@@ -235,7 +235,7 @@
|
||||
"description": "Unit used for level related setpoints and thresholds."
|
||||
}
|
||||
},
|
||||
"heightInlet": {
|
||||
"inflowLevel": {
|
||||
"default": 2,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
@@ -243,7 +243,7 @@
|
||||
"description": "Height of the inlet pipe measured from the basin floor (m)."
|
||||
}
|
||||
},
|
||||
"heightOutlet": {
|
||||
"outflowLevel": {
|
||||
"default": 0.2,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
@@ -251,7 +251,7 @@
|
||||
"description": "Height of the outlet pipe measured from the basin floor (m)."
|
||||
}
|
||||
},
|
||||
"heightOverflow": {
|
||||
"overflowLevel": {
|
||||
"default": 2.5,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
@@ -433,36 +433,28 @@
|
||||
}
|
||||
},
|
||||
"levelbased": {
|
||||
"minLevel": {
|
||||
"default": 1,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "Below this level the MGC shuts down all pumps (unconditional stop). Above dryRunLevel (safety), below startLevel (DEAD ZONE)."
|
||||
}
|
||||
},
|
||||
"startLevel": {
|
||||
"default": 1,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "start of pump / group when level reaches this in meters starting from bottom."
|
||||
"description": "Level at which the pump demand ramp begins at 0 %. Demand scales linearly from startLevel (0 %) to maxLevel (100 %)."
|
||||
}
|
||||
},
|
||||
"stopLevel": {
|
||||
"default": 1,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "stop of pump / group when level reaches this in meters starting from bottom"
|
||||
}
|
||||
},
|
||||
"minFlowLevel": {
|
||||
"default": 1,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "min level to scale the flow lineair"
|
||||
}
|
||||
},
|
||||
"maxFlowLevel": {
|
||||
"maxLevel": {
|
||||
"default": 4,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "max level to scale the flow lineair"
|
||||
"description": "Level at which the pump demand saturates at 100 %. Above this, demand stays clamped."
|
||||
}
|
||||
}
|
||||
},
|
||||
@@ -638,14 +630,6 @@
|
||||
"description": "Volume percentage below which dry run protection activates."
|
||||
}
|
||||
},
|
||||
"dryRunDebounceSeconds": {
|
||||
"default": 30,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "Time the low-volume condition must persist before dry-run protection engages (seconds)."
|
||||
}
|
||||
},
|
||||
"enableOverfillProtection": {
|
||||
"default": true,
|
||||
"rules": {
|
||||
@@ -662,14 +646,6 @@
|
||||
"description": "Volume percentage above which overfill protection activates."
|
||||
}
|
||||
},
|
||||
"overfillDebounceSeconds": {
|
||||
"default": 30,
|
||||
"rules": {
|
||||
"type": "number",
|
||||
"min": 0,
|
||||
"description": "Time the high-volume condition must persist before overfill protection engages (seconds)."
|
||||
}
|
||||
},
|
||||
"timeleftToFullOrEmptyThresholdSeconds": {
|
||||
"default": 0,
|
||||
"rules": {
|
||||
|
||||