ['lin_proc_setupmode']));
|
|
||||||
nodes.push(linkOut('ps_dash_lout_setup_inflow', TAB_SETUP, 'setup:to-ps-inflow', LANE_X[7], 220, ['lin_proc_setupinflow']));
|
|
||||||
|
|
||||||
const setupIds = ['ps_dash_setup_mode', 'ps_dash_setup_inflow',
|
|
||||||
'ps_dash_lout_setup_mode', 'ps_dash_lout_setup_inflow'];
|
|
||||||
nodes.push(group('ps_dash_grp_setup', TAB_SETUP, 'Deploy-time setup', S88.neutral, setupIds, bboxOf(nodes, setupIds, 25)));
|
|
||||||
|
|
||||||
return nodes;
|
|
||||||
}
|
|
||||||
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
/* README */
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
|
|
||||||
const README = `# pumpingStation - Example Flows
|
|
||||||
|
|
||||||
Three Node-RED flows demonstrating the Phase-2 pumpingStation node on the
|
|
||||||
canonical topic API (\`set.mode\`, \`set.inflow\`, \`set.demand\`,
|
|
||||||
\`cmd.calibrate.volume\`, \`cmd.calibrate.level\`). Legacy aliases
|
|
||||||
(\`changemode\`, \`q_in\`, \`Qd\`, \`calibratePredictedVolume\`,
|
|
||||||
\`calibratePredictedLevel\`, \`registerChild\`) still work but log a
|
|
||||||
one-time deprecation warning; these fresh flows use the canonical names only.
|
|
||||||
|
|
||||||
## Files
|
|
||||||
|
|
||||||
| File | Tier | Tabs | Purpose |
|
|
||||||
|---|---|---|---|
|
|
||||||
| \`01-Basic.json\` | 1 | Process Plant | Single pumpingStation driven by inject nodes - no parent, no dashboard. |
|
|
||||||
| \`02-Integration.json\` | 2 | Process Plant + Setup | Adds a \`measurement\` level child and a \`machineGroupControl\` parent with two \`rotatingMachine\` pumps. Demonstrates the Phase-2 parent/child handshake. |
|
|
||||||
| \`03-Dashboard.json\` | 3 | Process Plant + Dashboard UI + Setup | Tier 2 plumbing plus a FlowFuse Dashboard 2.0 page with 3 charts (flow / level / volume %), text widgets, and 2 controls (mode dropdown + demand slider). |
|
|
||||||
|
|
||||||
## Prerequisites
|
|
||||||
|
|
||||||
- Node-RED with the EVOLV package installed (so the \`pumpingStation\`,
|
|
||||||
\`measurement\`, \`machineGroupControl\`, and \`rotatingMachine\` node
|
|
||||||
types are registered).
|
|
||||||
- For \`03-Dashboard.json\`: \`@flowfuse/node-red-dashboard\` (Dashboard 2.0).
|
|
||||||
|
|
||||||
## How to load
|
|
||||||
|
|
||||||
\`\`\`bash
|
|
||||||
# Drop a file into a running Node-RED instance using its Admin API.
|
|
||||||
curl -X POST -H 'Content-Type: application/json' \\
|
|
||||||
--data @nodes/pumpingStation/examples/01-Basic.json \\
|
|
||||||
http://localhost:1880/flows
|
|
||||||
\`\`\`
|
|
||||||
|
|
||||||
Or in the editor: **Menu -> Import -> select file -> Import**. The flows
|
|
||||||
import into their own tabs and can be deployed immediately.
|
|
||||||
|
|
||||||
## 01-Basic - what to try
|
|
||||||
|
|
||||||
1. Deploy.
|
|
||||||
2. Inject \`set.mode = manual\`.
|
|
||||||
3. Inject \`set.inflow = 60 m3/h\` - the basin starts filling. Watch the
|
|
||||||
formatted Port 0 payload in the debug sidebar.
|
|
||||||
4. Inject \`set.demand = 40 %\` - in manual mode this would feed any
|
|
||||||
registered children; here there are no pump children so it is logged
|
|
||||||
and shown on Port 0.
|
|
||||||
5. Inject \`cmd.calibrate.volume = 25 m3\` to jump the predicted-volume
|
|
||||||
integrator to half-full.
|
|
||||||
|
|
||||||
## 02-Integration - what to try
|
|
||||||
|
|
||||||
1. Deploy. The Setup tab fires \`set.mode = levelbased\` to the station
|
|
||||||
and \`set.mode = auto\` to the MGC.
|
|
||||||
2. The two pumps register with the MGC via Port 2; the MGC and the level
|
|
||||||
sensor register with the station via Port 2. Watch the registration
|
|
||||||
debug taps to confirm.
|
|
||||||
3. The level inject pushes a 1.6 m measurement so the station sees a
|
|
||||||
non-zero starting level. Setup also seeds \`set.inflow = 60 m3/h\`.
|
|
||||||
4. The station's \`controlMode = levelbased\` then drives the MGC, which
|
|
||||||
dispatches to Pump A / Pump B.
|
|
||||||
|
|
||||||
## 03-Dashboard - what to try
|
|
||||||
|
|
||||||
1. Deploy.
|
|
||||||
2. Open the dashboard at \`http://localhost:1880/dashboard/page/pumping-station\`.
|
|
||||||
3. Use the **Control mode** dropdown to switch between \`manual\`,
|
|
||||||
\`levelbased\`, \`flowbased\`, \`none\`.
|
|
||||||
4. In manual mode, drag the **Manual demand** slider - the demand cascades
|
|
||||||
to the MGC and on to the pumps.
|
|
||||||
5. The three charts (flow, level, volume %) plot live data; the four text
|
|
||||||
widgets show state, percControl, direction, and time-to-empty.
|
|
||||||
|
|
||||||
## Layout conventions
|
|
||||||
|
|
||||||
These flows follow the EVOLV layout rule set in
|
|
||||||
\`.claude/rules/node-red-flow-layout.md\`:
|
|
||||||
|
|
||||||
- Tabs split by **concern**: Process Plant (EVOLV nodes) / Dashboard UI
|
|
||||||
(\`ui-*\` widgets) / Setup (once-true injects).
|
|
||||||
- Cross-tab wiring via **named link out / link in channels**:
|
|
||||||
\`setup:to-ps-mode\`, \`setup:to-ps-inflow\`, \`setup:to-mgc-mode\`,
|
|
||||||
\`cmd:ps-mode\`, \`cmd:ps-demand\`, \`evt:flow\`, \`evt:level\`,
|
|
||||||
\`evt:volpct\`, \`evt:state\`, \`evt:perc\`, \`evt:dir\`, \`evt:tempty\`.
|
|
||||||
- **Lane positions** L0-L7 = \`[120, 360, 600, 840, 1080, 1320, 1560, 1800]\`,
|
|
||||||
driven by each node's S88 level (Process Cell on L5, Unit on L4,
|
|
||||||
Equipment on L3, Control Module on L2).
|
|
||||||
- **Group boxes** wrap each parent + its direct children, coloured by the
|
|
||||||
parent's S88 level.
|
|
||||||
|
|
||||||
## Regenerating
|
|
||||||
|
|
||||||
These flows are generated from \`tools/build-examples.js\`. Edit the
|
|
||||||
generator, never the JSON, then:
|
|
||||||
|
|
||||||
\`\`\`bash
|
|
||||||
node nodes/pumpingStation/tools/build-examples.js
|
|
||||||
\`\`\`
|
|
||||||
|
|
||||||
The script writes \`01-Basic.json\`, \`02-Integration.json\`, and
|
|
||||||
\`03-Dashboard.json\` into this directory.
|
|
||||||
`;
|
|
||||||
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
/* Main */
|
|
||||||
/* ------------------------------------------------------------------ */
|
|
||||||
|
|
||||||
function writeFlow(filename, builder) {
|
|
||||||
const flow = builder();
|
|
||||||
const dest = path.join(OUT_DIR, filename);
|
|
||||||
fs.writeFileSync(dest, JSON.stringify(flow, null, 2) + '\n', 'utf8');
|
|
||||||
console.log(`wrote ${dest} (${flow.length} nodes)`);
|
|
||||||
}
|
|
||||||
|
|
||||||
function main() {
|
|
||||||
if (!fs.existsSync(OUT_DIR)) fs.mkdirSync(OUT_DIR, { recursive: true });
|
|
||||||
writeFlow('01-Basic.json', buildBasic);
|
|
||||||
writeFlow('02-Integration.json', buildIntegration);
|
|
||||||
writeFlow('03-Dashboard.json', buildDashboard);
|
|
||||||
fs.writeFileSync(path.join(OUT_DIR, 'README.md'), README, 'utf8');
|
|
||||||
console.log(`wrote ${path.join(OUT_DIR, 'README.md')}`);
|
|
||||||
}
|
|
||||||
|
|
||||||
main();
|
|
||||||
@@ -1,6 +1,6 @@
|
|||||||
# Reference — Contracts
|
# Reference — Contracts
|
||||||
|
|
||||||
 
|
 
|
||||||
|
|
||||||
> [!NOTE]
|
> [!NOTE]
|
||||||
> Full topic contract, configuration schema, and child-registration filters for `pumpingStation`. The topic-contract and data-model sections are **regenerated by `npm run wiki:all`** — do not hand-edit between the `BEGIN AUTOGEN` / `END AUTOGEN` markers. Source of truth for everything on this page: the node's `src/commands/index.js`, `src/specificClass.js` `configure()`, and the schema at `generalFunctions/src/configs/pumpingStation.json`.
|
> Full topic contract, configuration schema, and child-registration filters for `pumpingStation`. The topic-contract and data-model sections are **regenerated by `npm run wiki:all`** — do not hand-edit between the `BEGIN AUTOGEN` / `END AUTOGEN` markers. Source of truth for everything on this page: the node's `src/commands/index.js`, `src/specificClass.js` `configure()`, and the schema at `generalFunctions/src/configs/pumpingStation.json`.
|
||||||
@@ -11,7 +11,11 @@
|
|||||||
|
|
||||||
## Topic contract
|
## Topic contract
|
||||||
|
|
||||||
The **Unit** column reflects each descriptor's `units: { measure, default }` declaration. The default unit is what the commandRegistry coerces incoming `msg.unit` values to before the handler runs.
|
The **Unit** column reflects each descriptor's declared unit (via the `unit: 'm3/h'` shorthand or the legacy `units: { measure, default }`; the measure is derived from the unit). The default unit is what the commandRegistry coerces incoming values to before the handler runs.
|
||||||
|
|
||||||
|
**Command envelope (all EVOLV nodes).** Every command shares one envelope on top of `msg.topic`:
|
||||||
|
- **Value + unit** — send `msg.payload` as a number (with optional sibling `msg.unit`) **or** as `{ value, unit }`. The registry always converts the value to the descriptor's unit before the handler; numeric strings are converted too. A missing unit assumes the descriptor default.
|
||||||
|
- **`msg.origin`** — the control authority that issued the command: `parent` (automation/parent controller, the default), `GUI` (SCADA/HMI operator), or `fysical` (physical buttons). On nodes with a control mode, the mode's `allowedSources` decides which origins are accepted; releasing control is done by changing the mode.
|
||||||
|
|
||||||
<!-- BEGIN AUTOGEN: topic-contract -->
|
<!-- BEGIN AUTOGEN: topic-contract -->
|
||||||
|
|
||||||
@@ -27,6 +31,48 @@ The **Unit** column reflects each descriptor's `units: { measure, default }` dec
|
|||||||
|
|
||||||
<!-- END AUTOGEN: topic-contract -->
|
<!-- END AUTOGEN: topic-contract -->
|
||||||
|
|
||||||
|
### Input message examples
|
||||||
|
|
||||||
|
One worked `msg` per accepted topic. Send these into **Port 0**. For unit-bearing
|
||||||
|
topics the commandRegistry converts `msg.unit` (or a `{ value, unit }` payload) to
|
||||||
|
the default unit *before* the handler runs — so the unit is optional and any
|
||||||
|
[compatible unit](https://gitea.wbd-rd.nl/RnD/EVOLV/wiki/Topic-Conventions) is accepted.
|
||||||
|
|
||||||
|
```js
|
||||||
|
// 1. set.mode — switch control strategy
|
||||||
|
msg = { topic: 'set.mode', payload: 'manual' }; // manual | levelbased | flowbased | none
|
||||||
|
|
||||||
|
// 2. child.register — register a child (usually arrives on Port 2 from the child;
|
||||||
|
// this is the manual form). payload = the child node's Node-RED id.
|
||||||
|
msg = { topic: 'child.register', payload: 'a1b2c3d4.ef567', positionVsParent: 'upstream' };
|
||||||
|
// positionVsParent: upstream | downstream | atequipment (or in | out for predicted-flow children)
|
||||||
|
|
||||||
|
// 3. cmd.calibrate.volume — seed the predicted-volume integrator (default m³)
|
||||||
|
msg = { topic: 'cmd.calibrate.volume', payload: 12.5 }; // 12.5 m³
|
||||||
|
msg = { topic: 'cmd.calibrate.volume', payload: 12500, unit: 'L' }; // 12 500 L → auto-converted to 12.5 m³
|
||||||
|
|
||||||
|
// 4. cmd.calibrate.level — seed the predicted level (default m)
|
||||||
|
msg = { topic: 'cmd.calibrate.level', payload: 1.8 }; // 1.8 m
|
||||||
|
|
||||||
|
// 5. set.inflow — push a measured inflow (default m³/h)
|
||||||
|
msg = { topic: 'set.inflow', payload: 45 }; // 45 m³/h
|
||||||
|
msg = { topic: 'set.inflow', payload: 12.5, unit: 'L/s' }; // 12.5 L/s → 45 m³/h
|
||||||
|
msg = { topic: 'set.inflow', payload: { value: 45, unit: 'm3/h' }, timestamp: 1716998400000 };
|
||||||
|
|
||||||
|
// 6. set.outflow — push a measured/forced outflow (default m³/h)
|
||||||
|
msg = { topic: 'set.outflow', payload: 30 }; // 30 m³/h drawn from the basin
|
||||||
|
|
||||||
|
// 7. set.demand — operator outflow setpoint (default m³/h); ignored unless mode === 'manual'
|
||||||
|
msg = { topic: 'set.demand', payload: 120 }; // 120 m³/h
|
||||||
|
|
||||||
|
// Built-in (every EVOLV node): query.units — ask which units each topic accepts.
|
||||||
|
// Replies on Port 0 with { topic:'query.units', payload:{ node, units } }.
|
||||||
|
msg = { topic: 'query.units', payload: null };
|
||||||
|
```
|
||||||
|
|
||||||
|
> Deprecated aliases behave identically and log a one-time warning, e.g.
|
||||||
|
> `{ topic: 'q_in', payload: 45 }` ≡ `set.inflow`, `{ topic: 'Qd', payload: 120 }` ≡ `set.demand`.
|
||||||
|
|
||||||
---
|
---
|
||||||
|
|
||||||
## Data model — `getOutput()` shape
|
## Data model — `getOutput()` shape
|
||||||
@@ -39,35 +85,88 @@ Keys composed each tick by `specificClass.getOutput()` and emitted via `outputUt
|
|||||||
|---|---|---|---|
|
|---|---|---|---|
|
||||||
| `direction` | string | — | `"steady"` |
|
| `direction` | string | — | `"steady"` |
|
||||||
| `dryRunLevel` | number | — | `0.20400000000000001` |
|
| `dryRunLevel` | number | — | `0.20400000000000001` |
|
||||||
| `dryRunSafetyVol` | number | — | `0.20400000000000001` |
|
| `dryRunSafetyVol` | number | — | `2.55` |
|
||||||
| `flowSource` | null | — | `null` |
|
| `flowSource` | null | — | `null` |
|
||||||
| `heightBasin` | number | m | `1` |
|
| `heightBasin` | number | m | `4` |
|
||||||
| `highVolumeSafetyLevel` | number | — | `2.45` |
|
| `highVolumeSafetyLevel` | number | — | `3.7239999999999998` |
|
||||||
| `highVolumeSafetyVol` | number | — | `2.45` |
|
| `highVolumeSafetyVol` | number | — | `46.55` |
|
||||||
| `inflowLevel` | number | m | `2` |
|
| `inflowLevel` | number | m | `1.5` |
|
||||||
| `inletPipeDiameter` | number | — | `0.4` |
|
| `inletPipeDiameter` | number | — | `0.4` |
|
||||||
| `maxVol` | number | m3 | `1` |
|
| `manualDemand` | null | — | `null` |
|
||||||
| `maxVolAtOverflow` | number | m3 | `2.5` |
|
| `maxVol` | number | m3 | `50` |
|
||||||
|
| `maxVolAtOverflow` | number | m3 | `47.5` |
|
||||||
| `minHeightBasedOn` | string | — | `"outlet"` |
|
| `minHeightBasedOn` | string | — | `"outlet"` |
|
||||||
| `minVol` | number | m3 | `0.2` |
|
| `minVol` | number | m3 | `2.5` |
|
||||||
| `minVolAtInflow` | number | m3 | `2` |
|
| `minVolAtInflow` | number | m3 | `18.75` |
|
||||||
| `minVolAtOutflow` | number | m3 | `0.2` |
|
| `minVolAtOutflow` | number | m3 | `2.5` |
|
||||||
|
| `mode` | string | — | `"levelbased"` |
|
||||||
| `outflowLevel` | number | m | `0.2` |
|
| `outflowLevel` | number | m | `0.2` |
|
||||||
| `outletPipeDiameter` | number | — | `0.4` |
|
| `outletPipeDiameter` | number | — | `0.4` |
|
||||||
| `overflowLevel` | number | m | `2.5` |
|
| `overflowLevel` | number | m | `3.8` |
|
||||||
| `percControl` | number | % | `0` |
|
| `percControl` | number | % | `0` |
|
||||||
| `predictedOverflowRate` | number | — | `0` |
|
| `predictedOverflowRate` | number | — | `0` |
|
||||||
| `predictedOverflowVolume` | number | — | `0` |
|
| `predictedOverflowVolume` | number | — | `0` |
|
||||||
| `predictedUnderflowVolume` | number | — | `0` |
|
| `predictedUnderflowVolume` | number | — | `0` |
|
||||||
| `surfaceArea` | number | m2 | `1` |
|
| `surfaceArea` | number | m2 | `12.5` |
|
||||||
| `timeleft` | null | s | `null` |
|
| `timeleft` | null | s | `null` |
|
||||||
| `volEmptyBasin` | number | m3 | `1` |
|
| `volEmptyBasin` | number | m3 | `50` |
|
||||||
| `volume.predicted.atequipment.wikigen-pumpingstation-id` | number | m3 | `0.2` |
|
| `volume.predicted.atequipment.wikigen-pumpingstation-id` | number | m3 | `2.5` |
|
||||||
|
|
||||||
<!-- END AUTOGEN: data-model -->
|
<!-- END AUTOGEN: data-model -->
|
||||||
|
|
||||||
Sample values come from a stub instantiation in `wikiGen` — in a live deployment the volume key is shaped `volume.<variant>.<position>.<childId>` per the standard [Measurement Key Shape](https://gitea.wbd-rd.nl/RnD/EVOLV/wiki/Topic-Conventions#measurement-key-shape).
|
Sample values come from a stub instantiation in `wikiGen` — in a live deployment the volume key is shaped `volume.<variant>.<position>.<childId>` per the standard [Measurement Key Shape](https://gitea.wbd-rd.nl/RnD/EVOLV/wiki/Topic-Conventions#measurement-key-shape).
|
||||||
|
|
||||||
|
> [!NOTE]
|
||||||
|
> Two control-state keys carry the live operating mode rather than a measurement:
|
||||||
|
> - `mode` — string, the active control strategy (`levelbased` / `manual` / `flowbased` / `none`). Echoes the most recent `set.mode` input.
|
||||||
|
> - `manualDemand` — number (m³/h) or `null`. The operator outflow setpoint last accepted via `set.demand`; `null` outside `manual` mode.
|
||||||
|
|
||||||
|
### Output message examples
|
||||||
|
|
||||||
|
The node emits on three ports every tick (`outputUtils.formatMsg`). Port 0 / Port 1
|
||||||
|
fire only when at least one field changed (delta-compression); Port 2 fires once at
|
||||||
|
startup. `topic` is the station's configured name (here `"PS-Influent-01"`).
|
||||||
|
|
||||||
|
```js
|
||||||
|
// Port 0 — process data. payload = only the keys that changed this tick.
|
||||||
|
msg = {
|
||||||
|
topic: 'PS-Influent-01',
|
||||||
|
payload: {
|
||||||
|
mode: 'levelbased',
|
||||||
|
direction: 'filling',
|
||||||
|
percControl: 25,
|
||||||
|
'level.predicted.atequipment.default': 3.25, // m
|
||||||
|
'volume.predicted.atequipment.default': 32.5, // m³
|
||||||
|
timeleft: 400, // s, or null when steady
|
||||||
|
manualDemand: null // m³/h, or null outside manual mode
|
||||||
|
}
|
||||||
|
};
|
||||||
|
|
||||||
|
// Port 1 — InfluxDB telemetry. Same changed fields, wrapped for the InfluxDB node.
|
||||||
|
msg = {
|
||||||
|
topic: 'PS-Influent-01',
|
||||||
|
payload: {
|
||||||
|
measurement: 'PS-Influent-01',
|
||||||
|
fields: { percControl: 25, 'volume.predicted.atequipment.default': 32.5 },
|
||||||
|
tags: { id: 'a1b2c3d4.ef567', softwareType: 'pumpingstation', type: 'pumpingStation' },
|
||||||
|
timestamp: '2026-05-29T10:00:00.000Z' // Date
|
||||||
|
}
|
||||||
|
};
|
||||||
|
|
||||||
|
// Port 2 — registration handshake, sent once at startup to the upstream parent.
|
||||||
|
msg = {
|
||||||
|
topic: 'child.register',
|
||||||
|
payload: 'a1b2c3d4.ef567', // this node's id
|
||||||
|
positionVsParent: 'atEquipment',
|
||||||
|
distance: null
|
||||||
|
};
|
||||||
|
```
|
||||||
|
|
||||||
|
> **Child-facing events** are not Port messages — they fire on
|
||||||
|
> `source.measurements.emitter` as `<type>.<variant>.<position>`, e.g. event
|
||||||
|
> `volume.predicted.atequipment` with payload `{ value: 32.5, unit: 'm3', timestamp }`.
|
||||||
|
> Parents subscribe by event name.
|
||||||
|
|
||||||
---
|
---
|
||||||
|
|
||||||
## Configuration schema — editor form to config keys
|
## Configuration schema — editor form to config keys
|
||||||
|
|||||||
Reference in New Issue