fix(safety): overfill must keep pumps running, not shut them down
Two hard rules for the safety controller, matching sewer PS design: 1. BELOW stopLevel (dry-run): pumps CANNOT start. All downstream equipment shut down. safetyControllerActive=true blocks _controlLogic so level control can't restart pumps. Only manual override or emergency can change this. 2. ABOVE overflow level (overfill): pumps CANNOT stop. Only UPSTREAM equipment is shut down (stop more water coming in). Machine groups (downstream pumps) are NOT shut down — they must keep draining. safetyControllerActive is NOT set, so _controlLogic continues commanding pumps at the demand dictated by the level curve (which is >100% near overflow = all pumps at maximum). Only manual override or emergency stop can shut pumps during an overfill event. Previously the overfill branch called turnOffAllMachines() on machine groups AND set safetyControllerActive=true, which shut down the pumps and blocked level control from restarting them — exactly backwards for a sewer pumping station where the sewage keeps coming. Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -558,6 +558,24 @@ class PumpingStation {
|
|||||||
|
|
||||||
/* --------------------------- Safety --------------------------- */
|
/* --------------------------- Safety --------------------------- */
|
||||||
|
|
||||||
|
/**
|
||||||
|
* Safety controller — two hard rules:
|
||||||
|
*
|
||||||
|
* 1. BELOW stopLevel (dry-run): pumps CANNOT start.
|
||||||
|
* Shuts down all downstream machines + machine groups.
|
||||||
|
* Only a manual override or emergency can restart them.
|
||||||
|
* safetyControllerActive = true → blocks _controlLogic.
|
||||||
|
*
|
||||||
|
* 2. ABOVE overflow level (overfill): pumps CANNOT stop.
|
||||||
|
* Shuts down UPSTREAM equipment only (stop more water coming in).
|
||||||
|
* Does NOT shut down downstream pumps or machine groups — they
|
||||||
|
* must keep draining. Does NOT set safetyControllerActive — the
|
||||||
|
* level-based control keeps running so pumps stay at the demand
|
||||||
|
* dictated by the current level (which will be >100% near overflow,
|
||||||
|
* meaning all pumps at maximum via the normal demand curve).
|
||||||
|
* Only a manual override or emergency stop can shut pumps during
|
||||||
|
* an overfill event.
|
||||||
|
*/
|
||||||
_safetyController(remainingTime, direction) {
|
_safetyController(remainingTime, direction) {
|
||||||
this.safetyControllerActive = false;
|
this.safetyControllerActive = false;
|
||||||
|
|
||||||
@@ -584,10 +602,12 @@ class PumpingStation {
|
|||||||
const triggerHighVol = this.basin.maxVolOverflow * ((Number(overfillThresholdPercent) || 0) / 100);
|
const triggerHighVol = this.basin.maxVolOverflow * ((Number(overfillThresholdPercent) || 0) / 100);
|
||||||
const triggerLowVol = this.basin.minVol * (1 + ((Number(dryRunThresholdPercent) || 0) / 100));
|
const triggerLowVol = this.basin.minVol * (1 + ((Number(dryRunThresholdPercent) || 0) / 100));
|
||||||
|
|
||||||
|
// Rule 1: DRY-RUN — below stopLevel, pumps cannot run.
|
||||||
if (direction === 'draining') {
|
if (direction === 'draining') {
|
||||||
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
||||||
const dryRunTriggered = dryRunEnabled && vol < triggerLowVol;
|
const dryRunTriggered = dryRunEnabled && vol < triggerLowVol;
|
||||||
if (timeTriggered || dryRunTriggered) {
|
if (timeTriggered || dryRunTriggered) {
|
||||||
|
// Shut down all downstream equipment — pumps must stop.
|
||||||
Object.values(this.machines).forEach((machine) => {
|
Object.values(this.machines).forEach((machine) => {
|
||||||
const pos = machine?.config?.functionality?.positionVsParent;
|
const pos = machine?.config?.functionality?.positionVsParent;
|
||||||
if ((pos === 'downstream' || pos === 'atequipment') && machine._isOperationalState()) {
|
if ((pos === 'downstream' || pos === 'atequipment') && machine._isOperationalState()) {
|
||||||
@@ -597,28 +617,38 @@ class PumpingStation {
|
|||||||
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
||||||
Object.values(this.machineGroups).forEach((group) => group.turnOffAllMachines());
|
Object.values(this.machineGroups).forEach((group) => group.turnOffAllMachines());
|
||||||
this.logger.warn(
|
this.logger.warn(
|
||||||
`Safe guard triggered: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down downstream equipment`
|
`Dry-run safety: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down downstream equipment`
|
||||||
);
|
);
|
||||||
|
// Block _controlLogic so level-based control can't restart pumps.
|
||||||
this.safetyControllerActive = true;
|
this.safetyControllerActive = true;
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|
||||||
|
// Rule 2: OVERFILL — above overflow level, pumps cannot stop.
|
||||||
|
// Only shut down UPSTREAM equipment. Downstream pumps + machine
|
||||||
|
// groups keep running at whatever the level control demands
|
||||||
|
// (which will be >100% near overflow = all pumps at max).
|
||||||
|
// Do NOT set safetyControllerActive — _controlLogic must keep
|
||||||
|
// running to maintain pump demand.
|
||||||
if (direction === 'filling') {
|
if (direction === 'filling') {
|
||||||
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
const timeTriggered = timeProtectionEnabled && remainingTime != null && remainingTime < timeleftToFullOrEmptyThresholdSeconds;
|
||||||
const overfillTriggered = overfillEnabled && vol > triggerHighVol;
|
const overfillTriggered = overfillEnabled && vol > triggerHighVol;
|
||||||
if (timeTriggered || overfillTriggered) {
|
if (timeTriggered || overfillTriggered) {
|
||||||
|
// Shut down UPSTREAM only — stop more water coming in.
|
||||||
Object.values(this.machines).forEach((machine) => {
|
Object.values(this.machines).forEach((machine) => {
|
||||||
const pos = machine?.config?.functionality?.positionVsParent;
|
const pos = machine?.config?.functionality?.positionVsParent;
|
||||||
if (pos === 'upstream' && machine._isOperationalState()) {
|
if (pos === 'upstream' && machine._isOperationalState()) {
|
||||||
machine.handleInput('parent', 'execSequence', 'shutdown');
|
machine.handleInput('parent', 'execSequence', 'shutdown');
|
||||||
}
|
}
|
||||||
});
|
});
|
||||||
Object.values(this.machineGroups).forEach((group) => group.turnOffAllMachines());
|
|
||||||
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
Object.values(this.stations).forEach((station) => station.handleInput('parent', 'execSequence', 'shutdown'));
|
||||||
|
// NOTE: machine groups (downstream pumps) are NOT shut down.
|
||||||
|
// They must keep draining to prevent overflow from worsening.
|
||||||
this.logger.warn(
|
this.logger.warn(
|
||||||
`Safe guard triggered: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down upstream equipment`
|
`Overfill safety: vol=${vol.toFixed(2)} m3, remainingTime=${remainingTime ? remainingTime.toFixed(1) : 'N/A'} s; shutting down upstream equipment only — pumps keep running`
|
||||||
);
|
);
|
||||||
this.safetyControllerActive = true;
|
// NOTE: safetyControllerActive is NOT set — level control
|
||||||
|
// keeps commanding pumps at maximum demand.
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
}
|
}
|
||||||
|
|||||||