docs: initialize project wiki from production hardening session
12 pages covering architecture, findings, and metrics from the rotatingMachine + machineGroupControl hardening work: - Overview: node inventory, what works/doesn't, current scale - Architecture: 3D pump curves, group optimization algorithm - Findings: BEP-Gravitation proof (0.1% of optimum), NCog behavior, curve non-convexity, pump switching stability - Metrics: test counts, power comparison table, performance numbers - Knowledge graph: structured YAML with all data points and provenance - Session log: 2026-04-07 production hardening - Tools: query.py, search.sh, lint.sh Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
This commit is contained in:
34
wiki/findings/pump-switching-stability.md
Normal file
34
wiki/findings/pump-switching-stability.md
Normal file
@@ -0,0 +1,34 @@
|
||||
---
|
||||
title: Pump Switching Stability
|
||||
created: 2026-04-07
|
||||
updated: 2026-04-07
|
||||
status: proven
|
||||
tags: [machineGroupControl, stability, switching]
|
||||
sources: [nodes/machineGroupControl/test/integration/ncog-distribution.integration.test.js]
|
||||
---
|
||||
|
||||
# Pump Switching Stability
|
||||
|
||||
## Concern
|
||||
Frequent pump on/off cycling causes mechanical wear, water hammer, and process disturbance.
|
||||
|
||||
## Test Method
|
||||
Sweep demand from 5% to 95% in 2% steps, count combination changes. Repeat in reverse to check for hysteresis.
|
||||
|
||||
## Results — Mixed Station (2x H05K + 1x C5)
|
||||
|
||||
Rising 5→95%: **1 switch** at 27% (H05K-1+C5 → all 3)
|
||||
Falling 95→5%: **1 switch** at 25% (all 3 → H05K-1+C5)
|
||||
|
||||
Same transition zone, no hysteresis.
|
||||
|
||||
## Results — Equal Station (3x H05K)
|
||||
|
||||
Rising 5→95%: **2 switches**
|
||||
- 19%: 1 pump → 2 pumps
|
||||
- 37%: 2 pumps → 3 pumps
|
||||
|
||||
Clean monotonic transitions, no flickering.
|
||||
|
||||
## Why It's Stable
|
||||
The marginal-cost refinement only adjusts flow distribution WITHIN a combination — it never changes which pumps are selected. Combination selection is driven by total power comparison, which changes smoothly with demand.
|
||||
Reference in New Issue