- Archived 20 pre-refactor pages to wiki/Archive/ with standard banners:
- All 6 architecture/ pages (old _loadConfig/_setupSpecificClass internals,
pre-refactor S88 hierarchy, deployment blueprint)
- All 3 sessions/ logs (Apr-07 + Apr-13 session summaries)
- findings/open-issues-2026-03.md (issues 1-5 all resolved by refactor)
- concepts/generalfunctions-api.md (missing BaseDomain/BaseNodeAdapter)
- concepts/sources-readme.md (empty PDF placeholder, never populated)
- manuals/nodes/rotatingMachine.md + measurement.md (superseded by per-repo wikis)
- Top-level SCHEMA.md, index.md, log.md, metrics.md, overview.md,
knowledge-graph.yaml (all Apr-07 snapshot, pre-refactor)
- Kept wiki/concepts/ domain pages (ASM, PID, pump-affinity, settling, etc.)
- Kept wiki/findings/ proven results (BEP, NCog, curve-non-convexity, stability)
- Kept wiki/manuals/node-red/* (FlowFuse + Node-RED runtime docs, still current)
- Kept wiki/tools/* (utility scripts)
- Updated wiki/Archive.md index with 20 rows
- Fixed wiki/Home.md: Tier 6 was wrongly marked done; corrected to pending;
Tier 9 updated to reflect 2026-05-11 in-progress wave
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2.9 KiB
2.9 KiB
title, updated
| title | updated |
|---|---|
| Metrics Dashboard | 2026-04-07 |
⚠️ ARCHIVED — pre-refactor (Tier 1–4, 2026-05)
This page describes the architecture before the platform refactor. The current page is the per-node wiki on gitea.wbd-rd.nl/RnD or Home.
Kept for historical reference only. Do not update.
Metrics Dashboard
All numbers with provenance. Source of truth: knowledge-graph.yaml.
Test Results
| Suite | Pass/Total | File | Date |
|---|---|---|---|
| rotatingMachine basic | 10/10 | test/basic/*.test.js | 2026-04-07 |
| rotatingMachine integration | 16/16 | test/integration/*.test.js | 2026-04-07 |
| rotatingMachine edge | 17/17 | test/edge/*.test.js | 2026-04-07 |
| machineGroupControl basic | 1/1 | test/basic/*.test.js | 2026-04-07 |
| machineGroupControl integration | 3/3 | test/integration/*.test.js | 2026-04-07 |
| machineGroupControl edge | 1/1 | test/edge/*.test.js | 2026-04-07 |
Performance — machineGroupControl Optimization
| Metric | Value | Source | Date |
|---|---|---|---|
| BEP-Gravitation + refinement (3 pumps, 6 combos) | 0.027-0.153ms median | benchmark script | 2026-04-07 |
| Tick loop budget used | 0.015% of 1000ms | benchmark script | 2026-04-07 |
| Max gap from brute-force optimum (1000 steps) | 0.1% | BEP Gravitation Proof | 2026-04-07 |
| Pump switching stability (5-95% sweep) | 1-2 transitions, no hysteresis | stability sweep | 2026-04-07 |
Performance — rotatingMachine Prediction
| Metric | Value | Source |
|---|---|---|
| predict.y(x) call | O(log n), effectively O(1) | predict_class.js |
| buildAllFxyCurves | sub-10ms for typical curves | predict_class.js |
| Curve cache | full caching of splines + calculated curves | predict_class.js |
Power Comparison: machineGroupControl vs Baselines
Station: 2x H05K-S03R + 1x C5-D03R-SHN1 @ ΔP=2000 mbar
| Demand | Qd (m3/h) | machineGroupControl | Spillover | Equal-all | Gap to optimum |
|---|---|---|---|---|---|
| 10% | 71 | 17.6 kW | 22.0 kW (+25%) | 23.9 kW (+36%) | -0.10% |
| 25% | 136 | 34.6 kW | 36.3 kW (+5%) | 39.1 kW (+13%) | +0.01% |
| 50% | 243 | 62.9 kW | 73.8 kW (+17%) | 64.2 kW (+2%) | -0.00% |
| 75% | 351 | 96.8 kW | 102.9 kW (+6%) | 99.6 kW (+3%) | +0.08% |
| 90% | 415 | 122.8 kW | 123.0 kW (0%) | 123.0 kW (0%) | +0.07% |
Disproven Claims
| Claim | Evidence For | Evidence Against | Date |
|---|---|---|---|
| NCog as proportional weight works | Simple implementation | Starves small pumps, overloads large ones at high demand | 2026-04-07 |
| Q/P ratio always has mid-range peak | Expected from pump physics | Monotonically decreasing at high ΔP due to affinity laws (P ∝ Q³) | 2026-04-07 |
| Equal-marginal-cost solver is optimal | KKT theory for convex curves | C5 curve is non-convex due to sparse data points (5 per pressure) | 2026-04-07 |