fix: deduplicate predicted-flow child registration + single event subscription
Three bugs in registerChild caused multi-counted outflow in _updatePredictedVolume: 1. machinegroup registered twice (line 66 + line 70 both called _registerPredictedFlowChild). Fixed: only register in the machinegroup branch. 2. Individual machines registered alongside their machinegroup parent. Each pump's predicted flow is already included in MGC's aggregated total — subscribing to both triple-counts. Fixed: only register individual machines when no machinegroup is present (direct-wired pumps without MGC). 3. _registerPredictedFlowChild subscribed to BOTH flow.predicted.downstream AND flow.predicted.atequipment events. These carry the same total flow on two event names — the handler wrote the value twice per tick. Fixed: subscribe to ONE event per child (downstream for outflow, upstream for inflow). These are generalizable patterns: - When a group aggregator exists, subscribe to IT, not its children. - One event per measurement type per child — pick the most specific. Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -63,10 +63,21 @@ class PumpingStation {
|
|||||||
this.stations[child.config.general.id] = child;
|
this.stations[child.config.general.id] = child;
|
||||||
} else if (softwareType === 'machinegroup') {
|
} else if (softwareType === 'machinegroup') {
|
||||||
this.machineGroups[child.config.general.id] = child;
|
this.machineGroups[child.config.general.id] = child;
|
||||||
this._registerPredictedFlowChild(child);
|
|
||||||
}
|
}
|
||||||
|
|
||||||
if (softwareType === 'machine' || softwareType === 'pumpingstation' || softwareType === 'machinegroup') {
|
// Register predicted-flow subscription. Only register the HIGHEST-
|
||||||
|
// level aggregator: if a machinegroup is present, subscribe to IT
|
||||||
|
// (its flow.predicted already aggregates all child machines). Do NOT
|
||||||
|
// also subscribe to individual machines — that would double-count
|
||||||
|
// because each pump's flow is included in the group total.
|
||||||
|
//
|
||||||
|
// Individual machines (softwareType='machine') are only subscribed
|
||||||
|
// when there is NO machinegroup parent — i.e., pumps wired directly
|
||||||
|
// to the pumping station without an MGC in between.
|
||||||
|
if (softwareType === 'machinegroup' || softwareType === 'pumpingstation') {
|
||||||
|
this._registerPredictedFlowChild(child);
|
||||||
|
} else if (softwareType === 'machine' && Object.keys(this.machineGroups).length === 0) {
|
||||||
|
// Direct-child machine, no group above it — register its flow.
|
||||||
this._registerPredictedFlowChild(child);
|
this._registerPredictedFlowChild(child);
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
@@ -97,18 +108,21 @@ class PumpingStation {
|
|||||||
const childId = child.config.general.id ?? childName;
|
const childId = child.config.general.id ?? childName;
|
||||||
|
|
||||||
let posKey;
|
let posKey;
|
||||||
let eventNames;
|
let eventName;
|
||||||
switch (position) {
|
switch (position) {
|
||||||
case 'downstream':
|
case 'downstream':
|
||||||
case 'out':
|
case 'out':
|
||||||
case 'atequipment':
|
case 'atequipment':
|
||||||
posKey = 'out';
|
posKey = 'out';
|
||||||
eventNames = ['flow.predicted.downstream', 'flow.predicted.atequipment'];
|
// Subscribe to ONE event only. 'downstream' is the most specific
|
||||||
|
// — avoids double-counting from 'atequipment' which carries the
|
||||||
|
// same total flow on a different event name.
|
||||||
|
eventName = 'flow.predicted.downstream';
|
||||||
break;
|
break;
|
||||||
case 'upstream':
|
case 'upstream':
|
||||||
case 'in':
|
case 'in':
|
||||||
posKey = 'in';
|
posKey = 'in';
|
||||||
eventNames = ['flow.predicted.upstream', 'flow.predicted.atequipment'];
|
eventName = 'flow.predicted.upstream';
|
||||||
break;
|
break;
|
||||||
default:
|
default:
|
||||||
this.logger.warn(`Unsupported predicted flow position "${position}" from ${childName}`);
|
this.logger.warn(`Unsupported predicted flow position "${position}" from ${childName}`);
|
||||||
@@ -132,7 +146,7 @@ class PumpingStation {
|
|||||||
.value(eventData.value, ts, unit);
|
.value(eventData.value, ts, unit);
|
||||||
};
|
};
|
||||||
|
|
||||||
eventNames.forEach((ev) => child.measurements.emitter.on(ev, handler));
|
child.measurements.emitter.on(eventName, handler);
|
||||||
}
|
}
|
||||||
|
|
||||||
/* --------------------------- Calibration --------------------------- */
|
/* --------------------------- Calibration --------------------------- */
|
||||||
|
|||||||
Reference in New Issue