feat(dashboardapi): recursive subtree discovery + measurement-name/template parity

Generate dashboards for an entire parent-child subtree from a single root
registration (pre-order, cycle/diamond-safe), so wiring only the subtree root
(e.g. pumpingStation) to dashboardAPI yields dashboards for every descendant.

Fix two contract drifts that left generated panels blank against live telemetry:
- _measurement var now mirrors outputUtils.formatMsg (general.name ||
  <softwareType>_<id>); previously it always used the fallback form, so any
  named node's dashboard queried a non-existent series.
- pumpingStation template field keys realigned to emitted telemetry
  (flow.*.{upstream,out,overflow}, netFlowRate.measured, inflowLevel/
  outflowLevel/overflowLevel, maxVolAtOverflow/minVolAt{Inflow,Outflow}).

Adds template alias resolution (softwareType -> shared template file) and
locks parity with slice44/45/46 tests + output manifest. 67/67 pass.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
This commit is contained in:
znetsixe
2026-05-27 09:45:37 +02:00
parent dc08c85409
commit 990a8c09ea
7 changed files with 357 additions and 80 deletions

View File

@@ -453,7 +453,7 @@
},
"targets": [
{
"query": "from(bucket: \"${bucket}\")\n |> range(start: v.timeRangeStart, stop: v.timeRangeStop)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and r._field =~ /^netFlowRate\\.predicted\\.atequipment/)\n |> aggregateWindow(every: v.windowPeriod, fn: mean, createEmpty: false)",
"query": "from(bucket: \"${bucket}\")\n |> range(start: v.timeRangeStart, stop: v.timeRangeStop)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and r._field =~ /^netFlowRate\\.(predicted|measured)\\.atequipment/)\n |> aggregateWindow(every: v.windowPeriod, fn: mean, createEmpty: false)",
"refId": "A"
}
],
@@ -500,7 +500,7 @@
},
"targets": [
{
"query": "from(bucket: \"${bucket}\")\n |> range(start: v.timeRangeStart, stop: v.timeRangeStop)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and r._field =~ /^flow\\.(predicted|measured)\\.atequipment/)\n |> aggregateWindow(every: v.windowPeriod, fn: mean, createEmpty: false)",
"query": "from(bucket: \"${bucket}\")\n |> range(start: v.timeRangeStart, stop: v.timeRangeStop)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and r._field =~ /^flow\\.(predicted|measured)\\.(upstream|in|out|overflow)/)\n |> aggregateWindow(every: v.windowPeriod, fn: mean, createEmpty: false)",
"refId": "A"
}
],
@@ -562,7 +562,7 @@
},
"targets": [
{
"query": "from(bucket: \"${bucket}\")\n |> range(start: -7d)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and (r._field==\"heightInlet\" or r._field==\"heightOverflow\" or r._field==\"volEmptyBasin\"))\n |> last()",
"query": "from(bucket: \"${bucket}\")\n |> range(start: -7d)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and (r._field==\"inflowLevel\" or r._field==\"outflowLevel\" or r._field==\"overflowLevel\" or r._field==\"heightBasin\"))\n |> last()",
"refId": "A"
}
],
@@ -613,7 +613,7 @@
},
"targets": [
{
"query": "from(bucket: \"${bucket}\")\n |> range(start: -7d)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and (r._field==\"maxVol\" or r._field==\"minVol\" or r._field==\"maxVolOverflow\" or r._field==\"minVolOut\" or r._field==\"minVolIn\"))\n |> last()",
"query": "from(bucket: \"${bucket}\")\n |> range(start: -7d)\n |> filter(fn:(r) => r._measurement==\"${measurement}\" and (r._field==\"maxVol\" or r._field==\"minVol\" or r._field==\"maxVolAtOverflow\" or r._field==\"minVolAtOutflow\" or r._field==\"minVolAtInflow\"))\n |> last()",
"refId": "A"
}
],