znetsixe 472402c62d feat(mgc): rendezvous planner — same-time landing across all modes
Routes every dispatch through a tick-aware planner so all pumps reach
their setpoint at the same wall-clock instant t* = max(eta_i),
regardless of control strategy or per-pump reaction speed.

Architecture (src/movement/):
- machineProfile.js   – pure snapshot of a registered child (state,
                        position, velocityPctPerS, ladder timings,
                        flowAt / positionForFlow). Reads timings from
                        child.state.config.time (the actual storage
                        location — previous fallback paths silently
                        produced 0 s, collapsing every eta to ramp-only).
- moveTrajectory.js   – seconds-to-target per machine; handles
                        idle / starting / warmingup / operational / cooling.
- movementScheduler.js – t* = max eta over ALL non-noop moves. Every
                        command is delayed so its move finishes at t*.
                        Startup execsequence fires at 0; its flowmovement
                        is gated by max(ladderS, t* − rampS) so a fast
                        pump waits before ramping rather than landing
                        early. useRendezvous=false collapses to all
                        fireAtTickN=0 (legacy fire-and-forget).
- movementExecutor.js – wall-clock virtual cursor: each tick fires
                        every command whose fireAtTickN ≤ floor(elapsed/tickS).
                        tick() no longer awaits pending fireCommand
                        promises — the synchronous prologue of
                        handleInput claims the latest-wins gate, which
                        is what race-favouring relies on.

Shared dispatch path (src/specificClass.js):
- _dispatchFlowDistribution(distribution) — extracted from
  _optimalControl. Builds profiles, calls movementScheduler.plan,
  replans the executor, ticks once. Reads
  config.planner.useRendezvous (default true).
- _optimalControl computes its bestCombination and hands off.
- equalFlowControl (priorityControl mode) computes its
  flowDistribution and hands off via ctx.mgc._dispatchFlowDistribution.
  Same-time landing now applies in BOTH modes.

Editor toggle (mgc.html + src/nodeClass.js):
- New "Same-time landing" checkbox under Control Strategy.
- nodeClass.buildDomainConfig bridges uiConfig.useRendezvous →
  config.planner.useRendezvous. Default ON.

Tests:
- New: planner-convergence.integration.test.js (real-time end-to-end
  diagnostic — drives a 3-pump mixed-state dispatch and asserts both
  convergence to the demand setpoint AND same-time landing within
  one tick).
- New: planner-rendezvous.integration.test.js (schedule-shape
  assertions against real pump objects).
- New: movementScheduler.basic.test.js — includes a mixed-speed
  multi-startup case proving the fast pumps wait so all three land
  together (the regression that prompted this work).
- New: movementExecutor.basic.test.js + moveTrajectory.basic.test.js.
- Updated executor contract test: tick() must NOT await pending fires.

Commands + wiki:
- handlers.js: source/mode allow-list gate moved into a shared _gate()
  helper; every command now checks isValidActionForMode +
  isValidSourceForMode before dispatching. Status-level commands
  (set.mode, set.scaling) are allowed in every mode.
- commands.basic.test.js: coverage for the new gate behaviour.
- wiki regen: Home.md visual-first rewrite + Reference-{Architecture,
  Contracts,Examples,Limitations}.md split with _Sidebar.md index.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-05-17 19:43:55 +02:00

129 lines
7.6 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Reference &mdash; Limitations
![code-ref](https://img.shields.io/badge/code--ref-26e92b5-blue)
> [!NOTE]
> What `machineGroupControl` does not do, current rough edges, and open questions. The planner-decline question is tracked as Gitea issue `RnD/machineGroupControl#1`; other open items live in `.agents/improvements/IMPROVEMENTS_BACKLOG.md` in the superproject.
---
## When you would not use this node
| Scenario | Use instead |
|:---|:---|
| A single pump | Wire `rotatingMachine` directly under your parent. MGC's combinatorics + totals add no value below N=2. |
| Valves (no curve, no FSM-driven motor) | `valveGroupControl`. MGC's optimizer assumes a flow-vs-pressure characteristic. |
| Pumps behind independent headers | Multiple MGCs (one per header), each parented to its own logical aggregator. The equaliser assumes a shared discharge / suction pressure. |
| Curve-less assets | Without a curve, `optimalControl` excludes the machine from every combination; the dispatch loop falls into the empty-set branch and warns each tick. |
| Mixed compressor + pump groups | The optimizer is curve-agnostic in principle, but the η = (Q·ΔP)/P_shaft identity used in `_optimalControl` assumes an incompressible-flow head. Use separate MGCs per phase. |
---
## Known limitations
### `maintenance` mode is in the schema but not in the dispatch switch
`config.mode.current` accepts `maintenance` as a valid value (per the schema enum), but `_runDispatch`'s mode switch only handles `optimalcontrol` and `prioritycontrol`. Picking `maintenance` will log `'maintenance' is not a valid mode.` on every demand. Treated as schema-vs-code drift, not a runtime bug.
### `priorityControl` bypasses the movement planner
`equalFlowControl` (the priority-mode strategy) still uses the legacy direct-dispatch path:
```js
await Promise.all(flowDistribution.map(async ({ machineId, flow }) => {
if (flow > 0) {
await machine.handleInput('parent', 'flowmovement', ...);
if (currentState === 'idle') await machine.handleInput('parent', 'execsequence', 'startup');
} else { ... shutdown ... }
}));
```
The planner is only wired through `optimalControl`. Consequence: priority-mode transitions can show a flow dip while one pump warms up and another keeps spinning. Tracked for a future pass; the planner's API is mode-agnostic so the surgery is straightforward when priorities allow.
### `mgc.scaling` is undefined
The orchestrator no longer carries a `scaling` field &mdash; `set.demand` is unit-self-describing per message. The `io/output.js` formatter still references `mgc.scaling`, which always reads `undefined`. The status-badge cosmetically displays `norm`. This is a leftover artifact of the pre-refactor design; harmless, scheduled for removal.
### Group efficiency naming &mdash; `maxEfficiency` is the **mean**, not the peak
`GroupEfficiency.calcGroupEfficiency` returns `{ maxEfficiency, lowestEfficiency }`. `maxEfficiency` is the **mean cog** across all machines, not the maximum. The name is preserved for behavioural parity with the pre-refactor code; callers using it as "the peak" will over-estimate the BEP target. Tracked &mdash; rename is a follow-up.
### `calcAbsoluteTotals` implicit pressure coupling
`TotalsCalculator.calcAbsoluteTotals` iterates a machine's `predictFlow.inputCurve` and re-indexes the SAME pressure key into `predictPower.inputCurve`. If the two curves were sampled at different pressures the lookup is `undefined` and the call throws. Mitigation deferred to the rotatingMachine curveLoader pass (P5).
### Power-cap parameter has no canonical topic
`handleInput(source, demand, powerCap)` accepts a `powerCap` argument and threads it to `validPumpCombinations`, but there is no `set.power-cap` topic in `commands/index.js`. Only programmatic callers can set it. Tracked.
### Per-pump fan-out not on Port 0
MGC's Port 0 carries the group aggregate only (`atEquipment_predicted_flow`, `headerDiffPa`, etc.). If you want per-pump trends on a dashboard you must wire each `rotatingMachine`'s Port 0 separately. By design &mdash; the alternative would put N × M fields on the MGC payload.
### Curve-less members silently drop out
`combinatorics/pumpCombinations.validPumpCombinations` filters by FSM state and mode but not by curve presence. A machine with `predictFlow === null` (because its curve loader failed at startup) has `currentFxyYMin / Max = 0`, so its contribution to subset envelopes is zero. It can still appear in subsets &mdash; the optimizer just gives it zero flow. The drop-out is silent; the only signal is the curve-loader's error log at startup.
---
## Open questions (tracked)
| Question | Where it lives |
|:---|:---|
| Should the planner ever decline a combination when the slowest startup exceeds an SLA on demand spikes? | [machineGroupControl#1](https://gitea.wbd-rd.nl/RnD/machineGroupControl/issues/1) |
| Wire the movement planner through `priorityControl` | Internal &mdash; not yet ticketed |
| Remove the `mgc.scaling` artifact + the `scaling` badge field | Internal |
| Rename `maxEfficiency``meanGroupCog` in `GroupEfficiency` | Internal |
| Decline-and-fall-back vs always-commit on planner level | Same as the Gitea issue above |
---
## Migration notes
### From pre-planner
The MGC's `_optimalControl` used to fan commands out inline (lines 226&ndash;239 in `26e92b5^`):
```js
await Promise.all(Object.entries(this.machines).map(async ([id, machine]) => {
if (flow > 0) {
await machine.handleInput('parent', 'flowmovement', ...);
if (state === 'idle') await machine.handleInput('parent', 'execsequence', 'startup');
} else if (ACTIVE_STATES.has(state)) {
await machine.handleInput('parent', 'execsequence', 'shutdown');
}
}));
```
That code is gone. The new path: build profiles &rarr; `scheduler.plan` &rarr; `executor.replan` &rarr; `await executor.tick()` (synchronous first tick) &rarr; `setInterval(1000)` for the rest. The flow / power numbers and the optimizer's pick are unchanged; only the **timing** of the per-pump commands changed.
If your test fixture relied on commands firing inline during `_runDispatch`, the new behaviour fires `fireAtTickN=0` commands synchronously inside the first `await executor.tick()` and later ones on the wall-clock interval. Tests that asserted exact timing should use the `executor.schedule()` introspection getter.
### From pre-unit-self-describing demand
The old `set.scaling` topic and its persistent `scaling.current` config field have been removed. Each `set.demand` now carries its own unit context:
| Pre | Post |
|:---|:---|
| `set.scaling = "absolute"`; `set.demand = 80` | `set.demand = {value: 80, unit: "m3/h"}` |
| `set.scaling = "normalized"`; `set.demand = 50` | `set.demand = 50` (bare number = %) |
| `set.scaling = "absolute"`; `set.demand = 0.022` (m³/s) | `set.demand = {value: 0.022, unit: "m3/s"}` |
Old flows that still send `set.scaling` will silently ignore it; the topic is no longer registered.
### From `prioritypercentagecontrol`
The mode `prioritypercentagecontrol` was retired with the unit-self-describing refactor. Use `priorityControl` with absolute-unit `set.demand` payloads, or `optimalControl` with the same.
---
## Related pages
| Page | Why |
|:---|:---|
| [Home](Home) | Intuitive overview |
| [Reference &mdash; Contracts](Reference-Contracts) | Topic + config + child filters |
| [Reference &mdash; Architecture](Reference-Architecture) | Code map, dispatch lifecycle, planner internals |
| [Reference &mdash; Examples](Reference-Examples) | Shipped flows + debug recipes |
| [rotatingMachine &mdash; Limitations](https://gitea.wbd-rd.nl/RnD/rotatingMachine/wiki/Reference-Limitations) | The child's own limitations (drift, multi-parent, virtual-child stale data) |