Routes every dispatch through a tick-aware planner so all pumps reach
their setpoint at the same wall-clock instant t* = max(eta_i),
regardless of control strategy or per-pump reaction speed.
Architecture (src/movement/):
- machineProfile.js – pure snapshot of a registered child (state,
position, velocityPctPerS, ladder timings,
flowAt / positionForFlow). Reads timings from
child.state.config.time (the actual storage
location — previous fallback paths silently
produced 0 s, collapsing every eta to ramp-only).
- moveTrajectory.js – seconds-to-target per machine; handles
idle / starting / warmingup / operational / cooling.
- movementScheduler.js – t* = max eta over ALL non-noop moves. Every
command is delayed so its move finishes at t*.
Startup execsequence fires at 0; its flowmovement
is gated by max(ladderS, t* − rampS) so a fast
pump waits before ramping rather than landing
early. useRendezvous=false collapses to all
fireAtTickN=0 (legacy fire-and-forget).
- movementExecutor.js – wall-clock virtual cursor: each tick fires
every command whose fireAtTickN ≤ floor(elapsed/tickS).
tick() no longer awaits pending fireCommand
promises — the synchronous prologue of
handleInput claims the latest-wins gate, which
is what race-favouring relies on.
Shared dispatch path (src/specificClass.js):
- _dispatchFlowDistribution(distribution) — extracted from
_optimalControl. Builds profiles, calls movementScheduler.plan,
replans the executor, ticks once. Reads
config.planner.useRendezvous (default true).
- _optimalControl computes its bestCombination and hands off.
- equalFlowControl (priorityControl mode) computes its
flowDistribution and hands off via ctx.mgc._dispatchFlowDistribution.
Same-time landing now applies in BOTH modes.
Editor toggle (mgc.html + src/nodeClass.js):
- New "Same-time landing" checkbox under Control Strategy.
- nodeClass.buildDomainConfig bridges uiConfig.useRendezvous →
config.planner.useRendezvous. Default ON.
Tests:
- New: planner-convergence.integration.test.js (real-time end-to-end
diagnostic — drives a 3-pump mixed-state dispatch and asserts both
convergence to the demand setpoint AND same-time landing within
one tick).
- New: planner-rendezvous.integration.test.js (schedule-shape
assertions against real pump objects).
- New: movementScheduler.basic.test.js — includes a mixed-speed
multi-startup case proving the fast pumps wait so all three land
together (the regression that prompted this work).
- New: movementExecutor.basic.test.js + moveTrajectory.basic.test.js.
- Updated executor contract test: tick() must NOT await pending fires.
Commands + wiki:
- handlers.js: source/mode allow-list gate moved into a shared _gate()
helper; every command now checks isValidActionForMode +
isValidSourceForMode before dispatching. Status-level commands
(set.mode, set.scaling) are allowed in every mode.
- commands.basic.test.js: coverage for the new gate behaviour.
- wiki regen: Home.md visual-first rewrite + Reference-{Architecture,
Contracts,Examples,Limitations}.md split with _Sidebar.md index.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
129 lines
7.6 KiB
Markdown
129 lines
7.6 KiB
Markdown
# Reference — Limitations
|
||
|
||

|
||
|
||
> [!NOTE]
|
||
> What `machineGroupControl` does not do, current rough edges, and open questions. The planner-decline question is tracked as Gitea issue `RnD/machineGroupControl#1`; other open items live in `.agents/improvements/IMPROVEMENTS_BACKLOG.md` in the superproject.
|
||
|
||
---
|
||
|
||
## When you would not use this node
|
||
|
||
| Scenario | Use instead |
|
||
|:---|:---|
|
||
| A single pump | Wire `rotatingMachine` directly under your parent. MGC's combinatorics + totals add no value below N=2. |
|
||
| Valves (no curve, no FSM-driven motor) | `valveGroupControl`. MGC's optimizer assumes a flow-vs-pressure characteristic. |
|
||
| Pumps behind independent headers | Multiple MGCs (one per header), each parented to its own logical aggregator. The equaliser assumes a shared discharge / suction pressure. |
|
||
| Curve-less assets | Without a curve, `optimalControl` excludes the machine from every combination; the dispatch loop falls into the empty-set branch and warns each tick. |
|
||
| Mixed compressor + pump groups | The optimizer is curve-agnostic in principle, but the η = (Q·ΔP)/P_shaft identity used in `_optimalControl` assumes an incompressible-flow head. Use separate MGCs per phase. |
|
||
|
||
---
|
||
|
||
## Known limitations
|
||
|
||
### `maintenance` mode is in the schema but not in the dispatch switch
|
||
|
||
`config.mode.current` accepts `maintenance` as a valid value (per the schema enum), but `_runDispatch`'s mode switch only handles `optimalcontrol` and `prioritycontrol`. Picking `maintenance` will log `'maintenance' is not a valid mode.` on every demand. Treated as schema-vs-code drift, not a runtime bug.
|
||
|
||
### `priorityControl` bypasses the movement planner
|
||
|
||
`equalFlowControl` (the priority-mode strategy) still uses the legacy direct-dispatch path:
|
||
|
||
```js
|
||
await Promise.all(flowDistribution.map(async ({ machineId, flow }) => {
|
||
if (flow > 0) {
|
||
await machine.handleInput('parent', 'flowmovement', ...);
|
||
if (currentState === 'idle') await machine.handleInput('parent', 'execsequence', 'startup');
|
||
} else { ... shutdown ... }
|
||
}));
|
||
```
|
||
|
||
The planner is only wired through `optimalControl`. Consequence: priority-mode transitions can show a flow dip while one pump warms up and another keeps spinning. Tracked for a future pass; the planner's API is mode-agnostic so the surgery is straightforward when priorities allow.
|
||
|
||
### `mgc.scaling` is undefined
|
||
|
||
The orchestrator no longer carries a `scaling` field — `set.demand` is unit-self-describing per message. The `io/output.js` formatter still references `mgc.scaling`, which always reads `undefined`. The status-badge cosmetically displays `norm`. This is a leftover artifact of the pre-refactor design; harmless, scheduled for removal.
|
||
|
||
### Group efficiency naming — `maxEfficiency` is the **mean**, not the peak
|
||
|
||
`GroupEfficiency.calcGroupEfficiency` returns `{ maxEfficiency, lowestEfficiency }`. `maxEfficiency` is the **mean cog** across all machines, not the maximum. The name is preserved for behavioural parity with the pre-refactor code; callers using it as "the peak" will over-estimate the BEP target. Tracked — rename is a follow-up.
|
||
|
||
### `calcAbsoluteTotals` implicit pressure coupling
|
||
|
||
`TotalsCalculator.calcAbsoluteTotals` iterates a machine's `predictFlow.inputCurve` and re-indexes the SAME pressure key into `predictPower.inputCurve`. If the two curves were sampled at different pressures the lookup is `undefined` and the call throws. Mitigation deferred to the rotatingMachine curveLoader pass (P5).
|
||
|
||
### Power-cap parameter has no canonical topic
|
||
|
||
`handleInput(source, demand, powerCap)` accepts a `powerCap` argument and threads it to `validPumpCombinations`, but there is no `set.power-cap` topic in `commands/index.js`. Only programmatic callers can set it. Tracked.
|
||
|
||
### Per-pump fan-out not on Port 0
|
||
|
||
MGC's Port 0 carries the group aggregate only (`atEquipment_predicted_flow`, `headerDiffPa`, etc.). If you want per-pump trends on a dashboard you must wire each `rotatingMachine`'s Port 0 separately. By design — the alternative would put N × M fields on the MGC payload.
|
||
|
||
### Curve-less members silently drop out
|
||
|
||
`combinatorics/pumpCombinations.validPumpCombinations` filters by FSM state and mode but not by curve presence. A machine with `predictFlow === null` (because its curve loader failed at startup) has `currentFxyYMin / Max = 0`, so its contribution to subset envelopes is zero. It can still appear in subsets — the optimizer just gives it zero flow. The drop-out is silent; the only signal is the curve-loader's error log at startup.
|
||
|
||
---
|
||
|
||
## Open questions (tracked)
|
||
|
||
| Question | Where it lives |
|
||
|:---|:---|
|
||
| Should the planner ever decline a combination when the slowest startup exceeds an SLA on demand spikes? | [machineGroupControl#1](https://gitea.wbd-rd.nl/RnD/machineGroupControl/issues/1) |
|
||
| Wire the movement planner through `priorityControl` | Internal — not yet ticketed |
|
||
| Remove the `mgc.scaling` artifact + the `scaling` badge field | Internal |
|
||
| Rename `maxEfficiency` → `meanGroupCog` in `GroupEfficiency` | Internal |
|
||
| Decline-and-fall-back vs always-commit on planner level | Same as the Gitea issue above |
|
||
|
||
---
|
||
|
||
## Migration notes
|
||
|
||
### From pre-planner
|
||
|
||
The MGC's `_optimalControl` used to fan commands out inline (lines 226–239 in `26e92b5^`):
|
||
|
||
```js
|
||
await Promise.all(Object.entries(this.machines).map(async ([id, machine]) => {
|
||
if (flow > 0) {
|
||
await machine.handleInput('parent', 'flowmovement', ...);
|
||
if (state === 'idle') await machine.handleInput('parent', 'execsequence', 'startup');
|
||
} else if (ACTIVE_STATES.has(state)) {
|
||
await machine.handleInput('parent', 'execsequence', 'shutdown');
|
||
}
|
||
}));
|
||
```
|
||
|
||
That code is gone. The new path: build profiles → `scheduler.plan` → `executor.replan` → `await executor.tick()` (synchronous first tick) → `setInterval(1000)` for the rest. The flow / power numbers and the optimizer's pick are unchanged; only the **timing** of the per-pump commands changed.
|
||
|
||
If your test fixture relied on commands firing inline during `_runDispatch`, the new behaviour fires `fireAtTickN=0` commands synchronously inside the first `await executor.tick()` and later ones on the wall-clock interval. Tests that asserted exact timing should use the `executor.schedule()` introspection getter.
|
||
|
||
### From pre-unit-self-describing demand
|
||
|
||
The old `set.scaling` topic and its persistent `scaling.current` config field have been removed. Each `set.demand` now carries its own unit context:
|
||
|
||
| Pre | Post |
|
||
|:---|:---|
|
||
| `set.scaling = "absolute"`; `set.demand = 80` | `set.demand = {value: 80, unit: "m3/h"}` |
|
||
| `set.scaling = "normalized"`; `set.demand = 50` | `set.demand = 50` (bare number = %) |
|
||
| `set.scaling = "absolute"`; `set.demand = 0.022` (m³/s) | `set.demand = {value: 0.022, unit: "m3/s"}` |
|
||
|
||
Old flows that still send `set.scaling` will silently ignore it; the topic is no longer registered.
|
||
|
||
### From `prioritypercentagecontrol`
|
||
|
||
The mode `prioritypercentagecontrol` was retired with the unit-self-describing refactor. Use `priorityControl` with absolute-unit `set.demand` payloads, or `optimalControl` with the same.
|
||
|
||
---
|
||
|
||
## Related pages
|
||
|
||
| Page | Why |
|
||
|:---|:---|
|
||
| [Home](Home) | Intuitive overview |
|
||
| [Reference — Contracts](Reference-Contracts) | Topic + config + child filters |
|
||
| [Reference — Architecture](Reference-Architecture) | Code map, dispatch lifecycle, planner internals |
|
||
| [Reference — Examples](Reference-Examples) | Shipped flows + debug recipes |
|
||
| [rotatingMachine — Limitations](https://gitea.wbd-rd.nl/RnD/rotatingMachine/wiki/Reference-Limitations) | The child's own limitations (drift, multi-parent, virtual-child stale data) |
|