Reference — Limitations

code-ref

Note

What valve does not do, current rough edges, and open questions. Open items live in .agents/improvements/IMPROVEMENTS_BACKLOG.md in the superproject.

Pending full node review (2026-05). Content reflects CONTRACT.md and current source only.


When you would not use this node

Scenario Use instead
A fixed-restriction orifice (no actuator, no curve) Model the deltaP externally; valve assumes a position-controlled Kv lookup.
A non-return / check valve (no motorised actuation) Don't use valve — no FSM-driven position control is exposed for this case.
A pump or compressor (rotating equipment on a QH curve) rotatingMachine — it loads a flow / power curve and predicts the operating point.
A throttling device with no known Kv curve Without asset.valveCurve or a registry-resolved model, the predictor stays empty and deltaP recomputes return null. There is no fallback hydraulic model.
A grouped valve manifold valveGroupControl — instantiate this as a child.

Known limitations

Gas-choke detection is a hard cap

hydraulicModel.js _calculateGasDeltaP caps the effective deltaP at gasChokedRatioLimit * P2_abs once the raw deltaP exceeds that threshold. The result is a discontinuous step in deltaP — chart traces show a sharp ceiling rather than a smooth choked-flow transition. The isChoked flag in hydraulicDiagnostics lets consumers detect the regime. Tracked.

Single-source pressure for the deltaP recompute

MeasurementRouter looks for pressure.measured.downstream (preferred) or pressure.predicted.downstream to feed the gas-flow formula. There is no fallback if both are missing — the hydraulic model returns null and delta_predicted_pressure simply doesn't get written. The liquid-flow path doesn't need downstream pressure. Tracked.

Multi-parent registration

Allowed but not exercised in production tests. valve overrides BaseDomain.registerChild with FluidCompatibility.registerChild, which records upstream sources and aggregates serviceType. Teardown ordering (parent gone first vs valve gone first) is not test-covered. Open question.

flowController.handleInput only gates by source, not action

The schema's mode.allowedActions is defined but flowController.handleInput only enforces isValidSourceForMode. A cmd.shutdown from a source allowed for the current mode will fire regardless of whether the schema lists execSequence in allowedActions[mode]. This differs from rotatingMachine, which gates both. TODO: confirm whether this is intentional (valve's reduced operational set) or a backlog item.

execSequence legacy umbrella

The execSequence topic (with payload.action = 'startup' | 'shutdown' | 'emergencystop') is kept alive for legacy flows. The handler demuxes to the canonical topic; the deprecation warning fires once per session. Scheduled for removal in Phase 7. Use cmd.startup / cmd.shutdown / cmd.estop instead.

data.flow payloads don't clear stale values

If a flow source stops emitting, the last-known value persists in MeasurementContainer. There is no TTL and no explicit clear topic. Workaround: send value: 0 explicitly. The deltaP recompute then writes 0 (or null if it short-circuits on flow === 0). Tracked.

Editor cosmetics don't reflect asset derivation

The editor form may still expose supplier / category / type fields even though _rejectLegacyAssetFields rejects them on save. Re-saving an old flow surfaces the legacy-fields error until each valve is re-opened and the model re-picked. Cosmetic; the registry is the source of truth.

No entermaintenance / exitmaintenance sequences out of the box

valve.json ships startup / shutdown / emergencystop / boot sequences only. maintenance is reachable via set.mode = maintenance, but there is no canned state-transition sequence for entering / leaving. rotatingMachine defines these in its own config — valve does not. TODO: confirm intentional.

Position residue handling depends on shared state machine

The residue handler that lets a mid-decel set.position re-engage cleanly lives in generalFunctions/src/state/state.js moveTo. valve inherits the behaviour but the integration test coverage is thin. The sequence-abort token mechanism (rotatingMachine, 2026-05-15) may or may not apply to valve's shutdown ramp; TODO: confirm from FlowController.executeSequence behaviour when a new set.position arrives during the pre-shutdown ramp-to-zero.


Open questions (tracked)

Question Where it lives
Gate mode.allowedActions in flowController.handleInput for parity with rotatingMachine? Internal
Add entermaintenance / exitmaintenance sequences to valve.json? Internal
Multi-parent teardown ordering Internal
Add an explicit data.clear-flow topic for stale flow cleanup Internal
Smooth choked-flow transition instead of a hard cap hydraulicModel.js
Does the sequence-abort token mechanism (rotatingMachine, 2026-05-15) apply to valve's pre-shutdown ramp? Internal — flagged in Architecture
Phase 7 removal of execSequence umbrella + legacy aliases Internal
calculationMode (low / medium / high) — does the dispatch path consult it? valve.json schema vs source

Migration notes

From pre-AssetResolver

Old flows saved with supplier, category, or assetType fields will throw on deploy:

valve: legacy asset field(s) [supplier, category] are saved on this node.
After the AssetResolver refactor these are derived from the model id.
Open the node in the editor, re-select the model, and save to migrate.

The fix is mechanical: open each valve node, re-pick the model from the asset menu, save. No data is lost — the registry has the same supplier / category / type the old flow carried.

From inline valveCurve only

valve still supports asset.valveCurve as a fully inline curve fallback when no asset.model is set. The predictor logs which (densityKey, diameterKey) lane of the dataset it selected. If you migrate from inline-only to a registry-resolved model, the curve may pick a slightly different lane and your operating-point predictions will shift — review on the dashboard before declaring done.

From setpoint topic name (pre-canonical)

The old topic without a set. prefix has been retired. Use set.position (alias execMovement) for position setpoints.


Page Why
Home Intuitive overview
Reference — Contracts Topic + config + child filters
Reference — Architecture Code map, FSM, hydraulic-model pipeline
Reference — Examples Shipped flows + debug recipes
valveGroupControl — Limitations Where the parent's aggregator sits