governance + unit-self-describing demand + dashboard fixes
Two governance items from the 2026-05-14 quality review:
- test/_output-manifest.md enumerates every Port 0/1/2 key MGC emits, its
source, type, range, and which tests cover it in populated/degraded states
(per .claude/rules/output-coverage.md).
- src/control/strategies.js extracts computeEqualFlowDistribution as a pure
function so the equal-flow algorithm is testable without an MGC fixture.
test/basic/equalFlowDistribution.basic.test.js (6 tests) covers all three
demand branches and pins the legacy quirk where the default branch counts
active machines but iterates priority-ordered first-N (documented in the
test so the future cleanup is a deliberate change).
Plus rolled-up session work that landed alongside:
- set.demand is now unit-self-describing ({value, unit:'m3/h'|'l/s'|'%'|...}
or bare number = %); setScaling/scaling.current removed from MGC, commands,
editor (mgc.html), specificClass.
- _optimalControl + equalFlowControl now compute eta = (Q*dP)/P_shaft rather
than Q/P, keeping the metric in the same scale as each child's cog.
- groupEfficiency.calcRelativeDistanceFromPeak returns undefined (was 1) when
pumps are homogeneous (|max-min| < 1e-9). Dashboard treats undefined as
'-' instead of showing a misleading 100% / 0% reading.
- examples/02-Dashboard.json: auto-init inject so the dashboard populates at
deploy, NCog formatter normalizes the SUM emitted by MGC by
machineCountActive, Q-H fanout trims the flat-Q tail so the H axis isn't
stretched to 40m by curve-envelope clamp points, num/pct treat null AND
undefined as no-data (closes the +null === 0 trap).
- new test/integration/dashboard-fanout.integration.test.js (17 tests),
bep-distance-demand-sweep.integration.test.js (3 tests),
group-bep-cascade.integration.test.js -- total suite now 108/108 green.
- .gitignore: wiki/test.gif (143 MB screen recording, kept locally only).
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
@@ -44,7 +44,7 @@ function groupConfig() {
|
||||
return {
|
||||
general: { logging: { enabled: false, logLevel: 'error' }, name: 'station' },
|
||||
functionality: { softwareType: 'machinegroup', role: 'groupcontroller' },
|
||||
scaling: { current: 'absolute' },
|
||||
// No scaling field — handleInput always takes canonical m³/s post-refactor.
|
||||
mode: { current: 'optimalcontrol' }
|
||||
};
|
||||
}
|
||||
@@ -139,7 +139,6 @@ test('machineGroupControl vs naive baselines — real curves, verified flow', as
|
||||
|
||||
// Run machineGroupControl optimalControl with absolute scaling
|
||||
mg.setMode('optimalcontrol');
|
||||
mg.setScaling('absolute');
|
||||
mg.calcAbsoluteTotals();
|
||||
mg.calcDynamicTotals();
|
||||
await mg.handleInput('parent', Qd);
|
||||
@@ -196,7 +195,6 @@ test('machineGroupControl vs naive baselines — real curves, verified flow', as
|
||||
injectPressure(m);
|
||||
}
|
||||
mg.setMode('optimalcontrol');
|
||||
mg.setScaling('absolute');
|
||||
mg.calcAbsoluteTotals();
|
||||
mg.calcDynamicTotals();
|
||||
await mg.handleInput('parent', Qd);
|
||||
|
||||
Reference in New Issue