#!/usr/bin/env node
/**
* Add initial volume calibration inject nodes to the demo flow.
*
* Problem: All 3 pumping stations start with initial volume = minVol,
* which is below the dryRun safety threshold. This causes the safety
* guard to trigger immediately on every tick, preventing normal control.
*
* Fix: Add inject nodes that fire once at deploy, sending
* calibratePredictedVolume to each PS with a reasonable starting volume.
*
* PS West: 500m3 basin, startLevel=2.5m → start at 200m3 (level 1.6m)
* Below startLevel, pumps stay off. q_in fills basin naturally.
* PS North: 200m3 basin, flowbased → start at 100m3 (50% fill)
* PS South: 100m3 basin, manual → start at 50m3 (50% fill)
*/
const fs = require('fs');
const path = require('path');
const flowPath = path.join(__dirname, '..', 'docker', 'demo-flow.json');
const flow = JSON.parse(fs.readFileSync(flowPath, 'utf8'));
// Check if calibration nodes already exist
const existingCalib = flow.filter(n => n.id && n.id.startsWith('demo_inj_calib_'));
if (existingCalib.length > 0) {
console.log('Calibration nodes already exist:', existingCalib.map(n => n.id));
console.log('Removing existing calibration nodes first...');
for (const node of existingCalib) {
const idx = flow.findIndex(n => n.id === node.id);
if (idx !== -1) flow.splice(idx, 1);
}
}
// Find the WWTP tab for positioning
const wwtpTab = flow.find(n => n.id === 'demo_tab_wwtp');
if (!wwtpTab) {
console.error('WWTP tab not found!');
process.exit(1);
}
// Calibration configs: { ps_id, name, volume, x, y }
const calibrations = [
{
id: 'demo_inj_calib_west',
name: 'Cal: PS West → 200m3',
target: 'demo_ps_west',
volume: 200,
x: 100, y: 50,
},
{
id: 'demo_inj_calib_north',
name: 'Cal: PS North → 100m3',
target: 'demo_ps_north',
volume: 100,
x: 100, y: 100,
},
{
id: 'demo_inj_calib_south',
name: 'Cal: PS South → 50m3',
target: 'demo_ps_south',
volume: 50,
x: 100, y: 150,
},
];
let added = 0;
calibrations.forEach(cal => {
const injectNode = {
id: cal.id,
type: 'inject',
z: 'demo_tab_wwtp',
name: cal.name,
props: [
{
p: 'payload',
vt: 'num',
},
{
p: 'topic',
vt: 'str',
},
],
repeat: '',
crontab: '',
once: true,
onceDelay: '0.5',
topic: 'calibratePredictedVolume',
payload: String(cal.volume),
payloadType: 'num',
x: cal.x,
y: cal.y,
wires: [[cal.target]],
};
flow.push(injectNode);
added++;
console.log(`Added ${cal.id}: ${cal.name}${cal.target} (${cal.volume} m3)`);
});
fs.writeFileSync(flowPath, JSON.stringify(flow, null, 2) + '\n');
console.log(`\nDone. ${added} calibration node(s) added.`);