stopLevel Schmitt-trigger hysteresis + dead-zone keep-alive

Levelbased control now distinguishes startLevel (rising-edge engage,
ramp foot) from stopLevel (falling-edge disengage). _stopHystRunning
flag flips TRUE crossing startLevel up, FALSE crossing stopLevel down.
While engaged AND level inside [stopLevel, startLevel] (basin draining
through the dead band), emit a configurable keep-alive percControl
(default 1 %) so MGC keeps a single pump running for a full drain
stroke instead of oscillating at startLevel.

Hard turn-off the moment level <= stopLevel — independent of ramp
scaling. Manual-mode demand=0 now also issues explicit turnOff to
keep parity with the new MGC handleInput semantics where demand<=0
means "off".

Editor preview shades the new hysteresis band; admin endpoint
exposes runtime engaged state.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
Rene De Ren
2026-05-08 11:20:36 +02:00
parent 6ab585bcc2
commit e2ebb31816
5 changed files with 110 additions and 7 deletions